Ang cycle sa pag-operasyon sa circuit breaker sa generator (GCB) sa grid

Edwiin
Edwiin
Larangan: Switch sa kuryente
China

Ang mga generator circuit breakers mao ang sayong para sa daghang klase sa power generation plants, kasagaran ang fossil-fired, nuclear, gas turbine, combined-cycle, hydro, ug pumped storage power plants. Sila usab ideal para sa retrofitting sa existing power stations nga walay generator circuit breakers.

Mga Advantages sa General Circuit Breakers (GCB) sa Grid

Sa nakaraan, ang mga generator circuit breakers kasagaran gigamit sa multi-unit stations diin ang daghang kauban nga small generators gilink sa usa ka common bus. Apan, tungod sa rapid growth sa generator size ug escalation sa system fault current levels, ang interrupting capabilities sa kini nga tipo sa switchgear lisod na mogahin. Subsequently, ang unit concept giatiman, diin ang bawg generator adunay independent steam supply auxiliary system direkta giconnect sa step-up transformer ug high-side breaker(s).

Kon ikomparar sa unit connection, ang paggamit sa generator circuit breakers aron mogahin sa generators sa ilang terminal voltage maghatag og daghang benefits:

  • Streamlined Operations: Ito simplifies operational procedures, reducing the complexity and potential for human error during generator-related switching tasks.

  • Enhanced Protection: Ito offers improved protection for the generator, as well as for the main and unit transformers, safeguarding these critical components from electrical faults and surges.

  • Increased Reliability: Ito boosts the security of the power generation system and significantly enhances the overall availability of the power plant, minimizing downtime and maximizing power output.

  • Economic Gains: Ito also brings about economic advantages, such as reduced maintenance costs and improved long-term operational efficiency.

Ang key requirements para sa electrical layout sa power plants mahimong masummary kini:

  • Efficient Power Transfer: Transfer the generated electrical energy from the generator to the high-voltage (HV) transmission system, taking into account operational needs, as well as factors related to availability, reliability, and economic viability.

  • Reliable Auxiliary Power Supply: Ensure the supply of electrical power for auxiliary and station service systems, which is crucial for maintaining safe and reliable power plant operation.

Figure 1 illustrates examples of power station layouts that utilize a generator circuit breaker to connect the generator to the main transformer, demonstrating how these breakers are integrated into the overall power plant electrical configuration.

Generator Circuit Breaker Operation Duties

Ang mga generator circuit breakers naglupad og crucial ug multifaceted role sa power systems, fulfilling a variety of essential operation duties:

  • Synchronization with the HV System: They are responsible for synchronizing the generator with the system voltage at the high voltage (HV) level. This ensures a seamless connection between the generator's output and the grid, facilitating the efficient transfer of electrical energy.

  • Disconnection from the HV System: They enable the separation of generators from the HV system, which is particularly useful when switching off unloaded or lightly loaded generators. This operation helps in maintaining the stability and safety of the power grid.

  • Load Current Interruption: These breakers are capable of interrupting load currents, with the capacity to handle up to the full-load current of the generators. This functionality is vital for normal operation and load management within the power plant.

  • System-Fed Short-Circuit Interruption: They can interrupt system-fed short-circuits, safeguarding the generator and other components from the potentially damaging effects of excessive current flow caused by faults in the system.

  • Generator-Fed Short-Circuit Interruption: Similarly, they are designed to interrupt generator-fed short-circuits, protecting the generator itself from internal faults and ensuring its continued safe operation.

  • Out-of-Phase Current Interruption: Generator circuit breakers can handle interrupting current under out-of-phase conditions, with the ability to manage up to an out-of-phase angle of 180°. This feature is crucial for maintaining system stability during abnormal operating conditions.

  • Synchronization in Pumped Storage Power Plants (Motor Mode): In pumped storage power plants, when the generator-motor is started in the motor mode, the circuit breaker is used to synchronize the machine with the HV system. There are different synchronization methods available, such as using a static frequency converter (SFC) starting or back-to-back starting.

  • Starting Current Handling in Pumped Storage Power Plants (Motor Mode): When the generator-motor is started in the motor mode with asynchronous starting in pumped storage power plants, the circuit breaker closes on and interrupts the starting current, ensuring a smooth and controlled start-up process.

  • Low-Frequency Short-Circuit Current Interruption: In gas turbine, combined-cycle, and pumped storage power plants, depending on the start-up supply, the circuit breaker can interrupt generator-fed short-circuit currents at frequencies below 50/60 Hz, adapting to the specific requirements of these power generation systems.

Synchronization Methods in Pumped Storage Power Plants

There are multiple synchronization approaches in pumped storage power plants.

  • Static Frequency Converter (SFC) Starting Scheme: This scheme primarily comprises a thyristor converter connected to a unit transformer at the HV side and an inverter linked to the generator. The inverter initiates the generator's operation from a low power frequency and gradually ramps it up to the rated power frequency. Once the generator is excited to produce power, there may be a phase angle difference between its output and that of the network. At the moment when the phase difference between the generator and the HV network is minimized, the generator is synchronized with the HV network using either a generator circuit breaker or an HV circuit breaker.

