| Marca | Wone Store |
| Numerus Modeli | Testor Fulguris Impetus 100kV5KJ |
| Votum nominatum | 220V |
| Capacitas nominata | 10kVA |
| Series | JC2 |
Praegressio
Hic generator applicatur ad transformatores electricitatis parvi capacitatis, transformatores instrumentorum, reactores, arrestores, commutatores, bocchias, isolatores et alia exemplaria testis cum nive tensionis testi 100 KV et infra pro testibus plenarum undarum impulsi fulminis standard.
Parametri
Projectum |
Parametri |
|
Ingressus potens |
Tensio nominata |
AC 220V±10% 50Hz |
Ingressus potens |
2-phase 3-wire |
|
Egressus transformatoris |
Capacitas nominata |
10kVA |
Tensio egressionis transformatoris |
0~100kv |
|
Currens egressionis transformatoris |
0-100mA |
|
Resistentia ad terram |
≤0.5Ω |
|
Distancia securitatis campi electrici |
≥2m |
|
Potentia nominata |
5kJ |
|
Capacitas impulsi totalis |
0.7uF 60KVx2 |
|
Capacitas oneris |
500~5000PF |
|
Forma undae impulsi fulminis |
Tempus capitis undae |
1.2S 30% |
Tempus caudae undae |
50S 20% |
|
Deviation culminis |
3% |
|
efficiencia |
≥85% |
|
Temperatura operationis |
-10℃-50℃ |
|
Altitudo |
≤1000m |
|