| Brand | Wone Store |
| Numero ng Modelo | Serye ng mataas na boltag na cross-linked cable na YJLW |
| Tensyon na Naka-ugali | 110kV |
| bilang ng core | 1-core |
| Nominal na Seksiyon | 500mm² |
| Struktura ng Insulasyon ng Kable | XLPE insulatio& Water-blocking Layer&Al Sheath&PVC sheath |
| Uri ng materyales ng konduktor | Al-core |
| Serye | YJLW Series |
Overview
Ang produktong ito ay angkop para sa 110-500kV power transmission at distribution system para sa transmisyon ng enerhiya elektriko, may mababang usok at hindi nangangailangan ng accounting para sa performance na retardant ng apoy na mas mataas kaysa sa pambansang pamantayan, malawakang ginagamit sa mga paliparan, nuclear power plants, key water control projects, mataas na gusali, chemical, metallurgy, petroleum, traffic at iba pang lugar na nangangailangan ng mahalagang properties na retardant ng apoy.
Implementation standards
66-132kV product implementation standards: GB / T 11017 at GB / T 19666, ang properties na retardant ng apoy ay sumasang-ayon sa mga requirement ng GB / T 18380;
220-500kV product implementation standards: GB / T 18890 at GB / T 19666, ang properties na retardant ng apoy ay sumasang-ayon sa mga requirement ng GB / T 18380.
Name and structure
Model |
Pangalan | |
Cu-core |
Al-core |
|
YJLW02 |
YJLLW02 |
Kable ng kapangyarihan na may cross-linked polyethylene insulation, corrugated aluminum o welded corrugated aluminum sheath at polyvinyl chloride sheathed. |
YJLW03 |
YJLLW03 |
Kable ng kapangyarihan na may cross-linked polyethylene insulation, corrugated aluminum o welded corrugated aluminum sheath at polyethylene sheathed. |
YJLW02 - Z |
YJLLW02 - Z |
Kable ng kapangyarihan na may cross-linked polyethylene insulation, corrugated aluminum o welded corrugated aluminum sheath at polyvinyl chloride sheathed longitudinal water blocking. |
YJLW03 - Z |
YJLLW03 - Z |
Kable ng kapangyarihan na may cross-linked polyethylene insulation, corrugated aluminum o welded corrugated aluminum sheath at polyethylene sheathed longitudinal water blocking. |


parametro
66KV cross-linked power cable
Nominal cross- sectional area mm² |
Diameter of conductor mm |
Nominal thickness of insulation mm |
Thickness of aluminum sheath mm |
Thickness of over sheath mm |
Approximation outer diameter mm |
Approximate Weight(kg/km) |
|||
Copper (Cu)- PVC sheath |
Copper (Cu)- PE sheath |
Aluminum (Al)- PVC sheath |
Aluminum (Al)- PE sheath |
||||||
240 |
18.5 |
13.5 |
2.0 |
4.0 |
78 |
6598 |
6281 |
5128 |
4811 |
300 |
20.7 |
13.5 |
2.0 |
4.0 |
80 |
7329 |
7003 |
5487 |
5161 |
400 |
23.5 |
13.5 |
2.0 |
4.0 |
83 |
8317 |
7979 |
5961 |
5623 |
500 |
26.5 |
13.5 |
2.0 |
4.0 |
86 |
9546 |
9194 |
6520 |
6168 |
630 |
29.8 |
13.5 |
2.0 |
4.0 |
89 |
11113 |
10748 |
7201 |
6836 |
800 |
33.8 |
13.0 |
2.0 |
4.0 |
93 |
12912 |
12534 |
7902 |
7524 |
800F |
35.0 |
13.0 |
2.0 |
4.0 |
