Transformātor 50 MVA 220 kV ad dūcendum electricitatis

  • Customization 50MVA 161kV 170kV 220kV transformer for power transmission

Attributa principalia

Marca ROCKWILL
Numerus Modeli Transformātor 50 MVA 220 kV ad dūcendum electricitatis
Frequenta nominata 50/60Hz
Series S

Descriptiones productorum a fornitori

Descriptio

Descriptio Transformatoris Transmissoris 220kV

Transformator transmissoris 220kV est apparatus electricus ad altam tensionem clavis in retibus regionalibus et interurbanis. Is coniungit retia transmissoria ad altiorem tensionem (exempli gratia 500kV) et systemata distributiva ad mediocrem tensionem (exempli gratia 110kV/35kV), reducens electricitatem 220kV ad nivella inferiores pro zonis industrialibus, centris urbanis, et infrastructura magnae scalae. Largiter dispositus in substationibus et punctis interconnectionis retium, is securitat fluxum stabilis electricitatis per medias vel longas distancias (50–200km), supportat aequilibratum onerum, et augit fiduciam distributionis energiae trans provincias vel areas metropolitanas.

  • Transformator 50MVA 220kV

Characteristica Transformatoris Transmissoris 220kV

  • Adaptabilitas Versatilis Tensionis: Optimizatus ad coniungendum retia 220kV cum systematibus minoris tensionis (110kV/35kV), permittens integrationem flexibilem in rete multilevel. Haec adaptabilitas facit eum aptum tam pro scenariis urbane quam rusticae transmissionis.

  • Alta Efficiencia & Parva Perdita: Adoptat nucleos silicis ferri parviperditarum et devolutiones cuprei optimizatas, reducens perditas sine onere et cum onere per 15–20% comparativus ad modellos veteres. Conformatur standardibus internationalibus efficiendi (exempli gratia IEC 60076) ad minimandum dispendium energiae durante transmissione.

  • Robustus Design Structurae: Aedificatus cum tankibus oleo immersis hermeticis vel insulatione sicca progressiva (ad usum interius) ad resistendum humori, pulvari, et temperaturis extremis (-30°C ad 45°C). Picturae resistentes corrosioni asseverant durabilitatem in ambientibus littoralibus vel industrialibus.

  • Mechanismi Augentes Securitatem: Equipatus cum valvulis relevo pressionis, sensoribus temperaturae, et protectione relais gasorum ad detectandum defectus ut circuitus brevis vel fuga olei. Mutatores tap cum onere (OLTC) permittunt adjustmentem tensionis sub pleno onere, praeventantes instabilitatem retis.

  • Compactus & Spatiis Parsimonia: Dispositus cum pede minore pro installatione faciliori in substationibus urbani cum spatiis limitatis. Characteristicae mitigantes sonum (exempli gratia bases absorbentes vibrationes) conformantur regulis environmentalibus in areis residentialibus.

  • Integratio Reticuli Intellectivi: Integratus cum systematibus monitorandi IoT-enable ad sequendum parametra real-time (qualitas olei, temperatura devolutionis, currentis oneris). Supportat diagnosticam remotam et maintenance predictivam, minuens tempus inoperae.

  • Capacitas Alta Sustinendi Circuitus Breves: Devolutiones robustae et structurae nuclei rigidae sustinent currentes breves temporales, asseverantes securitatem operationalem durante defectibus retis et extendentes vitam servitii (typice 30+ annos).

