Vacuum vs Air Circuit Breakers: Key Differences

Garca
Garca
फील्ड: Design & Maintenance
Congo

Low-Voltage Air Circuit Breakers vs. Vacuum Circuit Breakers: Structure, Performance and Application

Low-voltage air circuit breakers, also known as universal or molded frame circuit breakers (MCCBs), are designed for AC voltages of 380/690V and DC voltages up to 1500V, with rated currents ranging from 400A to 6300A or even 7500A. These breakers use air as the arc-quenching medium. The arc is extinguished through arc elongation, splitting, and cooling by an arc chute (arc runner). Such breakers can interrupt short-circuit currents of 50kA, 80kA, 100kA, or up to 150kA.

Main Components and Functionality

  • Operating Mechanism: Located at the front of the breaker, it provides the necessary speed for contact separation and closure. Fast contact motion helps stretch and cool the arc, facilitating extinction.

  • Intelligent Trip Unit: Mounted beside the operating mechanism, this is the "brain" of the low-voltage circuit breaker. It receives current and voltage signals via sensors, calculates electrical parameters, and compares them with preset LSIG protection settings:

    • L: Long-time delay (overload protection)

    • S: Short-time delay (short-circuit protection)

    • I: Instantaneous (instant trip)

    • G: Ground fault protection
      Based on these settings, the trip unit signals the mechanism to open the breaker under overloads or short circuits, providing comprehensive protection.

  • Arc Chamber and Terminals: Located at the rear, the arc chamber contains the contacts and arc chute. The lower three-phase outgoing terminals are equipped with:

    • Electronic current sensors (for signal input to the trip unit)

    • Electromagnetic current transformers (CTs) (to supply operating power to the trip unit)

The operating mechanism typically has a mechanical life of less than 10,000 operations.

VCB.jpg

Evolution from Air to Vacuum Interruption

Historically, medium-voltage air circuit breakers existed but were bulky, had limited breaking capacity, and produced significant arc flash (non-zero arc), making them unsafe and impractical.

In contrast, vacuum circuit breakers (VCBs) share a similar overall layout: the operating mechanism at the front, and the interrupter at the rear. However, the interrupter uses a vacuum interrupter (or "vacuum bottle"), which is structurally similar to an incandescent light bulb — a sealed glass or ceramic envelope evacuated to a high vacuum.

In a vacuum:

  • Only a small contact gap is needed to meet insulation and withstand voltage requirements.

  • The arc is rapidly extinguished due to the absence of ionizable medium and the efficient diffusion of metal vapor.

Applications of Vacuum Circuit Breakers

Vacuum circuit breakers have developed rapidly and are now widely used across low-voltage, medium-voltage, and high-voltage systems:

  • Low-Voltage VCBs: Typically rated at 1.14kV, with rated currents up to 6300A and short-circuit breaking capacity up to 100kA.

  • Medium-Voltage VCBs: Most common in the 3.6–40.5kV range, with currents up to 6300A and breaking capacity up to 63kA. Over 95% of medium-voltage switchgear now uses vacuum interruption.

  • High-Voltage VCBs: Single-pole interrupters have reached 252kV, and 550kV vacuum circuit breakers have been achieved through series-connected interrupters.

Key Design Differences

Unlike air circuit breakers that use contact springs, vacuum circuit breakers require the operating mechanism to:

  • Provide sufficient opening and closing speed

  • Ensure adequate contact pressure

This contact pressure must remain sufficient even after up to 3mm of contact wear, to reliably carry the rated current and withstand the peak short-time current during faults.

Advantages of Vacuum Circuit Breakers

  • High reliability and safety

  • Immune to environmental conditions (dust, humidity, altitude)

  • Zero arc flash (no external arcing)

  • Compact size and long maintenance intervals

These advantages make vacuum breakers ideal for use in hazardous environments such as chemical plants, coal mines, oil & gas facilities, where explosion risks and fire safety are critical.

Real-World Case Study: Vacuum vs. Air Breaker Performance Under Fault

A large chemical plant installed two circuit breakers — one air circuit breaker and one vacuum circuit breaker — in identical circuit configurations and subjected them to the same fault conditions.

The circuit was a tie configuration, where the power sources on either side of the breaker were out of synchronization. This resulted in a transient voltage across the contact gap approaching twice the rated voltage, leading to breaker failure.

Results:

  • Air Circuit Breaker:
    Suffered complete destruction. The breaker unit’s enclosure ruptured, and adjacent switchgear on both sides was severely damaged. Extensive reconstruction and replacement were required.

  • Vacuum Circuit Breaker:
    The failure was significantly less violent. After replacing the vacuum interrupter and cleaning the arc by-products (soot) from the breaker and compartment, the switchgear was restored to service quickly.

Conclusion

Vacuum circuit breakers demonstrate superior fault containment, safety, and reliability compared to air breakers, especially under severe transient overvoltages. Their sealed vacuum interrupters prevent arc propagation, minimizing damage and downtime.

In explosive or flammable environments such as chemical plants and coal mines, the arc-free operation and robust performance of vacuum circuit breakers provide a clear technological and safety advantage.

लेखकलाई टिप दिनुहोस् र प्रोत्साहन दिनुहोस्
सिफारिश गरिएको
How to Design 10kV Overhead Line Poles
How to Design 10kV Overhead Line Poles
This article combines practical examples to refine the selection logic for 10kV steel tubular poles, discussing clear general rules, design procedures, and specific requirements for use in 10kV overhead line design and construction.Special conditions (such as long spans or heavy ice zones) require additional specialized verifications based on this foundation to ensure safe and reliable tower operation.General Rules for Overhead Transmission Line Tower SelectionThe rational selection of overhead
James
10/20/2025
How to select a dry-type transformer?
How to select a dry-type transformer?
1. Temperature Control SystemOne of the main causes of transformer failure is insulation damage, and the greatest threat to insulation comes from exceeding the allowable temperature limit of the windings. Therefore, monitoring temperature and implementing alarm systems for transformers in operation are essential. The following introduces the temperature control system using the TTC-300 as an example.1.1 Automatic Cooling FansA thermistor is pre-embedded at the hottest spot of the low-voltage win
James
10/18/2025
How to Choose the Right Transformer?
How to Choose the Right Transformer?
Transformer Selection and Configuration Standards1. Importance of Transformer Selection and ConfigurationTransformers play a critical role in power systems. They adjust voltage levels to suit different requirements, enabling electricity generated at power plants to be efficiently transmitted and distributed. Improper transformer selection or configuration can lead to serious issues. For example, if the capacity is too small, the transformer may not support the connected load, causing voltage dro
James
10/18/2025
How to Inspect 10kV Vacuum Circuit Breakers Properly
How to Inspect 10kV Vacuum Circuit Breakers Properly
I. Inspection of Vacuum Circuit Breakers During Normal Operation1. Inspection in Closed (ON) Position The operating mechanism should be in the closed position; The main shaft roller should be disengaged from the oil damper; The opening spring should be in a charged (stretched) energy-stored state; The length of the moving contact rod of the vacuum interrupter protruding below the guide plate should be approximately 4–5 mm; The bellows inside the vacuum interrupter should be visible (this does no
Felix Spark
10/18/2025