In overhead distribution networks, temporary faults—such as tree branches brushing lines, lightning flashovers, or wildlife contact—account for over 70% of all faults. Tripping and locking out feeders on every brief disturbance subjects downstream customers to frequent outages and prolongs field restoration. An automatic circuit recloser addresses this challenge by rapidly interrupting fault current and automatically reclosing after a preset interval to restore power.
A recloser pairs fast arc interruption with controlled reclose attempts to distinguish transient disturbances from lasting equipment damage.
Fault Detection and Tripping: When a short circuit or ground fault occurs, built-in current sensors and a microprocessor relay detect the overcurrent and open the switch to clear the fault current.
Dead Time and Reclose Attempt: After a preset dead interval—typically ranging from hundreds of milliseconds to a few seconds—the recloser recloses. If a branch has cleared or an arc has extinguished, service resumes immediately with minimal disruption.
Lockout Isolation: If the fault persists after reclosing, the recloser repeats the sequence up to a configured shot limit (commonly one to four trips). Once that limit is reached without clearance, it classifies the event as a permanent fault and enters lockout, staying open until manual or supervisory intervention prevents repeated fault stress.