FAQ pro
Q: Quae sunt gradus tensionis in transformatoribus electricitatis usque ad 345kV et quae sunt communes rationes tensionis?
A:
Transformatores in hac serie duos principes gradus rete electricitatis continet: Tensionem Altam (TA) et Tensionem Extra Altam (TEA). Tensiones standard et communes rationes sunt ut sequitur:
  • Gradus tensionum nuclearium: Tensionem Altam (TA) includit 33kV, 66kV, 115kV, 132kV, 220kV, et 230kV; Tensionem Extra Altam (TEA) includit 345kV et 400kV. Haec omnia sunt tensiones systematis nominalis in normis internationalibus specificatae.
  • Rationes tensionum typicae: ① Elevatio generatoris: 345kV/13.8kV; ② Depressio substationis: 345kV/34.5kV; ③ Lineae transmissionis (saepe autotransformatores): 345kV/138kV, 345kV/230kV; ④ Aliae communes rationes: 220kV/132kV, 132kV/66kV, 132kV/33kV.
Cognosce tui fornitori
Venditio Online
Ratio praestabilitae tradendae
Tempus responsionis
100.0%
≤4h
Brevis Descriptio Societatis
Locus Operis: 108000m²m² Numerus omnium laborantium: 700+ Summa Annua Exportatio (USD): 150000000
Locus Operis: 108000m²m²
Numerus omnium laborantium: 700+
Summa Annua Exportatio (USD): 150000000
Servitia
Genus Negotii: Design/Fabricatio/Venditio
Categorias Principales: apparatus electrum altum voltus/transformator
Gubernatio vitae
Servitia gestionis curae integralis pro quaestu, usu, conservatione et post-venditionem apparatus electricorum, securitatem operationis, continuationem imperii et usum electricitatis sine cura garantia.
Fornitori instrumentorum praeteritus est certificationem qualificationis platformae et iudicium technicum, ut ex fonte conformitas, professionalitas et fiducia servantur.

Producta Connexa

Cognitio Connexa

  • Accidentia Transformatoris Principalis et Questiones Operationis Gas Luminis
    1. Registri accidentis (XIX Martii, MMXIX)Hora XVI:XIIX die XIX Martii, MMXIX, monitorium background reportavit actionem gas levis transformatoris principis numeri III. Conformiter Codex Operationis Transformatorum Electricitatis (DL/T572-2010), personale operationis et maintenance (O&M) inspectavit statum in situ transformatoris principis numeri III.Confirmatio in situ: Panel non-electricus protectionis WBH transformatoris principis numeri III reportavit actionem gas levis phase B corpus tr
    02/05/2026
  • Culpae et Tractatio Terrae Unipolaris in Lineis Distributionis 10kV
    Characteristica et Instrumenta Detegendi Defectus Terrae Monofasiales1. Characteristica Defectuum Terrae MonofasialiumSigna Centralia Admonitionis:Campanula admonitionis sonat, et lucerna indicativa inscripta „Defectus Terrae in Sectione Omnibus [X] kV [Y]“ accenditur. In systematibus ubi punctum neutrum per bobinam Petersen (bobinam suppressionis arcus) ad terram connectitur, lucerna indicativa „Bobina Petersen Operatur“ etiam accenditur.Indicationes Voltmetri Monitoris Isolationis:Tensio phase
    01/30/2026
  • Modus operationis terre iunctae puncti neutralis pro transformatoribus retis electricitatis 110kV~220kV
    Dispositio modi operis terrae puncti neutralis pro transformatoribus rete electricitatis 110kV~220kV debet exigentias tolerationis insulationis puncti neutralis transformatorum complere, et simul conari ut impedimentum sequentiae nullae stationum transformationis fere immutatum maneat, dum certatur ne impedimentum sequentiae nullae compositum in quocumque puncto raptus circuiti systematis ultra ter impedimentum sequentiae positivae compositum excedat.Pro transformatoribus 220kV et 110kV in novis
    01/29/2026
  • Cur Quare Substationes Lapidem Gravem Calculos et Rupem Fractam Utuntur
    Cur Quare Substationes Utuntur Lapidibus, Gravibus, Piscinis et Saxis Tritis?In stationibus transformationis, instrumenta ut transformatores electricitatis et distributionis, lineae transmissionis, transformatores tensionis, transformatores currentis et commutatores disiunctionis omnia terram exigunt. Praeter terram, nunc profundius explorabimus cur gravia et saxa trita in stationibus transformationis saepe utuntur. Quamquam videantur ordinaria, isti lapides partem criticam iuxtaque functionalem
    01/29/2026
  • Cur autem nucleus transformatoris tantum in uno puncto terram tangere debet Nonne terra multipuncta fidelius est
    Cur ergo nucleus transformatoris terram tangere debet?In operatione, nucleus transformatoris, simul cum structuris, partibus et componentibus metallicis quae fixant nucleum et spiras, in forti campo electrico situs est. Sub influentia huius campi electrici, potentialem relativum altum ad terram comparatum acquirunt. Si nucleus non terra tangitur, differentia potentialis inter nucleum et structuras claudicantes et vas terratum existet, quae possit ad intermitterentiam dismissionem ducere.Praetere
    01/29/2026
  • Intellegere Terram Neutralis Transformatoris
    I. Quid est Punctum Neutrum?In transformatoribus et generatoribus, punctum neutrum est locus specificus in spira ubi absoluta tensio inter hunc locum et singula terminalia externa aequalis est. In diagrammate infra, punctumOrepraesentat punctum neutrum.II. Cur Punctum Neutrum Terrendum Est?Modus connexionis electricae inter punctum neutrum et terram in systemate AC triphasico diciturmodus terrendi puncti neutri. Hic modus directe afficit:Securitatem, fidem et oeconomiciam retelectrici;Selectione
    01/29/2026

