| Handelmerk | ROCKWILL |
| Modelnommer | Hibriede Gasgeïsoleerde Skakeltoerusting tot 145kV |
| Gedraaide Spanning | 40.5kV |
| Gedraaide stroom | 2000A |
| Gedekte korte-sirkuitverbrekingstroom | 31.5kA |
| Reeks | RHP |
Produktopsig
Die RHP-tipe HGIS-elektriese toerusting is 'n nuwe tipe hoëspanningselektriese toerusting. Dit behou die voordele van GIS-gecombineerde elektriese toerusting, soos kompaktheid, hoë betroubaarheid en lae bedryfs- en instandhoudingsvereistes, terwyl dit innoverend die buslei as 'n konvensionele AIS-uitspanning behou vir plaaslike installasie en verbinding. Hierdie ontwerp oorkom effektief die nadele geassosieer met tradisionele AIS-toerusting, insluitend groot grondspoor, talryke verbindingpunte, en hoë inspeksie- en instandhoudingswerklast.
Dit is geskik vir 40.5kV tot 145kV en onder transmissie- en verspreidingsisteme in kragstasies, transformasiesentrales, spoorwegstasies, hawens, en groot industriële en mynbouondernemings. Dit is veral geskik vir projekte met beperkte ruimte, soos bergtransformasiesentrales en stedelike transformasiesentrales, en kan binne, buite, of op dakkappe geïnstalleer word.
Produkkomponent

Hoofkenmerke
Egte Oplossing vir Operasionele Betroubaarheidsuitdagings in Afsonderaar/Aardingsskake;
Gevorderde Self-ontploffende Onderbreking en Modulaire Struktuur vir Verbeterde Betroubaarheid;
Die eliminasie of aansienlike vermindering van skotelvormige isolatoren vir verbeterde betroubaarheid;
Die toepassing van gespesialiseerde vervaardigingstegnieke vermindert die aantal flenkses, wat die potensiaal vir gaslekkage minimeer;
Buite gemonteerde CT vir verbeterde veiligheid en betroubaarheid;
Kompakte Struktuur en Buigsame Uitleg;
Relatief meer ekonomies as AIS.
Tegniese Parameters
RHP-40.5
N |
Item |
Unit |
Parameters |
1 |
Rated maximum voltage |
kV |
40.5 |
2 |
Rated maximum current |
A |
≤2000 |
3 |
Rated frequency |
Hz |
50/60 |
4 |
First opening pole coefficient |
|
1.5 |
5 |
Rated short circuit breaking current |
kA |
31.5 |
6 |
Rated short-circuit duration |
s |
4 |
7 |
Rated out of step breaking current |
kA |
7.9 |
8 |
Rated peak value withstand current |
kA |
80 |
9 |
Rated 1min power frequency withstand voltage (Dry/Wet) |
kV |
To ground 110 |
Break 118 |
|||
10 |
Rated lightning impulse voltage |
kV |
To ground 215 |
Break 215 |
|||
11 |
Operation sequence |
|
O-0.3s-CO-180s-CO |
12 |
Opening time |
ms |
50±10 |
13 |
Closing time |
ms |
90±20 |
14 |
Close-open time |
ms |
≤100 |
15 |
Main circuit resistance |
μΩ |
≤150 |
16 |
Rated SF6 gas pressure (20℃gauge pressure) |
Mpa |
0.5 |
17 |
Alarm/blocking pressure(20℃gauge pressure) |
Mpa |
0.45/0.4 |
18 |
SF6 annual gas leakage rate |
% |
≤0.5 |
19 |
Gas moisture content |
Ppm(v) |
≤150 |
20 |
Mechanical life |
times |
6000 |
RHP-72.5
N |
Item |
Unit |
Parameters |
1 |
Rated maximum voltage |
kV |
72.5 |
2 |
Rated maximum current |
A |
≤3150 |
3 |
Rated frequency |
Hz |
50/60 |
4 |
First opening pole coefficient |
|
1.5 |
5 |
Rated short circuit breaking current |
kA |
40 |
6 |
Rated short-circuit duration |
s |
4 |
7 |
Rated out of step breaking current |
kA |
10 |
8 |
Rated peak value withstand current |
kA |
100 |
9 |
Rated 1min power frequency withstand voltage (Dry/Wet) |
kV |
To ground 275 |
Break 315 |
|||
10 |
Rated lightning impulse voltage |
kV |
To ground 650 |
Break 750 |
|||
11 |
Operation sequence |
|
O-0.3s-CO-180s-CO |
12 |
Opening time |
ms |
32±7 |
13 |
Closing time |
ms |
85±10 |
14 |
Close-open time |
ms |
≤60 |
15 |
Main circuit resistance |
μΩ |
≤100 |
16 |
Rated SF6 gas pressure (20℃gauge pressure) |
Mpa |
0.5 |
17 |
Alarm/blocking pressure(20℃gauge pressure) |
Mpa |
0.55/0.5 |
18 |
SF6 annual gas leakage rate |
% |
≤0.5 |
19 |
Gas moisture content |
Ppm(v) |
≤150 |
20 |
Mechanical life |
times |
6000 |
RHP-145
N |
Item |
Unit |
Parameters |
1 |
Rated maximum voltage |
kV |
145 |
2 |
Rated maximum current |
A |
≤3150 |
3 |
Rated frequency |
Hz |
50/60 |
4 |
First opening pole coefficient |
|
1.5 |
5 |
Rated short circuit breaking current |
kA |
40 |
6 |
Rated short-circuit duration |
s |
4 |
7 |
Rated out of step breaking current |
kA |
10 |
8 |
Rated peak value withstand current |
kA |
100 |
9 |
Rated 1min power frequency withstand voltage (Dry/Wet) |
kV |
To ground 275 |
Break 315 |
|||
10 |
Rated lightning impulse voltage |
kV |
To ground 650 |
Break 750 |
|||
11 |
Operation sequence |
|
O-0.3s-CO-180s-CO |
12 |
Opening time |
ms |
32±7 |
13 |
Closing time |
ms |
85±10 |
14 |
Close-open time |
ms |
≤60 |
15 |
Main circuit resistance |
μΩ |
≤100 |
16 |
Rated SF6 gas pressure (20℃gauge pressure) |
Mpa |
0.5 |
17 |
Alarm/blocking pressure(20℃gauge pressure) |
Mpa |
0.55/0.5 |
18 |
SF6 annual gas leakage rate |
% |
≤0.5 |
19 |
Gas moisture content |
Ppm(v) |
≤150 |
20 |
Mechanical life |
times |
6000 |
Dimensie
40.5kV

72.5kV

145kV

Die spanning dek 40.5kV-145kV en is geskik vir scenario's soos kragstasies, transformeerstasies, spoorweë, hawens, ens. Dit is veral geskik vir projekte met beperkte ruimte soos stedelike/bergige transformeerstasies, opgradering van ou stasies, en dakkappele/mobiele transformeerstasies.