Calculate derated ampacity of low-voltage insulated conductors (≤1 kV) per IEC 60364-5-52. Accounts for ambient temperature, harmonics, multiple circuits, and parallel conductors.
The tool implements the following formula:
I_max = I_base × K_temp × K_harmonic × K_circuit × K_parallel
Where:
Note: All values are derived directly from IEC 60364-5-52 tables. No empirical assumptions.
| Method | Code | Description | Derating Factor |
|---|---|---|---|
| Open air | 1-A1 | Single conductor exposed to air | 1.0 |
| In conduit | 1-B1 | Multiple conductors in metal or PVC conduit | 0.8–0.9 |
| Buried | 1-D1 | Directly buried in soil | 0.7–0.8 |
| Trunking | 1-C1 | Multiple circuits in open tray | 0.85 |
| Underground duct | 1-E1 | Conduit in underground duct | 0.75 |
| Field | Use Case | Why It Matters |
|---|---|---|
| Industrial Plants | Motor feeders with VFDs | High harmonic content requires derating to prevent overheating |
| Data Centers | Low-voltage power distribution units (PDUs) | Multiple circuits in conduits demand accurate derating for safety |
| Commercial Buildings | Lighting and HVAC circuits | Compliance with IEC 60364 ensures fire safety and code approval |
| Renewable Energy | DC PV array to inverter cables | Long runs require careful sizing to avoid voltage drop and overheating |
| Transportation | Electric vehicle charging stations | High-current DC circuits need precise thermal management |
Higher ambient temperature reduces conductor's ability to dissipate heat. The calculator applies a correction factor from IEC 60364-5-52 Table B.52.14 to ensure temperature does not exceed insulation limits.
Harmonics increase RMS current and cause additional heating. The calculator uses THD input to apply a derating factor, typically reducing allowable current by 10–20% for high-harmonic loads.
Yes, but select 'buried' or 'direct earth' installation method and input soil thermal resistivity. Underground cables have lower heat dissipation, so ratings are significantly reduced.
'Conductors for circuit' refers to current-carrying conductors in one phase (e.g., 3 for three-phase). 'Circuits in same conduit' means multiple independent circuits sharing a duct, which increases heat buildup and requires derating.