Phase Synchronizing Device or Controlled Switching Device

Electrical4u
Field: Basic Electrical
0
China

What Is A Phase Synchronizing Device

When we switch off an online circuit breaker to cut an inductive load, it is ideally desired to interrupt the current of the system during its zero crossing of the current waveform. But practically it is somewhat impossible to maintain the condition. In normal circuit breaker the current interruption may occur at an instant near to the zero crossing point but not exactly at zero crossing point of the current waveform. As the load is inductive in nature, this sudden interruption of current, causes high di/dt which results in high transient voltage in the system.


phase synchronizing device or controlled switching device


In low or medium voltage power system, this transient voltage during circuit breaker operation may not much affect the system performance, but in extra and ultra-high voltage systems, this is quite effective. If the separation of contacts in circuit breaker is not sufficient at the current interruption instant, there may be re-ionization between the contacts due to transient over voltage, hence the arcing may be re-established.
When we switch on an inductive load like
transformer or reactor, and if the circuit breaker closes the circuit near to the voltage zero crossing, there will be high DC component of current. This may saturate the core of transformer or reactor. This leads to a high inrush current in the transformer or reactor.
When we switch on a circuit breaker to connect a capacitive load to the system, such as capacitor bank, it is desirable to connect the current path at zero crossing of system
voltage waveform.



phase synchronizing device or controlled switching device


Otherwise due to sudden change in voltage during switching, high inrush current is created in the system. This may be followed by over voltage in the system too.

The
inrush current along with over voltage stress mechanically and electrically, the capacitor bank and other equipment in line.
Generally, in
circuit breaker all three phases open or close nearly at same instant. But there is 6.6 ms time gap between the zero crossings of two adjacent phases of three phase system.

A device installed at relay and control panel to overcome this transient behavior of voltage and current during switching. This device synchronizes the switching of individual pole of >circuit breaker according to the zero crossing of corresponding phase. This device is known as phase synchronizing device, in short PSD.

Sometimes it is also referred as controlled switching device or CSD.
This device takes voltage waveform from
potential transformer of bus or load, current waveform from current transformers of the load, auxiliary contact signal and reference contact signal from circuit breaker, closing and opening command from control switch of the circuit breaker installed in control panel. Voltage and current signal from each phase are required to identify exact instant of zero crossing of the waveform of individual phase. Breaker contact signals are required to calculate the operational delay of the circuit breaker, so that the opening or closing pulse to the breaker can be send accordingly, to match the interruption and zero crossing of either current or voltage wave, as per requirement.


PSD or CSD



This device is dedicated for manual operation of the circuit breaker. During faulty tripping, the trip signal to the circuit breaker is directly sent from the protection relay assembly, bypassing the device. The Phase Synchronizing Device or PSD may also be associated with a bypass switch which can bypass the device from the system if required in any situation.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!
Recommended
Ensuring Reliability: A Deep Dive into Transformer Maintenance
IntroductionElectric transformers are the backbone of modern power distribution systems, silently enabling the reliable delivery of electricity to homes, businesses, and industries. As these critical assets age and the demand for uninterrupted power grows, the importance of diligent transformer maintenance has never been greater. This essay explores the essential role of transformer maintenance, highlighting the value of proactive care, the impact of advanced diagnostic technologies, and the tra
Vziman
09/03/2025
How does a transformer work?
Transformer Operation PrincipleA transformer is an electrical device that operates on the principle of electromagnetic induction to transfer electrical energy from one circuit to another. It enables the adjustment of voltage levels within an alternating current (AC) system, either stepping up (increasing) or stepping down (decreasing) voltage while maintaining the same frequency.Working Principle:Basic ComponentsA transformer consists of two coils, known as windings—the "primary winding" connect
Rockwell
09/03/2025
What is the difference between a dielectric and an insulator?
Dielectrics and insulators are distinguished primarily by their applications. One of the main differences is that a dielectric can store electrical energy by becoming polarized in an electric field, whereas an insulator resists the flow of electrons to prevent current conduction. Other key differences between them are outlined in the comparison chart below.Definition of DielectricA dielectric material is a type of insulator that contains few or no free electrons. When subjected to an electric fi
Edwiin
08/30/2025
What losses occur during operation of the transformer? How to reduce losses?
Transformers experience various types of losses during operation, primarily categorized into two main types: copper losses and iron losses.Copper LossesCopper losses, also known as I²R losses, are caused by the electrical resistance of the transformer windings—typically made of copper. As current flows through the windings, energy is dissipated in the form of heat. These losses are proportional to the square of the load current (I²R), meaning they increase significantly with high
Rockwell
08/29/2025
Seed Inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.