| Brand | ROCKWILL |
| Series | REC |
| Rated Voltage | 12kV |
| Lightning Impulse Withstand Voltage | 75/85kV |
| Power Frequency Withstand Voltage | 42/48 kV-1m |
| Rated Frequency | 50Hz |




| Item | Unit | Parameter Value |
|---|---|---|
| Internal Arc Class (IAC) | kA/s | AFLR 20/1 |
| Partial Discharge of Complete Cabinet | pC | ≤10 (1.1Ur) |
| Protection Class - Gas Tank | - | IP67 |
| Protection Class - Complete Cabinet | - | IP41 |
| Eco-friendly Gas (Dry Air) | - | Moisture Content ≤300ppm |
| Rated Gas Pressure (20℃, Gauge Pressure) | MPa | 0.02 |
| Minimum Functional Pressure (20℃, Gauge Pressure) | MPa | 0 |
| Annual Leakage Rate | - | ≤0.05% |
| Busbar System | - | - |
| Short-time Withstand Current | kA/s | 20/4 |
| Load Break Switch | - | - |
| Rated Current | A | 630 |
| Short-circuit Making Current | kA | 50 |
| Mechanical Life of Main Switch | - | M2 10000 times |
| Mechanical Life of Three-position Disconnector | - | M1 3000 times |
| Circuit Breaker | - | - |
| Rated Current | A | 630 |
| Rated Breaking Current | kA | 20 |
| Rated Making Current | kA | 50 |
| Breaking Current of Cable Charging | A | 25 |
Absolutely not. This is a key practical improvement over traditional switchgears. Conventional switchgears rely on grease that oxidizes, dries or collects dust after long‑term standby or temperature changes, causing switching failure. Our mechanical mechanisms are specially tested for extreme long‑standby sudden operation. By simplifying components and adopting self‑lubricating oil‑free materials, the switch operates precisely even after years of inactivity. This field‑verified technology enables zero routine maintenance and lifelong trouble‑free operation.
This 12kV pure dry air insulated RMU completely eliminates SF6 greenhouse gas. It uses clean dry air for insulation and vacuum for arc extinction, achieving full zero-carbon operation. Compared with traditional SF6 products, it features non-toxic decomposition, zero gas recycling cost, lower maintenance cost and full environmental compliance for ESG and green grid projects.
The exclusive visible three-position observation window allows staff to directly check the physical state of closing, isolating and grounding, instead of relying on secondary electric signals. It eliminates signal misjudgment risk and fundamentally guarantees on-site operation safety.