96 |
13614 |
13180 |
8604 |
8170 |
1000F |
39.2 |
13.0 |
2.0 |
4.5 |
102 |
15844 |
15390 |
9557 |
9103 |
1200F |
42.0 |
13.0 |
2.0 |
4.5 |
106 |
17641 |
17173 |
10313 |
9845 |
| 1400F | 46.0 | 13.0 | 2.0 | 4.5 | 109 | 19771 | 19287 | 11190 | 10706 |
| 1600F | 48.6 | 13.0 | 2.0 | 4.5 | 112 | 218.06 | 21308 | 12010 | 11512 |
110KV cross-linked power cable
Nominal cross-sectional area mm² |
Diameter of conductor |
Nominal thickness of insulation |
Thickness of aluminum sheath mm |
Thickness of over sheath mm |
Approximation outer diameter mm |
Approximate Weight(kg/km) |
|||
Copper (Cu)- PVC sheath |
Copper (Cu)- PE sheath |
Aluminum (Al)- PVC sheath |
Aluminum (Al)- PE sheath |
||||||
240 |
18.5 |
19.0 |
2.0 |
4.0 |
90 |
7967 |
7599 |
6497 |
6129 |
300 |
20.7 |
18.5 |
2.0 |
4.0 |
91 |
8603 |
8230 |
6761 |
6388 |
400 |
23.5 |
17.5 |
2.0 |
4.0 |
92 |
9363 |
8986 |
7007 |
6630 |
500 |
26.5 |
17.0 |
2.0 |
4.0 |
94 |
10492 |
10106 |
7466 |
7080 |
630 |
29.8 |
16.5 |
2.0 |
4.5 |
98 |
12203 |
11766 |
8291 |
7854 |
800 |
33.8 |
16.0 |
2.0 |
4.5 |
102 |
14034 |
13583 |
9024 |
8573 |
800F |
35.0 |
16.0 |
2.0 |
4.5 |
106 |
14542 |
14073 |
9532 |
9063 |
1000F |
39.2 |
16.0 |
2.3 |
4.5 |
110 |
17054 |
16565 |
10767 |
10278 |
1200F |
42.0 |
16.0 |
2.3 |
5.0 |
114 |
19136 |
18589 |
11808 |
11261 |
1400F |
46.0 |
16.0 |
2.3 |
5.0 |
118 |
21356 |
20787 |
12775 |
12206 |
1600F |
48.6 |
16.0 |
2.3 |
5.0 |
121 |
23434 |
22849 |
13638 |
13053 |
132KV cross-linked power cable
Nominal cross-sectional area mm² |
Diameter of conductor mm |
Nominal thickness of insulation |
Thickness of aluminum sheath mm |
Thickness of over sheath mm |
Approximation outer diameter |
Approximate Weight(kg/km) |
|||
Copper (Cu)- PVC sheath |
Copper (Cu)- PE sheath |
Aluminum (Al)- PVC sheath |
Aluminum (Al)- PE sheath |
||||||
240 |
18.5 |
19.5 |
2.0 |
4.0 |
91 |
8097 |
7725 |
6627 |
6255 |
300 |
20.7 |
19.0 |
2.0 |
4.0 |
92 |
8735 |
8357 |
6893 |
6515 |
400 |
23.5 |
19.0 |
2.0 |
4.0 |
96 |
9767 |
9377 |
7411 |
7021 |
500 |
26.5 |
19.0 |
2.0 |
4.0 |
99 |
11043 |
10641 |
8017 |
7615 |
630 |
29.8 |
19.0 |
2.0 |
4.5 |
103 |
12924 |
12464 |
9012 |
8552 |
800 |
33.8 |
18.0 |
2.0 |
4.5 |
106 |
14625 |
14156 |
9615 |
9146 |
800F |
35.0 |
18.0 |
2.0 |
4.5 |
109 |
15154 |
14666 |
10144 |
9656 |
1000F |
39.2 |
18.0 |
2.3 |
4.5 |
114 |
17701 |
17194 |
11414 |
10907 |
1200F |
42.0 |
18.0 |
2.3 |
5.0 |
118 |
19809 |
19243 |
12481 |
11915 |
1400F |
46.0 |
18.0 |
2.3 |
5.0 |
122 |
22048 |
21459 |
13467 |
12878 |
1600F |
48.6 |
18.0 |
2.3 |
5.0 |
125 |
24144 |
23539 |
14348 |
13743 |
220KV cross-linked power cable
Nominal cross-sectional area mm² |
Diameter of conductor |
Nominal thickness of insulation |
Thickness of aluminum sheath mm |
Thickness of over sheath mm |
Approximation outer diameter |
Approximate Weight(kg/km) |
|
Copper (Cu)- PVC sheath |
Copper (Cu)- PE sheath |
