| Brand | Switchgear parts |
| Numero sa Modelo | GRV8-SV Voltage Sensing Relay ng IEE-Business |
| Nasodnong peryedyo | 45Hz-65Hz |
| Serye | GRV8 |
Ang GRV8-SV Voltage Sensing Relay nagmomonitor sa mga lebel sa voltage. Ito ay gumagana kung ang voltage ay masyadong mataas o mababa. Ito ay nagprotekta sa iyong equipment mula sa pinsala at nakakaprevent ng mahal na downtime. Ito ay idinisenyo para sa industriya, agrikultura, at transportasyon. Ang pag-mount nito sa DIN rail ay simple. Ito ay kumukuha lamang ng kaunting espasyo. Ang intuitive LCD ay nagpapakita ng data sa voltage. Ito ay nagme-measure ng voltage nang tumpak gamit ang true RMS. Maaari kang magtiwala sa kanyang accuracy at reliability.
Product Highlight:
Dual Voltage Protection: Nagbibigay ng seguridad laban sa over-voltage at under-voltage, panatilihin ang iyong equipment sa ligtas na operating limits.
True RMS Measurement: Nagbibigay ng accurate voltage readings na may ±1% precision para sa dependable monitoring.
Normal/Emergency Power Switching: Seamless transition sa pagitan ng mga power supplies, nagse-ensure ng walang interruption sa operasyon.
Real-Time LCD Display: Nagbibigay ng malinaw, instant visibility ng voltage levels at system status.
Compact Design: 2-module width na may DIN rail mounting para sa madaling integration sa control panels.
Ang GRV8-SV voltage sensing relay, kasama ang kanyang dual voltage protection, True RMS high-precision measurement, real-time LCD display, compact design, wide applicability, high durability, certified quality, at user-friendly features, ay ang ideal na choice para sa pagprotekta ng equipment mula sa voltage fluctuations at pag-ensure ng stable system operation.
| Model | GRV8-SV |
| Function | Over voltage, under voltage |
| Rated supply voltage | AC/DC110V…240V |
| Rated supply frequency | 45~65Hz,0Hz |
| Operation voltage range | 50V~350V |
| Burden | AC max.3VA |
| Over voltage operation value | 65V~300V,OFF |
| Under voltage operation value | OFF,65V~300V |
| Over/under voltage action delay | 0.1s~20s |
| Power-up delay | 0.5s~300s |
| Reset time | 0.5s~300s |
| Measurement error | ≤1% |
| Output | 2×SPDT |
| Current rating | 8A/AC1 |
| Switching voltage | 250VAC/24VDC |
| Electrical life(AC1) | 1×107 |
| Mechanical life | 1×105 |
| Operating temperature | -20℃ ~ +60℃ |
| Storage temperature | -35℃ ~ +75℃ |
| Mounting/DIN rail | Din rail EN/IEC 60715 |
| Protection degree | IP40 for front panel/IP20 terminals |
| Operating position | any |
| Overvoltage cathegory | III |
| Pollution degree | 2 |
| Max.cable size(mm²) | solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12) |
| Tightening torque | 0.4Nm |
| Dimensions | 82*36* 68mm |
| Weight | 100g |
| Standards | EN 60255-1,IEC60947-5-1 |
| Parameter | Range | Step value | Factory settings |
| Over voltage value | 65V~300V,OFF | 1V | 253V |
| Over voltage recovery value | 60V~295V | 1V | 248V |
| Under voltage value | OFF,65V~300V | 1V | 187V |
| Under voltage recovery value | 70V~305V | 1V | 192V |
| Voltage fault action time | 0.1s~20s | 0.1s | 2s |
| Power on delay time | 0.5s~300s | 0.1s/1s | 0.5s |
| Reset time | 0.5s~300s | 0.1s/1s | 1s |
| Fault reset | ON-OFF | / | ON |