| Marca | ROCKWILL |
| Numerus Modeli | Unitas anularis metallica solidis insulis inclusa 12/24kV |
| Votum nominatum | 12kV |
| Frequenta nominata | 50/60Hz |
| Series | CKSS |
Series CKSS-12/24 unitatis anuli principale est apparatum commutatorium metallico inclusum cum tanko communi, constans ex unitate commutatoris oneris, unitate combinationis commutatoris oneris et fusorum, unitate circuiti interruptoris vacui, et unitate lineae entrantis bus. Adoptat variam technologiarum et materialium, habens excellentes proprietates electricas et mechanicas, minus affectus ab environmento et clima, parvus in magnitudine, facile ad installandum, facile ad operandum, sine necessitate maintenance, et posse flexibiliter combinari. Designatio eius clara et intuitiva operatio certam et directam assequitur, capacitas connectionis feeder magna, apta pro variis systematibus wiring.
Feature
|
Codex unitatis |
Significatio |
|
C |
Unitas disjungendi oneris cum casu unico standard |
|
F |
Combinatio disjungentis oneris et fusibilis |
|
V |
Unitas apparatorum |
|
D |
Unitas cabalis (sine commutatore) |
|
+ |
Casus lateralis busbar |
|
- |
Casus superior busbar |
|
SL |
Unitas copulans busbar |
|
M |
Unitas mensurandi |
|
PT |
Unitas PT |
|
1K2(4) |
Unitas disjungendi oneris bimanualis |
Folium technicum
|
ltem |
Unit |
Load break switch unit |
Combination apparatus |
Fuse unit |
|
|
Rated voltage |
kV |
12/24 |
12/24 |
12/24 |
|
|
Rated frequency |
Hz |
50 |
50 |
50 |
|
|
Rated current |
A |
630 |
Depend on rated current of fuse |
630 |
|
|
P.F.withstand voltage (phase to phase.phase to earth) |
kV |
42/65 |
42/65 |
42/65 |
|
|
Ated insulation levels |
P.F.withstand voltage(Across open contacts) |
48/79 |
48/79 |
48/79 |
|
|
P.F.withstand voltage (Control and auxiliary circuit) |
2/2 |
2/2 |
2/2 |
||
|
Lightning impulse withstand voltage (phase to phase, phase to earth) |
75/125 |
75/125 |
75/125 |
||
|
Across open contacts |
85/145 |
85/145 |
85/145 |
||
|
Ogauge pressure test |
— |
Pass |
Pass |
Pass |
|
|
Rated short time withstand current |
kA |
20/4s/20/3s |
— |
20/4s/20/4s |
|
|
Rated peak withstand current |
kA |
63 |
—— |
63 |
|
|
Rated short circuit making current |
kA |
50 or 63 |
Subject to high-voltage fuse |
50 |
|
|
Rated short circuit breaking current |
kA |
— |
Subject to high-voltage fuse |
20/20 |
|
|
Rated transform current |
A |
— |
1750/1400 |
— |
|
|
Rated active load breaking current |
A |
630 |
— |
— |
|
|
Rated Closed loop breaking current |
A |
630 |
— |
630 |
|
|
Mechanical life |
Load break switch/breaker |
Time |
5000 |
5000 |
10000 |
|
Isolating switch/earthing switch |
5000 |
5000 |
5000 |
||
|
Loop resistance |
μΩ |
≤120 |
— |
≤120 |
|
|
Inflation pressure |
Rated inflation pressure(absolute pressure) |
bar |
1.3 |
1.3 |
1.3 |
|
Minimum inflation pressure(absolute pressure) |
1.2 |
1.2 |
1.2 |
||
|
Relative rate leakage of gas |
% |
≤0.02 |
≤0.02 |
≤0.02 |
|
Nota: l :Systema de terrae ad punctum neutrum per resistenciam parvam