||||||
400 |
23.5 |
27.0 |
2.4 |
5.0 |
116 |
13141 |
12504 |
500 |
26.5 |
27.0 |
2.4 |
5.0 |
119 |
14515 |
13860 |
630 |
29.8 |
26.0 |
2.4 |
5.0 |
121 |
15887 |
15225 |
800 |
33.8 |
25.0 |
2.4 |
5.0 |
124 |
17683 |
17004 |
800F |
35.0 |
25.0 |
2.4 |
5.0 |
127 |
18285 |
17586 |
1000F |
39.2 |
24.0 |
2.6 |
5.0 |
130 |
20519 |
19805 |
1200F |
42.0 |
24.0 |
2.6 |
5.0 |
134 |
22490 |
21752 |
1400F |
46.0 |
24.0 |
2.6 |
5.0 |
137 |
24759 |
24001 |
1600F |
48.6 |
24.0 |
2.6 |
5.0 |
140 |
26920 |
26144 |
1800F |
52.0 |
24.0 |
2.8 |
5.0 |
144 |
29208 |
28413 |
2000F |
55.2 |
24.0 |
2.8 |
5.0 |
148 |
31602 |
30783 |
500KV cross-linked power cable
Nominal cross-sectional area mm² |
Diameter of conductor mm |
Nominal thickness of insulation mm |
Thickness of aluminum sheath mm |
Thickness of over sheath mm |
Approximation outer diameter |
Approximate Weight(kg/km) |
|
Copper(Cu)- PVC sheath |
Copper (Cu)- PE sheath |
||||||
800 |
33.8 |
34.0 |
2.9 |
6.0 |
150 |
20393 |
19688 |
800F |
35.0 |
34.0 |
2.9 |
6.0 |
152 |
20772 |
20047 |
1000F |
39.2 |
33.0 |
3.0 |
6.0 |
154 |
23057 |
22317 |
1200F |
42.0 |
33.0 |
3.0 |
6.0 |
158 |
25068 |
24310 |
1400F |
46.0 |
32.0 |
3.0 |
6.0 |
160 |
27419 |
26640 |
1600F |
48.6 |
32.0 |
3.1 |
6.0 |
163 |
29679 |
28876 |
1800F |
52.0 |
31.0 |
3.2 |
6.0 |
165 |
32036 |
31213 |
2000F |
55.2 |
31.0 |
3.2 |
6.0 |
169 |
34476 |
33636 |
2200F |
57.4 |
31.0 |
3.2 |
6.0 |
171 |
36318 |
35464 |
2500F |
61.5 |
31.0 |
3.3 |
6.0 |
175 |
39548 |
38671 |
800 |
33.8 |
34.0 |
2.9 |
6.0 |
150 |
20393 |
19688 |
Gamit ang mga tampok
1、Pinakamataas na temperatura na inirerekomenda
Panahon ng matagal na pinakamataas na pinapayagang temperatura ng pag-operate ng conductor: 90 ℃, Pinakamataas na temperatura ng pag-operate sa maikling panahon ng overload: 105 90 ℃, Pinakamataas na temperatura ng pag-operate sa short circuit (ang haba ng oras ng short circuit ay 5 s): 250 ℃
2、Mga pangangailangan sa pag-install
Ang pag-lay ng kable ay hindi dapat maging limitado sa taas ng pagbagsak; ang temperatura ng kapaligiran para sa pag-lay ay hindi dapat mas mababa sa 0 90 ℃; C, at kung ang temperatura ng kapaligiran ay mas mababa sa 0 90 ℑ, ang kable ay dapat pre-heated.
2.1Pinakamaliit na radius ng pagbend ng kable
Sa panahon ng pag-lay ng kable: 20D0; at Permanenteng pag-install: 15D0.
Note: D0 ay sukat ng labas na diameter ng kable.
2.2Pinakamataas na pinapayagang axial traction para sa pag-install ng kable, T (radial side pressure sa bend na hindi isinasaalang-alang)
Conductor: T=K x Conductor section (kg)
Aluminum sheath:T x Aluminum sheath section(kg)
Kung saan, ang coefficient K=7kg/mm2para sa copper conductor at 4kg/mm2 para sa aluminum conductor at 2kg/mm2 para sa aluminum sheath.
2.3Pinakamataas na pinapayagang side pressure kapag ang kable ay nabend, P
P=T/R≤500(kg/m), kung saan T ay axial traction, at R ay radius ng pagbend.