| Brand | ROCKWILL |
| Numero ng Modelo | Hybrid na Gas Insulated Switchgear hanggang 145kV |
| Nararating na Voltase | 40.5kV |
| Narirating na kuryente | 2000A |
| Narirating na agos ng pagkakawaswas sa short circuit | 31.5kA |
| Serye | RHP |
Paglalarawan ng Produkto
Ang RHP type HGIS electrical apparatus ay isang bagong uri ng mataas na voltaheng kagamitan. Ito ay nagsasama ng mga kakayahan ng GIS combined electrical apparatus, tulad ng kompakto, mataas na reliabilidad, at mababang operasyon at pangangalain, habang naisipang itinatago ang busbar bilang isang regular na AIS arrangement para sa pag-install at koneksyon sa site. Ang disenyo na ito ay epektibong nanalo sa mga hadlang na may kasamang tradisyonal na kagamitan ng AIS, kasama ang malaking sukat, maraming puntos ng koneksyon, at mataas na trabaho sa pagsusuri at pangangalain.
Ito ay angkop para sa 40.5kV hanggang 145kV at ibaba transmission at distribution systems sa mga power plants, substations, railway stations, ports, at malalaking industriyal at mining enterprises. Ito ay partikular na angkop para sa mga proyektong may limitadong espasyo tulad ng mga substation sa bundok at urban substations, at maaaring i-install sa loob, labas, o sa bubong.
Mga Komponente ng Produkto

Pangunahing Katangian
Totoong Solusyon sa mga Hamon sa Operational Reliability ng Disconnector/Earthing Switches;
Advanced Self-Blast Interruption at Modular Structure para sa Mas Mataas na Reliability;
Ang pag-alis o malaking pagbawas ng disc-type insulators para sa mas mataas na reliability;
Ang aplikasyon ng specialized manufacturing techniques na binabawasan ang bilang ng flanges, kaya't minumungkahi ang potensyal para sa gas leakage;
Externally Mounted CT para sa mas mataas na seguridad at reliability;
Kompaktong Estruktura at Flexible Layout;
Relatibong mas ekonomiko kaysa sa AIS.
Teknikal na mga Parameter
RHP-40.5
N |
Item |
Unit |
Parameters |
1 |
Rated maximum voltage |
kV |
40.5 |
2 |
Rated maximum current |
A |
≤2000 |
3 |
Rated frequency |
Hz |
50/60 |
4 |
First opening pole coefficient |
|
1.5 |
5 |
Rated short circuit breaking current |
kA |
31.5 |
6 |
Rated short-circuit duration |
s |
4 |
7 |
Rated out of step breaking current |
kA |
7.9 |
8 |
Rated peak value withstand current |
kA |
80 |
9 |
Rated 1min power frequency withstand voltage (Dry/Wet) |
kV |
To ground 110 |
Break 118 |
|||
10 |
Rated lightning impulse voltage |
kV |
To ground 215 |
Break 215 |
|||
11 |
Operation sequence |
|
O-0.3s-CO-180s-CO |
12 |
Opening time |
ms |
50±10 |
13 |
Closing time |
ms |
90±20 |
14 |
Close-open time |
ms |
≤100 |
15 |
Main circuit resistance |
μΩ |
≤150 |
16 |
Rated SF6 gas pressure (20℃gauge pressure) |
Mpa |
0.5 |
17 |
Alarm/blocking pressure(20℃gauge pressure) |
Mpa |
0.45/0.4 |
18 |
SF6 annual gas leakage rate |
% |
≤0.5 |
19 |
Gas moisture content |
Ppm(v) |
≤150 |
20 |
Mechanical life |
times |
6000 |
RHP-72.5
N |
Item |
Unit |
Parameters |
1 |
Rated maximum voltage |
kV |
72.5 |
2 |
Rated maximum current |
A |
≤3150 |
3 |
Rated frequency |
Hz |
50/60 |
4 |
First opening pole coefficient |
|
1.5 |
5 |
Rated short circuit breaking current |
kA |
40 |
6 |
Rated short-circuit duration |
s |
4 |
7 |
Rated out of step breaking current |
kA |
10 |
8 |
Rated peak value withstand current |
kA |
100 |
9 |
Rated 1min power frequency withstand voltage (Dry/Wet) |
kV |
To ground 275 |
Break 315 |
|||
10 |
Rated lightning impulse voltage |
kV |
To ground 650 |
Break 750 |
|||
11 |
Operation sequence |
|
O-0.3s-CO-180s-CO |
12 |
Opening time |
ms |
32±7 |
13 |
Closing time |
ms |
85±10 |
14 |
Close-open time |
ms |
≤60 |
15 |
Main circuit resistance |
μΩ |
≤100 |
16 |
Rated SF6 gas pressure (20℃gauge pressure) |
Mpa |
0.5 |
17 |
Alarm/blocking pressure(20℃gauge pressure) |
Mpa |
0.55/0.5 |
18 |
SF6 annual gas leakage rate |
% |
≤0.5 |
19 |
Gas moisture content |
Ppm(v) |
≤150 |
20 |
Mechanical life |
times |
6000 |
RHP-145
N |
Item |
Unit |
Parameters |
1 |
Rated maximum voltage |
kV |
145 |
2 |
Rated maximum current |
A |
≤3150 |
3 |
Rated frequency |
Hz |
50/60 |
4 |
First opening pole coefficient |
|
1.5 |
5 |
Rated short circuit breaking current |
kA |
40 |
6 |
Rated short-circuit duration |
s |
4 |
7 |
Rated out of step breaking current |
kA |
10 |
8 |
Rated peak value withstand current |
kA |
100 |
9 |
Rated 1min power frequency withstand voltage (Dry/Wet) |
kV |
To ground 275 |
Break 315 |
|||
10 |
Rated lightning impulse voltage |
kV |
To ground 650 |
Break 750 |
|||
11 |
Operation sequence |
|
O-0.3s-CO-180s-CO |
12 |
Opening time |
ms |
32±7 |
13 |
Closing time |
ms |
85±10 |
14 |
Close-open time |
ms |
≤60 |
15 |
Main circuit resistance |
μΩ |
≤100 |
16 |
Rated SF6 gas pressure (20℃gauge pressure) |
Mpa |
0.5 |
17 |
Alarm/blocking pressure(20℃gauge pressure) |
Mpa |
0.55/0.5 |
18 |
SF6 annual gas leakage rate |
% |
≤0.5 |
19 |
Gas moisture content |
Ppm(v) |
≤150 |
20 |
Mechanical life |
times |
6000 |
Sukat
40.5kV

72.5kV

145kV

Ang tensyon ay nakakalapat mula 40.5kV-145kV at angkop para sa mga pangangailangan tulad ng power plants, substations, riles, pantalan, atbp. Ito ay partikular na angkop para sa mga proyekto na may limitadong espasyo tulad ng urban/mountainous substations, renovation ng mga lumang istasyon, at rooftop/mobile substations.