Finis Principalis: Ut capacitors et rete electricum secure et stabiliter operentur, et ut vita apparatus prolongetur.
Cum condensatores alta tensio in rete electrico ponuntur, robustus systema protectionis est necessarius. Haec solutio, fundata in normis industriales et experientia practica, praebet directiva pro configuratione key protectionis:
I. Core Electrical Parameter Protection
- Overvoltage Protection:
- Function: Ad tutandum contra damnum cumulativum dielectrici capacitoris vel instantaneam intermissionem causatam per overvoltages atmospherica (fulgura), overvoltages commutationis, et overvoltages systematis stabili.
- Configuration:
- Surge Arrester (MOA - Metal Oxide Arrester): Installatur ad finem lineae et finem neutralis bankae condensatorum, praesertim ad latus lineae et latus puncti neutralis, ut efficaciter claudat intrusionem fulgurarum et culmen overvoltages commutationis.
- Overvoltage Relay: Continuo monitorat tensionem terminalium condensatorum. Quando tensio superat valorem statutum (typice 1.1Un), trippit bankam condensatorum post moram temporalem ut preveniat operationem prolongatam overvoltages. Determinatio setting requirit considerationem comprehensivam fluctuationis permittibilis systematis.
- Overcurrent Protection:
- Function: Ad respondendum ad incrementum currentis abnormalis ex oneribus internis vel externis bankae condensatorum, vel intermissione componentis interni.
- Configuration:
- Time-Delayed Overcurrent Protection: Servit ut protectio secundaria pro protectione principalis bankae condensatorum et tractat onera systematis. Setting debet coordinari et transire inrush currents durante energization, typice statutum ad 1.5 ad 2 vices currentis nominati.
- Instantaneous Overcurrent Protection: Targetat graves faultas short-circuit et trippit instantaneo ut clarificet faultam.
- Short-Circuit Protection:
- Function: Praebet extrema celeritas clearing faultarum in casu faultarum internarum vel externarum phase-to-phase vel single-phase-to-ground involving condensatores.
- Configuration:
- Dedicated High-Voltage Fuse: Preferens protectio pro faultis internis intra unum unitatem condensatoris. Fuses instantaneo ad occurrence faultae, isolando unitatem faultam dum permitit reliquam bancam continuare operationem.
- Circuit Breaker + Relay Protection: Praebet functionem backup short-circuit protection. Coordinatio inter operationem fusi et tempora tripping circuit breaker debet assecurari.
II. Key State Monitoring and Protection
- Temperature Protection (Thermal Protection):
- Function: Praeventio explosionum vel incendiorum causatarum ab temperaturebus abnormaliter altis resultantis ex overcurrent, harmonics, ventilatione mala, senectute dielectrici interni, vel intermissione componentis (quae fortasse primo indicatur per operationem fusi).
- Configuration:
- Embedded Temperature Sensors (PTC/Pt100): Embeduntur ad puncta key heat dissipation (sicut summa capsae condensatoris) ut monitorant temperaturem internam hotspot in real-time.
- Temperature Relay / Intelligent Monitoring Unit: Accipit signales a sensoribus. Activatur quando temperatura superat limen tuto (sicut 75°C - 80°C), emitens alarmos vel commanda tripping.
- Harmonic Protection and Mitigation:
- Function: Ad suppressione "harmonic amplification" effectus in condensatoribus causatarum per harmonics systematis, quae ducunt ad severum overcurrent, overheating, et rapidum senescere apparatus.
- Configuration:
- Harmonic Monitoring Meter: Continuo monitorat Total Harmonic Distortion (THD) et contentum harmonicum individuum currentis/voltus in busbar vel circuitu condensatoris. Emitit alarmos ad abnormalitatem.
- Harmonic Filters: In ambientibus cum pollutione harmonica severa vel pro magnis bankis condensatorum, prioritate installe filter capacitor banks cum ratio reactance matching (sicut cum 6%, 13% reactors) potius quam puras compensationis bankas condensatorum. In casibus extremis, configure Active Power Filters (APF).
III. Safety Assurance and Operational Control
- Grounding Protection:
- Function: Assecurat personale et apparatus per praebendum viam efficientem pro currente faultae.
- Configuration:
- Terre reliable capsae metallica; resistencia terre debet compleri regulis.
- Unum terminus secundarii winding coil/resistor discharge debet terre.
- Installe open-delta voltage protection in systematis cum neutrales non-effectively grounded.
- Disconnecting Switch (Isolator):
- Function: Creat break visibile durante maintenance, assecurans nullum periculum back-feed et praebens punctum isolationis tuto.
- Configuration: Installe disconnecting switches cum breaks aeris visibiles ad latus fontis (latus lineae) circuit breaker. Operation debet stricto sequi mechanismum "Five-Prevention" interlocking.
- Automatic Trip Device (Interlock Protection):
- Function: Comprehensiviter determinat faultas vel conditiones operationis abnormalis ad level control systematis ad intelligent tripping.
- Configuration:
- Plures criteria (tensio, current, temperatura, signales operationis fusi, etc.) integrantur in unitatem protectionis et controlis.
- Initiat automatico logicam tripping durante conditiones abnormalis, agens circuit breaker ad operationem. Integratum in Substation Automation System (SAS).