  • Back-to-Back Starting Scheme: In a power plant with multiple generators, a back-to-back starting scheme can be employed. The power generated by a generator operating under nominal conditions is utilized to start a halted generator up to the rated power frequency. Subsequently, the generator is synchronized with the HV network using either a generator circuit breaker or an HV circuit breaker.

Generator Circuit Breaker Operation Duties as per IEC/IEEE 62271-37-13

According to the IEC/IEEE 62271-37-13 standard, the rated short circuit duty cycle of a generator circuit breaker is specified as consisting of two units of operations, with a 30-minute interval between each operation. The duty cycle is represented as "CO – 30 minutes – CO", which means two complete short circuit interruptions, with a 30-minute gap between each short circuit closing event.This design is specifically intended to safeguard power plants and generators. Performing two consecutive close-open operations during a full short circuit could potentially cause damage to the generator and the step-up transformers.

Such types of short circuits are highly improbable, and it is also very unlikely that a plant manager would attempt to close the circuit again just 30 minutes after a full short circuit event.

The 30-minute interval between two operations is essential for restoring the initial conditions of the circuit breaker and preventing excessive heating of its components. It should be noted that this time interval may vary depending on the specific type of operation and the characteristics of the generator circuit breaker.

Maghatag og tip ug pagsalig sa author
Gipareserbado
Angga ang mga PM Actuators Relable? Pagkumpara sa Mga Tipo ug Benepisyo
Angga ang mga PM Actuators Relable? Pagkumpara sa Mga Tipo ug Benepisyo
Ang pagkakataon sa operasyon ng mga mekanismo ng circuit breaker ay mahalagang paktor para sa maasahan at ligtas na suplay ng kuryente. Habang ang iba't ibang mekanismo ay may kanilang mga pangunahing benepisyo, ang paglitaw ng bagong tipo hindi ganap na nagpapalit sa mga tradisyonal. Halimbawa, bagama't ang pagdami ng eco-friendly gas insulation, ang solid insulation ring main units pa rin ay may higit sa 8% ng merkado, nagpapakita na ang mga bagong teknolohiya malamang na hindi ganap na nagpap
Edwiin
10/23/2025
Unsa ang mga Tipo sa Reactors? Key Roles sa mga Power Systems
Unsa ang mga Tipo sa Reactors? Key Roles sa mga Power Systems
Reactor (Inductor): Pahayag ug mga UriAng reactor, gikataas usab og inductor, mao ang nag-generate og magnetic field sa kalibutan sa palibot samtang adunay kasinatong nga nag-usbong sa usa ka conductor. Busa, anang tanang conductor nga adunay kasinatong natural nga adunay inductance. Apan, ang inductance sa usa ka straight conductor gamay ra ug nag-produce og dili matibay nga magnetic field. Ang praktikal nga reactors gibuo sa pag-winding sa conductor sa usa ka solenoid shape, gikataas usab og a
James
10/23/2025
35kV Distribusyon Line Single-Phase Ground Fault Handling
35kV Distribusyon Line Single-Phase Ground Fault Handling
Distribution Lines: A Key Component of Power SystemsAng mga distribution lines usa ka importante nga komponente sa mga power systems. Sa parehas nga voltage-level busbar, gikonekta ang daghang distribution lines (para sa input o output), kung diin adunay daghang branches nga gisulayan radially ug gikonekta sa mga distribution transformers. Human sa pag-step down sa low voltage niining mga transformers, gigibit og kuryente sa daghang end users. Sa sulod niining mga distribution networks, mahimong
Encyclopedia
10/23/2025
Unsa ang Teknolohiya sa MVDC? Benepisyo, Hamubo & Mga Futuro nga Tendensya
Unsa ang Teknolohiya sa MVDC? Benepisyo, Hamubo & Mga Futuro nga Tendensya
Ang teknolohiya sa medium-voltage direct current (MVDC) usa ka pangunahan nga pagbag-o sa pagpahibalo sa kuryente, gihimo aron mubag-o sa mga limitasyon sa tradisyonal nga sistema sa AC sa pipila ka aplikasyon. Tungod sa pagpahibalo sa elektrisidad pinaagi sa DC sa mga voltaje nga kasagaran nangadako gikan sa 1.5 kV hangtod sa 50 kV, gitugotan kini ang mga buluhaton sa long-distance transmission sa high-voltage DC sama sa flexibility sa low-voltage DC distribution. Sa konteksto sa pag-integro sa
Echo
10/23/2025
Mga Produktong Nakarrelasyon
Inquiry
Pangutana
Pangutana sa IEE-Business Application
Pangita og mga equipment gamit ang IEE-Business app asa asa ug kailan man sugad og pagkuha og solusyon pagsulay sa mga eksperto ug pagpadayon sa industriya nga pakisayran suportahan ang imong proyekto sa kuryente ug negosyo