RPS Pole-Mounted SF6 Load Break Switch(LBS)
RPS pole-mounted SF6 load break switch: 6-40.5kV, 400-1250A, lightning impulse 75-195kV, 4s short-time 20kA, making peak 50kA. For distribution-automation overhead lines.
RPS pole-mounted SF6 load break switch: 6-40.5kV, 400-1250A, lightning impulse 75-195kV, 4s short-time 20kA, making peak 50kA. For distribution-automation overhead lines.
RPS is stainless‑steel‑tank SF6‑insulated pole‑mounted load break switch with manual / motor operation, compatible with distribution‑automation controller, complete protection‑measurement‑event‑recording functions, IP67 mechanism box for wide‑temperature & high‑altitude harsh‑environment, complying with relevant IEC load‑switch standards and supporting custom full‑set solutions.
Outdoor sectionalizing vacuum load break switch for 12kV lines, enabling safe isolation of faulted sections to restore power quickly.
Manual cable-outgoing pole-mounted SF6 load break switch for 40.5kV, enabling safe, on-pole circuit interruption and isolation.
Rockwill RPS pole-mounted SF6 load break switch 38kV. KEMA type-tested, 3mm SS tank, -45°C to +85°C. Manual or motorized.
Les modes de fonctionnement manuel et motorisé sont tous deux disponibles. Il peut être associé au contrôleur RWK‑38, assurant ainsi des protections multiples, la mesure des paramètres électriques, ainsi que l'enregistrement des défauts et des événements pour l'automatisation de la distribution à distance.
Endurance mécanique de l'interrupteur principal : 5 000 manœuvres CO, sectionneur de mise à la terre : 2 000 manœuvres. Équipé d'un système de surveillance de la pression du SF6, d'une alarme de bas niveau de gaz et d'un mécanisme de protection par verrouillage à basse pression.
Courant de coupure de charge de ligne 50 A ; courant de coupure de charge de câble 40-50 A ; courant de coupure de charge de câble en condition de défaut à la terre jusqu'à 80 A.