Solutiones Relatae

  • Design Solution of 24kV Siccum Aera Insulatum Ring Main Unit
    Combinatio Solidi Insulationis Adiuvantis + Insulationis Aereae Siccae repraesentat directionem pro RMU 24kV. Per requirementa insulationis cum compactitate equilibrata et adiuvante solidum insulationis, testes insulationis sine magnificatione significativa dimensionum inter phasos et inter phasos et terram transigi possunt. Inclusio columnae pole solidificat insulationem pro interruptore vacuo et conductoribus eius coniunctis.Maintinendo spatium phasorum exiens 24kV ad 110mm, intensitas electri
    08/16/2025
  • Optimizatio Design Schematum pro Unitate Circulorum Principalium Aere Insulata 12kV ad Minuendam Probabilitatem Disruptionis Emissionis
    Cum celeri progressus industriae electricitatis, conceptus ecologicus de carbonis minore, energiae servanda, et conservatione ambientis profundissime integratus est in designum et fabricam productorum electricorum pro distributione et generatione electricitatis. Unitas Distributiva Circuli (RMU) est dispositivum electricum clavem in retibus distributionis. Securitas, conservatio ambientis, fides operativa, efficacia energetica, et oeconomia sunt tendentiae inevitabiles in eius progressu. RMUs tr
    08/16/2025
  • Analyse communium problematum in unitatibus principali circuitu isolatis gas 10kV (RMUs)
    Introductio:​​RMUs insulati gaseis 10kV sunt amplissime usitati propter multas suas utilitates, sicut quod sint perfecte clausi, habeant excellentem insulativam qualitatem, non requirant maintenance, sint compacti, et praebent installationem flexibilem et commodam. In hoc stadio, paulatim facti sunt nodus criticus in rete distributionis urbano anulari et iocabuntur partem significativam in systemate distributionis electricitatis. Difficultates in RMUs insulatis gaseis possunt graviter impingere
    08/16/2025
Instrumenta Libera Cognata
Non invenisti adhuc opportunos fornitoris ut te inveniant Citationem Nunc Accipe
Non invenisti adhuc opportunos fornitoris ut te inveniant
Citationem Nunc Accipe
Inquiry
+86
Click to upload file
Descarica
Obtine Applicatio Commerciale IEE-Business
Utiliza app IEE-Business ad inveniendum apparatus obtinendumque solutiones coniungendum cum peritis et participandum in collaboratione industriale ubique et semper propter totam supportionem tuorum projectorum electricitatis et negotiorum