RHD-40.5 SF6 Gas Dead tank Circuit Breaker
Zeichnung · ROCKWILL

RHD-40.5 SF6 Gas Dead tank Circuit Breaker

RHD-40.5 dead-tank SF6 circuit breaker: 40.5kV, 1600-3150A, lightning impulse 185/215kV, short-time 25-31.5kA, making peak 80-100kA. For MV grid switching and short-circuit faults.

Letzte Aktualisierung2026.09
SpracheEnglish
DateiPDF · 355.9 KB
Dead tank Circuit BreakerSF6 Gas Circuit Breaker
Herunterladen

Dokumentbeschreibung

This circuit breaker adopts self‑blast arc‑extinguishing principle, three‑phase post‑type porcelain insulator structure and pointer‑type density relay, with mechanical life up to 10 000 times and customized manufacturing available. It complies with IEC 62271‑100 and GB/T 1984 standards, featuring high safety, reliability and easy installation.

Verwandte Produkte

Häufig gestellte Fragen

Es erfüllt die Normen IEC 62271‑100 und GB/T 1984. Kundenspezifische Fertigung und Gesamtlösungen einschließlich Konstruktion, Montage und Prüfung sind verfügbar.

Nenn-SF₆-Gasdruck 0,5–0,6 MPa, jährliche Leckagerate ≤0,5 %; mechanische Lebensdauer erreicht 10 000 Schaltspiele.

Speichermotor und Steuerkreis unterstützen DC110 V / DC220 V; die integrierte Heizung ist für AC220 V ausgelegt.