Электр мотори аглиси

V
%
Tavsif

Elektr motorning elektr energiyasidan, shunalardan, quvvatlanish koeffitsiyentidan va samaradorlikdan qatnashadigan oqimni hisoblaydi, bu elektr tarmoq dizayni va jihoz tanlash uchun foydali.

Qo'llab-quvvatlaydi:

  • To'g'ri jarayon (DC)

  • Bir fazalı AC

  • Uch fazalı AC

Negizgi Formula

Bir fazalı: I = P / (V × PF × η)
Uch fazalı: I = P / (√3 × V × PF × η)
DC: I = P / (V × η)

Bu yerda:
I: Oqim (A)
P: Faol quvvat (kW)
V: Shuna (V)
PF: Quvvatlanish koeffitsiyenti (0.6–1.0)
η: Samaradorlik (0.7–0.96)

Misol

Uch fazalı motor: 400V, 10kW, PF=0.85, η=0.9 →
I = 10,000 / (1.732 × 400 × 0.85 × 0.9) ≈ 18.9 A