Ⅰ. Pangunahing Mga Function & Performance
|
Parameter |
Value |
Mga Puna |
|
Nararating na Voltage |
12kV |
- |
|
Nararating na Current |
630A, 800A, 1250A, 1600A |
Pwedeng i-customize |
|
Kapangyarihan sa Pag-break ng Short-Circuit |
20kA, 25kA, 31.5kA |
Pwedeng i-customize |
|
Power-Frequency Withstand Voltage (1min) |
Tuyo: 48kV / Basa: 38kV |
Sumasang-ayon sa DL/T403 |
|
Lightning Impulse Withstand Voltage |
75kV |
- |
|
Mekanikal na Buhay |
≥10,000 operasyon |
Spring mechanism, walang langis na disenyo |
|
Short-Time Withstand Current (4s) |
31.5kA |
- |
II. Mga Application & Compatibility
|
Serye ng Cabinet |
Compatible Models |
|
Domestic Cabinets |
KYN28, KYN96, XGN series |
|
International Cabinets |
ABB ZS series |
|
Uri ng Installation: Fixed (Lateral Type) |
III. Mga Teknikal na Advantages & Innovations
IV. Mga Serbisyo ng Customization
|
Customization Item |
Options |
|
Insulation Medium |
Air-insulated / Gas-insulated (SF₆ alternative) |
|
Secondary Wiring Layout |
Front/Rear/Side wiring |
|
Special Current Ratings |
>1600A o >31.5kA designs |
|
High-altitude Adaptation |
≤2500m (derating required for higher elevations) |
V. Installation & Maintenance
VI. Typical Configurations (Examples)
|
Application Scenario |
Recommended Configuration |
Protection Target |
|
Substation Inlet Cabinet |
VSC-1250A/31.5kA + Motorized |
Main transformer short-circuit |
|
Industrial Distribution Center |
VSC-1600A/25kA + Rear Wiring |
Large motor control |
|
Commercial Complex |
VSC-800A/20kA + Front Wiring |
LV busbar segmentation |
VII. Mga Serbisyo ng Suporta
Rockwill Electric Technical Guarantee: