| Marke | Switchgear parts |
| Numru tal-Model | Modular UpS sors ta' l-enerġija mhux miftuħa |
| Rated frequency | 50/60Hz |
| volt tal-aħjar | 380/400/415VAC |
| Ingħaddi dħul | 380/400/415VAC |
| kapasità | 300kVA |
| Siri | HBM |
Il-HBM50-600KW huwa l-aħħar ġenerazzjoni ta’ UPS moduljar tat-tliet flit-tlet li ġiet lanġasata mill-kompanija tagħna. Il-prodott jadoper kontrollo diġitali, dissenju moduljar, u teknoloġija ta’ ridondanza parallela N+X, li tigħaddim il-maqsimgħa tecnika ta’ l-aħħar fil-fieqer tal-elettronika tal-enerġija u tal-kontroll awtomatiku. Huwa prodott standard fil-fieqer tal-UPS moduljar.
Il-kapaċita tal-prodott tkoppja sivvijiet diversi bejn 50kW u 600kW, li jgħin lil l-utenti jikkonfiguraw u jinvestjaw b’mudanza. Tista’ tirran 4 mašini paralleli sa 2400kW.
Karatteristiċi tal-prodott
Speċifikazzjonijiet Tekniki
Kull parte tal-arċitettrura hi miktrola digitalment, bl-iżmir għal prestazzjoni tajba u stabilità sistemaalta. Ikkun jidher bi kapabbiltajiet ta’ protezzjoni u diagnosu tad-difetti, waqt li jiviti r-riskju ta’ falliment tal-apparat analoġiku, li jgħin li l-sistema ta’ kontrollo tkun aktar stabili u fidati.
Biex jintużaw it-teknika avviżata tal-trilivel, l-effiċjenza kompletta tal-mašina hija sa 96%.
Dissenju ta’ dennisità tan-enerġija alta, modulu singol 50KW (L x P x A) 440 x 620 x 130mm.
Il-mixxi jistgħu jiġu kollegati mal-last minn karrikatur mhux bilanċati. Meta l-mixxi jiġu kollegati mal-last minn karrikatur mhux bilanċati, il-kurrenti tal-input huma bilanċati fit-tliet fasi, li jgħin li l-każ tal-last tal-grid tal-tliet fasi tkun bilanċata.
fidabilità għoli
Id-disenju ta’ ridondanza parallela N+X jasegura disponibbiltà tas-sistema ta’ 99.999% u MTBF ta’ aktar minn 250,000 siegħ, li jisoddisfa l-ħafien ta’ fidabilità għoli tal-karrikatur kritika fuq is-sistema tan-enerġija; Is-setting tal-ridondanza parallela fleksibbli jgħin tas-sistema tafforni l-kapaċita mixsima tal-output.
Ridondanza parallela tas-sistema ta’ kontrollo, mid-disenju ta’ kontrollo distributu u managemenċ konċentrat; L-unità ta’ kontrollo konċentrata ikollha kollegata b’mod ridondanti, u l-falliment ta’ wahda minnhom ma jeffeċċja lill-operażjoni ollverali tal-mašina; Il-kabinet distributu optimitzat jasegura s-sigurtà tal-kollegament parallelu tas-sistema.
Il-modulu ta’ monitoraġġ konċentrata għandu funzjonalità ta’ hot swappable. Meta l-modulu ta’ monitoraġġ jiġi skollegat, is-sistema tista’ topera normalment permezz tal-forz tal-bypass konċentrata, li jgħin li s-sigurtà tal-forz tal-bypass tkun ażżeljata.
Funzjonalità EPO, inpressja buton EPO fi situazzjonijiet emergenza biex issit tasswifa; Id-disenju tal-buton EPO huwa għall-protezzjoni u jgħamel funzjunalità ta’ tasswifa emergenza remote (REPO) biex jippreveni l-operazzjonijiet mgħarrajja.
Fleksibbli u kemm huwa sewwi
Disenju moduljar, magħmul minn 1 sa 12 moduli kollegati b’mod parallelu, b’kapaċita massima ta’ 600kW. L-utenti jistgħu jżidu l-ammont tal-moduli b’fleksibilità; Permezz tal-teknika ta’ hot swappable, il-moduli jistgħu jiġu żidu u skollegaw online, biex jagħmlu "żero" ftit ta’ manutenzjoni.
It-taqsam tal-manutenzjoni huwa qasir. In-numru tal-moduli difettivi huwa inferjuri jew daqs in-numru tal-moduli ridundanti, u l-ftit ta’ manutenzjoni huwa "żero"; In-numru tal-moduli difettivi huwa superjuri għal in-numru tal-moduli ridundanti tal-UPS, u l-ftit ta’ manutenzjoni ma jikkarja l-5 minuti.
Il-display ta’ touchscreen tal-kolor tal-LCD tal-kabinet jafforna informazzjoni riċa dwar l-istat tal-UPS, l-informazzjoni tal-avvertiment, l-informazzjoni tad-difetti, etc; Il-display tal-LED ta’ modulu singol, l-utenti jistgħu jafu l-istat ta’ xogħol tal-modulu permezz tal-lumijiet tal-LED tal-modulu.
Fi situazzjonijiet emergenza, l-UPS tista’ tiftaħ lil forz tal-bypass għal manutenzjoni, u l-personal tal-manutenzjoni jistgħu joperaw riparazzjonijiet online b’sigurtà.
diseñ intelligenza
Il-kurrenti tal-ħarġ jistgħu jiġu settati, u l-kapaċita tal-batteriji konfiguratih mil-utent u l-kurrenti tal-ħarġ jistgħu jiġu settati permezz tal-LCD tal-panel biex jirrealizzaw is-silġ automaticament bejn modi ta’ ħarġ kostanti, modi ta’ ħarġ kostanti, u modi ta’ ħarġ floating.
Metodu ta’ ħarġ intelligenza, adoperant it-teknika avviżata tal-ħarġ bi tre stadi, jistgħu jieffettivament bilanċjaw l-obiettivi ta’ ħarġ veloċi u l-estensjoni ta’ l-ewwel tal-batteriji, jisparmja l-investiment tal-utent fis-sistema tal-batteriji.
Jaffornaw varjetà kbira ta’ opzjonijiet, inkluż trasformaturi ta’ isolazzjoni, pannelli ta’ distribuzzjoni, karti SNMP, karti ta’ kontatt tad-dry relay, etc., biex jissostanzjaw sisem ta’ distribuzzjoni żgħir u medju.
Diseñ Verde
Biex jintużaw il-kabinet standard ta’ 19 colli, huwa jmatcha perfettament l-ambjent tal-applikazzjoni tal-room tal-komputatur u jsalva l-area utilizzabile tal-room tal-komputatur.
Isharing tal-batteriji parallelament jidher drastikament in-numru tal-konfigurazzjonijiet tal-batteriji, li jgħin lill-utenti jkonfiguraw l-batteriji b’mudanza bażita fuq it-temps tal-backup.
In-numru tal-batteriji esterni huwa opzjonali, u l-utenti jistgħu jagħżlu 30/32/34/36/38/40/42/44/46/48/50 celli (30-50 celli huma opzjonali) skond il-beħrin tagħhom.
Speċifikazzjonijiet Tekniki
| Model | HBM90-30 | HBM150-30 | HBM300-30 |
|---|---|---|---|
| Capacity | |||
| UPS Cabinet | 30-90kVA | 30-150KVA | 30-300KVA |
| Power Module | 30kVA | 30kVA | 30kVA |
| Input | |||
| Input Mode | Three-phase Four-wire + Ground | ||
| Rated Voltage | 380/400V/415Vac | ||
| Voltage Range | 208~478Vac | ||
| Frequency Range | 40~70Hz | ||
| Power Factor | ≥0.99 | ||
| Bypass Range | 380 upper limit: 25% (optional +10%, +15%, +20%)
|
||
| Input Current Harmonic | ≤3% (100% Non-linear Load) | ||
| Output | |||
| Output Mode | Three-phase Four-wire + Ground | ||
| Rated Voltage | 380/400V/415Vac | ||
| Power Factor | 0.9 or 1 | ||
| Voltage Accuracy | ±1% | ||
| Output Frequency | |||
| Mains Mode | Synchronous with input; when mains frequency exceeds maximum ±10% (can be set to ±1%, ±2%, ±4%, ±5%), output frequency is 50×(±0.2%)Hz | ||
| Battery Mode | (50/60±0.2%)Hz | ||
| Load Crest Factor | 3:1 | ||
| Switching Time | Mains mode to bypass mode: 0ms (tracking); Mains mode to battery mode: 0ms | ||
| Overload Capacity | Load ≤110%, 60min; ≤125%, maintain 10min; ≤150% maintain 1min; ≥150% switch to bypass immediately | ||
| Output Voltage Harmonic | ≤2% (100% Linear Load) | ||
| Efficiency | 95% in Normal Mode | ||
| Communication Interface | RS232, RS485, 2 Intelligent Slot (Smart Card Slot), Dry Contact | ||
| Battery | |||
| Battery Voltage | ±192V±204V±216V±228V±240V DC; (32, 34, 36, 38, 40 cells optional) | ||
| Charging Current | |||
| UPS Cabinet | 30A Max. | 50A Max. | 100A Max. |
| Power Module | 10A Max. | 10A Max. | 10A Max. |
| Working Environment | |||
| Working Temperature | 0℃ ~ 40℃ | 0℃ ~ 40℃ | 0℃ ~ 40℃ |
| Relative Humidity | 0 ~ 95% non condensing | ||
| Storage Temperature | -25℃ ~ 55℃ | ||
| Altitude | < 1500m | < 1500m | < 1500m |
| Physical Characteristics | |||
| Appearance Dimensions (D×W×H) mm | |||
| Cabinet | 840 x 600 x 1400 | 840 x 600 x 1400 | 1100 x 600 x 2000 |
| Module | 580 x 443 x131 | 580 x 443 x131 | 580 x 443 x131 |
| Weight (Net Weight) Kg | |||
| Cabinet | 158 | 170 | 305 |
| Module | 30K module, 33.5KGS | ||
| Execution Standard | CE,EN/IEC 62040-2, EN/IEC 62040-1-1, YD/T1095-2008 | ||
| Model | HBM300-50 | HBM400-50 | HBM500-50 | HBM600-50 |
|---|---|---|---|---|
| Capacity | ||||
| Cabinet | 50-300KW | 50-400KW | 50-500KW | 50-600KW |
| Module | 50KW | 50KW | 50KW | 50KW |
| Maximum Number of Modules | 6 | 8 | 10 | 12 |
| Input | ||||
| Main Path Input | ||||
| Rated Input Voltage (Vac) | 380/400/415 | |||
| Input Voltage Range (Vac) | 138 ~ 485Vac | |||
| Wiring Mode | Three-phase Five-wire | |||
| Input Frequency Range (Hz) | 40-70 | |||
| Input Power Factor | ≥0.99 | |||
| Input Current Harmonic (THDi) | ≤3% (100% Linear Load) | |||
| Bypass Input | ||||
| Rated Input Voltage (Vac) | 380/400/415 | |||
| Input Voltage Range (Vac) | 220 upper limit: 25% (optional +10%, +15%, +20%) 230 upper limit: 20% (optional +10%, +15%) 240 upper limit: 15% (optional +10%) lower limit: -45% (optional -10%, -20%, -30%) | |||
| Wiring Mode | Three-phase Five-wire | |||
| Bypass Synchronous Tracking Range (Hz) | ±10% | |||
| Generator Input | Supported | |||
| Power Walking In | Supported | |||
| Bypass Reverse Feeding | Supported | |||
| Output | ||||
| Voltage (Vac) | 380/400/415±1% | |||
| Power Factor | 1 | |||
| Frequency (Hz) | ||||
| Mains Mode | ±1%/±2%/±4%/±5%/±10% (Configurable) | |||
| Battery Mode | (50/60±0.1%)Hz | |||
| Waveform | Sine Wave | |||
| Current Crest Ratio | 3:1 | |||
| Output Voltage Harmonic (THDV) | ≤2% (100% Linear Load); ≤3% (100% Non-linear Load) | |||
| Switching Time (ms) | 0 | |||
| Overall Efficiency (%) | 96 | |||
| Overload Capacity | 110% load, transfer to bypass after 60min; 125% load, transfer to bypass after 10min; 150% load, transfer to bypass after 1min | |||
| Battery | ||||
| Maximum Module Charging Current (A) | 20 | |||
| Battery Voltage | 30~50 cells optional, default 36 cells; optional voltages: ±180V/±192V/±204V/±216V/±228V/±240V/±252/±264/±276/±288/±300Vdc (30/32/34/36/38/40/42/44/46/48/50 cells) | |||
| Environment | ||||
| Working Temperature | 0℃ ~ 40℃ | |||
| Storage Temperature | —25℃ ~ 55℃ | |||
| Humidity Range | 0 ~ 95% (Non-condensing) | |||
| Working Altitude | < 1500m (Derate for use above 1500m) | |||
| Noise (1m Distance) | <68dB | <70dB | <70dB | <70dB |
| Other Functions | ||||
| Protection Functions | Short circuit, overload, over temperature, output over voltage, battery under voltage, fan fault alarm, bypass reverse feeding, lightning protection | |||
| Alarm Functions | Mains abnormality, overload, UPS fault, battery under voltage and other multiple alarm functions | |||
| Communication Functions | CAN, RS485, Network Interface, Dry Contact, Parallel Interface, LBS Interface, Smart Card Slot, Temperature Sensor Interface | |||
| Mechanical Characteristics | ||||
| Dimensions (W×D×H) | ||||
| Cabinet (mm) | 600×850×2000 | 600×850×2000 (Standard); 1200×850×2000 (Fully Loaded) | 1200×850×2000 | 1200×850×2000 |
| Module (mm) | 440×620×130 | |||
| Net Weight | ||||
| Cabinet (kg) | 260 | 280/600 | 645 | 720 |
| Module (kg) | 32 | |||
| Execution Standard | YD/T 2165-2010 | |||