| برنډ | Wone Store |
| د مودل نمبر | د YJLW سری کابل های عبوری پايه بالا متقاطع شده |
| نامتوسط ولتي | 132kV |
| عدد النوى | 1-core |
| نامینال سطح مقطع | 500mm² |
| کیبل ایزولیشن سټرکچر | XLPE insulatio& Water-blocking Layer&Al Sheath&PVC sheath |
| د سیمه جوړونکي ماتريال | Al-core |
| سلسله | YJLW Series |
Overview
This product is suitable for 110-500kV power transmission and distribution system for the transmission of electrical energy, low smoke no accounting for the flame retardant performance higher than the national standard, widely used in airports, nuclear power plants, key water control projects, high-rise buildings, Chemical, metallurgy, petroleum, traffic and other flame-retardant properties demanding places.
Implementation standards
66-132kV product implementation standards: GB / T 11017 and GB / T 19666, the flame retardant properties in line with GB / T 18380 requirements;
220-500kV product implementation standards: GB / T 18890 and GB / T 19666, the flame retardant properties in line with GB / T 18380 requirements.
Name and structure
Model |
Name | |
Cu-core |
Al-core |
|
YJLW02 |
YJLLW02 |
Cross - linked polyethylene insulated, corrugated aluminum or welded corrugated aluminum sheath and polyvinyl chloride sheathed power cable. |
YJLW03 |
YJLLW03 |
Cross - linked polyethylene insulated, corrugated aluminum or welded corrugated aluminum sheath and polyethylene sheathed power cable. |
YJLW02 - Z |
YJLLW02 - Z |
Cross - linked polyethylene insulated, corrugated aluminum or welded corrugated aluminum sheath and polyvinyl chloride sheathed longitudinal water blocking power cable. |
YJLW03 - Z |
YJLLW03 - Z |
Cross - linked polyethylene insulated, corrugated aluminum or welded corrugated aluminum sheath and polyethylene sheathed longitudinal water blocking power cable. |


parameters
66KV cross-linked power cable
Nominal cross-sectional area mm² |
Diameter of conductor mm |
Nominal thickness of insulation mm |
Thickness of aluminum sheath mm |
Thickness of over sheath mm |
Approximation outer diameter mm |
Approximate Weight(kg/km) |
|||
Copper (Cu)-PVC sheath |
Copper (Cu)-PE sheath |
Aluminum (Al)-PVC sheath |
Aluminum (Al)-PE sheath |
||||||
240 |
18.5 |
13.5 |
2.0 |
4.0 |
78 |
6598 |
6281 |
5128 |
4811 |
300 |
20.7 |
13.5 |
2.0 |
4.0 |
80 |
7329 |
7003 |
5487 |
5161 |
400 |
23.5 |
13.5 |
2.0 |
4.0 |
83 |
8317 |
7979 |
5961 |
5623 |
500 |
26.5 |
13.5 |
2.0 |
4.0 |
86 |
9546 |
9194 |
6520 |
6168 |
630 |
29.8 |
13.5 |
2.0 |
4.0 |
89 |
11113 |
10748 |
7201 |
6836 |
800 |
33.8 |
13.0 |
2.0 |
4.0 |
93 |
12912 |
12534 |
7902 |
7524 |
800F |
35.0 |
13.0 |
2.0 |
4.0 |
96 |
13614 |
13180 |
8604 |
8170 |
1000F |
39.2 |
13.0 |
2.0 |
4.5 |
102 |
15844 |
15390 |
9557 |
9103 |
1200F |
42.0 |
13.0 |
2.0 |
4.5 |
106 |
17641 |
17173 |
10313 |
9845 |
| 1400F | 46.0 | 13.0 | 2.0 | 4.5 | 109 | 19771 | 19287 | 11190 | 10706 |
| 1600F | 48.6 | 13.0 | 2.0 | 4.5 | 112 | 218.06 | 21308 | 12010 | 11512 |
110KV cross-linked power cable