• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Applications of 10kV Feeder Voltage Regulators

Echo
Echo
Field: Transformer Analysis
China

Rural power grids are characterized by numerous nodes, wide coverage, and long transmission lines. Meanwhile, the electrical load in rural areas shows strong seasonality. These features lead to high line losses on 10 kV rural feeders, and during peak load periods, the voltage at the end of the line drops too low, causing user equipment to malfunction.

Currently, there are three common voltage regulation methods for rural power grids:

  • Upgrading the power grid :Requires substantial investment.

  • Adjusting the on - load tap - changer of the main transformer :Takes the substation bus voltage as the reference. However, frequent adjustments affect the safe operation of the main transformer and cannot ensure stable line voltage.

  • Switching shunt capacitors :Reduces voltage drop caused by reactive power when the grid has large inductive loads, but the voltage regulation range is narrow.

After final discussion, it was decided to adopt a new - type voltage regulation device — the 10 kV feeder voltage regulator (SVR), which effectively improved the voltage quality of the rural power grid.And through the comparison of measures to improve voltage quality in the following table, it can be seen that using feeder voltage regulators is currently the most effective way to enhance the voltage quality of rural 10 kV lines.

Application Example

Taking the 10 kV Tuanjie Line of a certain substation as an example, the installation process of the SVR is as follows:

  • Identify the critical point where voltage drops exceed acceptable limits.

  • Select SVR capacity based on the maximum load at the critical point.

  • Determine voltage regulation range according to the measured voltage drop.

  • Choose installation location prioritizing accessibility for maintenance.

Calculation Method

Line Parameters:

  • Length: 20 km

  • Conductor: LGJ - 50

  • Resistivity: R₀ = 0.65 Ω/km

  • Reactance: X₀ = 0.4 Ω/km

  • Transformer Capacity: S = 2000 kVA

  • Power Factor: cosφ = 0.8

  • Rated Voltage: Ue = 10 kV

Step 1: Calculate Line Impedance

  • Resistance: R = R₀ × L = 0.65 × 20 = 13 Ω

  • Reactance: X = X₀ × L = 0.4 × 20 = 8 Ω

  • Active Power: P = S × cosφ = 2000 × 0.8 = 1600 kW

  • Reactive Power: Q = S × sinφ = 2000 × 0.6 = 1200 kvar

Step 2: Voltage Drop Calculation
ΔU = (PR + QX)/U = (1600×13 + 1200×8)/10 = 3.04 kV

Step 3: SVR Sizing

  • Installation Location: 10 km from the source (critical point with measured voltage 9.019 kV).

  • Load at Critical Point: P = 1200 kW, cosφ = 0.8 → S = 1200/0.8 = 1500 kVA.

  • Selected SVR Capacity: 2000 kVA.

Step 4: Voltage Regulation Range

  • Input Voltage: U₁ = 9 kV (measured)

  • Target Output Voltage: U₂ = 10.5 kV

  • Required Regulation Range: 0~+20%.

Step 5: Loss Reduction Calculation
Post - installation:

  • Remaining Line Length: L₁ = 20 km - 10 km = 10 km

  • Power Loss Reduction:
    ΔP = R₀ × L₁ × (S²/U₁² - S²/U₂²)
    = 0.65 × 10 × (1500²/9² - 1500²/10.5²)
    = 63.9 kW

  • Net Reduction (after SVR loss): 63.9 kW - 4.4 kW = 59.5 kW

Economic Benefits:

  • Annual Energy Savings: 59.5 kW × 24 h × 30 days × 4 months ≈ 450,000 kWh

  • Cost Savings: 450,000 kWh × ¥0.33/kWh ≈ ¥60,000

  • Revenue Increase: ¥80,000 annually

  • Payback Period: <1 year

This demonstrates that SVRs are the most effective and economical solution for improving rural voltage quality.

 

Give a tip and encourage the author!
Recommended
3D Wound-Core Transformer: Future of Power Distribution
3D Wound-Core Transformer: Future of Power Distribution
Technical Requirements and Development Trends for Distribution Transformers Low losses, especially low no-load losses; highlighting energy-saving performance. Low noise, particularly during no-load operation, to meet environmental protection standards. Fully sealed designto prevent transformer oil from contacting external air, enabling maintenance-free operation. Integrated protection devices within the tank, achieving miniaturization; reducing transformer size for easier on-site installation. C
Echo
10/20/2025
Reduce Downtime with Digital MV Circuit Breakers
Reduce Downtime with Digital MV Circuit Breakers
Reduce Downtime with Digitized Medium-Voltage Switchgear and Circuit Breakers"Downtime" — it’s a word no facility manager wants to hear, especially when it’s unplanned. Now, thanks to next-generation medium-voltage (MV) circuit breakers and switchgear, you can leverage digital solutions to maximize uptime and system reliability.Modern MV switchgear and circuit breakers are equipped with embedded digital sensors that enable product-level equipment monitoring, providing real-time insights into the
Echo
10/18/2025
One Article to Understand the Contact Separation Stages of a Vacuum Circuit Breaker
One Article to Understand the Contact Separation Stages of a Vacuum Circuit Breaker
Vacuum Circuit Breaker Contact Separation Stages: Arc Initiation, Arc Extinction, and OscillationStage 1: Initial Opening (Arc Initiation Phase, 0–3 mm)Modern theory confirms that the initial contact separation phase (0–3 mm) is critical to the interrupting performance of vacuum circuit breakers. At the beginning of contact separation, the arc current always transitions from a constricted mode to a diffused mode—the faster this transition, the better the interruption performance.Three measures c
Echo
10/16/2025
Advantages & Applications of Low-Voltage Vacuum Circuit Breakers
Advantages & Applications of Low-Voltage Vacuum Circuit Breakers
Low-Voltage Vacuum Circuit Breakers: Advantages, Application, and Technical ChallengesDue to their lower voltage rating, low-voltage vacuum circuit breakers have a smaller contact gap compared to medium-voltage types. Under such small gaps, transverse magnetic field (TMF) technology is superior to axial magnetic field (AMF) for interrupting high short-circuit currents. When interrupting large currents, the vacuum arc tends to concentrate into a constricted arc mode, where localized erosion zones
Echo
10/16/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.