• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Phase Synchronizing Device or Controlled Switching Device

Electrical4u
Electrical4u
Field: Basic Electrical
0
China

What Is A Phase Synchronizing Device

When we switch off an online circuit breaker to cut an inductive load, it is ideally desired to interrupt the current of the system during its zero crossing of the current waveform. But practically it is somewhat impossible to maintain the condition. In normal circuit breaker the current interruption may occur at an instant near to the zero crossing point but not exactly at zero crossing point of the current waveform. As the load is inductive in nature, this sudden interruption of current, causes high di/dt which results in high transient voltage in the system.

phase synchronizing device or controlled switching device

In low or medium voltage power system, this transient voltage during circuit breaker operation may not much affect the system performance, but in extra and ultra-high voltage systems, this is quite effective. If the separation of contacts in circuit breaker is not sufficient at the current interruption instant, there may be re-ionization between the contacts due to transient over voltage, hence the arcing may be re-established.

When we switch on an inductive load like transformer or reactor, and if the circuit breaker closes the circuit near to the voltage zero crossing, there will be high DC component of current. This may saturate the core of transformer or reactor. This leads to a high inrush current in the transformer or reactor.
When we switch on a circuit breaker to connect a capacitive load to the system, such as capacitor bank, it is desirable to connect the current path at zero crossing of system
voltage waveform.

phase synchronizing device or controlled switching device

Otherwise due to sudden change in voltage during switching, high inrush current is created in the system. This may be followed by over voltage in the system too.

The inrush current along with over voltage stress mechanically and electrically, the capacitor bank and other equipment in line.
Generally, in
circuit breaker all three phases open or close nearly at same instant. But there is 6.6 ms time gap between the zero crossings of two adjacent phases of three phase system.

A device installed at relay and control panel to overcome this transient behavior of voltage and current during switching. This device synchronizes the switching of individual pole of >circuit breaker according to the zero crossing of corresponding phase. This device is known as phase synchronizing device, in short PSD.

Sometimes it is also referred as controlled switching device or CSD.
This device takes voltage waveform from
potential transformer of bus or load, current waveform from current transformers of the load, auxiliary contact signal and reference contact signal from circuit breaker, closing and opening command from control switch of the circuit breaker installed in control panel. Voltage and current signal from each phase are required to identify exact instant of zero crossing of the waveform of individual phase. Breaker contact signals are required to calculate the operational delay of the circuit breaker, so that the opening or closing pulse to the breaker can be send accordingly, to match the interruption and zero crossing of either current or voltage wave, as per requirement.

PSD or CSD

This device is dedicated for manual operation of the circuit breaker. During faulty tripping, the trip signal to the circuit breaker is directly sent from the protection relay assembly, bypassing the device. The Phase Synchronizing Device or PSD may also be associated with a bypass switch which can bypass the device from the system if required in any situation.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!
Recommended
 Causes and Preventive Measures of Fire and Explosion in Oil Circuit Breakers
Causes and Preventive Measures of Fire and Explosion in Oil Circuit Breakers
Causes of Fire and Explosion in Oil Circuit Breakers When the oil level in an oil circuit breaker is too low, the oil layer covering the contacts becomes too thin. Under the effect of the electric arc, the oil decomposes and releases flammable gases. These gases accumulate in the space beneath the top cover, mixing with air to form an explosive mixture, which can ignite or explode under high temperature. If the oil level inside the tank is too high, the released gases have limited space to expan
Felix Spark
11/06/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Solid insulation assistance combined with dry air insulation is a development direction for 24 kV ring main units. By balancing insulation performance and compactness, the use of solid auxiliary insulation allows passing insulation tests without significantly increasing phase-to-phase or phase-to-ground dimensions. Encapsulation of the pole can address the insulation of the vacuum interrupter and its connected conductors.For the 24 kV outgoing busbar, with the phase spacing maintained at 110 mm,
Dyson
11/03/2025
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
Ring main units (RMUs) are used in secondary power distribution, directly connecting to end-users such as residential communities, construction sites, commercial buildings, highways, etc.In a residential substation, the RMU introduces 12 kV medium voltage, which is then stepped down to 380 V low voltage through transformers. The low-voltage switchgear distributes electrical energy to various user units. For a 1250 kVA distribution transformer in a residential community, the medium-voltage ring m
James
11/03/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.