Typical sensors used for UHF PD measurement for GIS

04/16/2025

In most types of Gas - Insulated Switchgear (GIS), the Ultra - High - Frequency (UHF) energy is concentrated within the frequency range of 100 MHz to 2 GHz. The frequency response of the sensor is contingent upon its size, shape, and the connection method employed. Most sensors are, in themselves, resonant structures at UHF frequencies, and this characteristic can be exploited to enhance performance. Typical sensors are depicted in the figure.
Internal sensors are typically installed in a recess within the enclosure. In this area, the radial component of the electric field is the most significant. Since degassing of the GIS chambers is essential, internal sensors must be installed during the manufacturing of the GIS or retrofitted during maintenance. These sensors commonly take the form of a metal disc that is insulated from the GIS enclosure by a dielectric material. The measurement connection is established through a coaxial connector, which is usually attached to the center of the disc.
Externally mounted sensors (for instance, at an inspection window or barrier insulator) will be influenced by the field patterns in the structure on which they are mounted. In such cases, the mounting arrangement should be regarded as an integral part of the sensor. External sensors are installed in an aperture in the chamber wall, such as an inspection window or an exposed barrier edge.
 

 

Hello,I'm Wdwiin. A decade of hands-on experience in electrical engineering, specializing in high-voltage systems, smart grids, and renewable energy technologies. Passionate about technical exchange and knowledge sharing, committed to interpreting industry trends with professional insights to empower peers. Connection creates value—let’s explore the boundless possibilities of the electrical world together!

What is the difference between a dielectric and an insulator?
What is the difference between a dielectric and an insulator?
Dielectrics and insulators are distinguished primarily by their applications. One of the main differences is that a dielectric can store electrical energy by becoming polarized in an electric field, whereas an insulator resists the flow of electrons to prevent current conduction. Other key differences between them are outlined in the comparison chart below.Definition of DielectricA dielectric material is a type of insulator that contains few or no free electrons. When subjected to an electric fi
08/30/2025
What losses occur during operation of the transformer? How to reduce losses?
What losses occur during operation of the transformer? How to reduce losses?
Transformers experience various types of losses during operation, primarily categorized into two main types: copper losses and iron losses.Copper LossesCopper losses, also known as I²R losses, are caused by the electrical resistance of the transformer windings—typically made of copper. As current flows through the windings, energy is dissipated in the form of heat. These losses are proportional to the square of the load current (I²R), meaning they increase significantly with high
Rockwell
08/29/2025
Cable Fault Detection, Testing, Location and Repair
Cable Fault Detection, Testing, Location and Repair
I. Methods for Cable Testing and Inspection:Insulation Resistance Test: Use an insulation resistance tester to measure the insulation resistance value of the cable. A high insulation resistance value indicates good insulation, while a low value may suggest insulation problems requiring further investigation.Voltage Withstand Test: Apply a high-voltage test using a high-voltage tester to verify whether the cable can withstand high voltage under its rated operating conditions. Under normal circums
08/29/2025
Cable Quality Inspection and Cable Detection & Testing
Cable Quality Inspection and Cable Detection & Testing
Power cable quality inspection and cable testing are conducted to ensure that the cable's quality and performance meet specified requirements, thereby guaranteeing the safe and stable operation of power systems. Below are some common contents of power cable quality inspection and cable testing:Visual Inspection: Check the cable surface for physical defects such as damage, deformation, or scratches to ensure the cable's exterior is intact.Dimensional Measurement: Measure dimensional parameters su