RHB-145 Live tank SF6 gas circuit breaker
dessin · ROCKWILL

RHB-145 Live tank SF6 gas circuit breaker

RHB-145 HV circuit breaker: 145kV, 2500-4000A, lightning impulse 650/750kV, short-time 31.5-50kA, making peak 100-125kA. For 145kV HV grid switching and fault conditions.

Dernière mise à jour2026.09
LangueEnglish
FichierPDF · 315.5 KB
Live tank circuit breakerSF6 gas circuit breaker
Télécharger

Description du document

RHB‑145 is a 145 kV outdoor high‑voltage circuit breaker with robust construction, strict requirements for foundation static/dynamic load and foundation height difference. It complies with IEC 62271‑100 for high‑voltage switchgear, delivering reliable mechanical performance for outdoor power transmission projects.

Produits connexes

Questions fréquentes

Il est conforme à la norme IEC 62271‑100 relative aux appareillages à haute tension pour les applications de transport en extérieur.

Le poids unitaire est de 18000 kg. Dimensions de l'emballage 1 : 2920×700×2300 (1 pièce), 10000 kg ; Dimensions de l'emballage 2 : 1100×580×2300 (1 pièce), 8000 kg.

Charge statique de la fondation : 160 000 N ; charge horizontale dynamique de 50 000 N, charge dynamique verticale de 240 000 N (y compris le poids propre de l'équipement). La différence de hauteur de la fondation ne doit pas dépasser 2 mm.