Quid est Maxima Protectio a Currente Excessivo (MOCP vs MCA vs FLA vs LRA)

Electrical4u
Campus: Electrica Elementaria
0
China

Quid significet MOCP in terminis electricitatis

Quid significet MOCP in terminis electricitatis?

MOCP significat Maximum Over-Current Protection et definitur ut maximum permittibile currentis censum pro dispositivis protectionis over-current (sicut fusus vel circuit breaker) associatis cum aliquo instrumento electrico (exempli gratia motor vel aerator). MOCP est maximum permittibile rating or size of the circuit breaker quod recte disjungat circuitum vel instrumentum sub quovis praesumpto statu culpa.

Si dispositiva protectiva sunt nimis magna, fortasse non possunt operari sub statu culpa, et ideo, filum vel instrumentum potest laedi ex supercalore. Ergo, recta mensura necessaria est pro dispositivis protectivis.

Valorem MOCP adiuvat nos determinare maximam magnitudinem dispositivi protectionis over-current, id est, fusum et circuit breaker. MOCP uti potest ad protegendum filum et instrumentum sub praesumpto statu culpa.

Ita, MOCP vel MOP = Maximum Over-Current Protection = Maximum Fuse or Circuit Breaker Rating.

MCA vs MOCP vs FLA vs LRAs

Informatio de MCA, MOCP, FLA, et LRA valde necessaria est, quia requiritur pro sicura commutatione et protectione instrumentorum. Disseramus singula.

MCA

MCA significat Minimum Current Ampacity vel Minimum Circuit Ampacity, quod definitur ut minima censurae currentis pro ductu filo vel conductore in circuitu electrico. Alio modo, MCA est minima censurae currentis quas fili vel conductores debent tuto portare sub normalibus conditionibus operativis.

Minimum current ampacity est quantitas currentis quam conductor portare debet, igitur est capacitas portandi currentem conductoris vel fili.

Valorem MCA adiuvat nos determinare minimum magnitudinem fili ut asseveremus filum non supercaldescere sub normalibus conditionibus operativis.

Ita, MCA = Minimum Current Ampacity = Minimum Magnitudo Filorum vel Conductorum

Valorem MCA est 1.25 vices FLA motoris addendo omnibus aliis oneribus resistivis, id est, onus calidori.

MCA = 1.25 * (Motor FLA + Heater Current)

MOCP

MOCP est mensura usata ad determinandum maximum magnitudinis dispositivorum protectionis overcurrent sicut disjunctores vel fusibiles qui utuntur ad protegendum filum et apparatum sub conditionibus defectus.

Magnitudo disjunctoris vel fusibilis debet esse maior quam valorem minimi currentis amperiarum (MCA). Itaque valor MOCP semper maior est quam valor MCA.

MCA et MOCP sunt valores importantes qui determinant minimam magnitudinem filorum/conductorum et maximam magnitudinem fusibilium/disjunctorum quae permittuntur ad reducendum periculum overcurrent et ita ad reducendum periculum incendii.

Valorem MOCP est 2.55 vices FLA motoris maximi addendo omnibus aliis oneribus 1 A vel plus quae poterunt operari simul.

MOCP = (2.25 * FLA Motoris Maximi) + (Alia Onus Motorum) + (Omnia Alia Onera Electrica Resistiva, id est, Onera Calidorum)

FLA

FLA significat Full Load Ampere est quantitas currentis continui quod apparatus vel machinae possunt trahere in conditionibus operativis ad plenum onus. FLA est plenum onus currentis ad nominatum voltage et onus quod motor ducet ad producendum nominatum output HP.

Valorem FLA plus importantem esse, ut ad determinandum valorem MCA et MOCP uti solet. Indirecte ergo ad determinandum magnitudinem conductorum, apparatorum, praeservatorum overcurrent sicut fuse, MCB, circuit breakers, etc., uti solet.

  \begin{align*} FLA = 0.80 * MCA \end{align*}

et

  \begin{align*} FLA = 0.44 * MOCP \end{align*}

LRA

LRA significat Locked Rotor Ampere est quantitas currentis quod motor trahere potest in conditionibus rotoris clausi. Valorem LRA fere aequalem esse initio currentis motoris et circa octo vicies plenum onus currentis.

  \begin{align*} LRA = 8 * FLA \end{align*}

Valorem LRA utitur ad calculandum maximum diminutionem tensionis in condicionibus initiis motoris. Si diminutio tensionis maior est quam 80 % vel 85 %, motor potest recusare initium et incipit vibrare.

Quomodo Calculare MOCP

Valorem MOCP praebet fabricator in tabula nominum cuiusque instrumenti vel unitatis ad operationem tuto assecurandam. Dispositiva protectionis contra supracurrentem, sicut fusus et interruptor circuitus, recte dimensionantur ut instrumentum non possit trahere currentem plus quam rating MOCP. Possumus calculare valorem MOCP ex FLA.

MOCP = (2.25 * FLA maximae motoris) + (aliae onera motorum) + (omnia alia onera resistivae electrica i.e., onus calefactoris)

Rating currentis standardis interruptoris circuitus est 15 A, 20 A, 25 A, 30 A, 35 A ……, 60 A, etc. ubi 15 A est minimum rating currentis fusi vel interruptoris circuitus permittentis secundum Codicem Electricum Nationalem in USA.

Sunt duae species oneris in circuitibus electricis altae tensionis.

  1. Onus inductivum i.e., motor, compressor, etc.…

  2. Onus resistivum i.e., calefactores electrici.

Gradus ad calculandum MOCP

Primum, inveni FLA motoris vel compressoris – est plena onus currentis ad tensio nominata et onus.

Secundo, inveni onus calefactoris – est onus electricum resistivum.

Postquam valor MOCP calculatus est, debemus eligere valorem MOCP basati in tribus conditionibus quae infra dantur.

  1. Si MOCP \neq Multiplex quinque i.e., si valor calculatus MOCP non est multiplex par quinque, tunc valor MOCP ad proximum standard fusibile vel interruptor circuiti redigitur.

  2. Si MOCP < MCA i.e., si valor calculatus MOCP minor est quam valor MCA, tunc valor MOCP aequatur MCA et ad proximum standard fusibile vel interruptor circuiti, saepius multiplex quinque, redigitur. Itaque valor MOCP non est minor quam valor MCA.

  3. Si MOCP < 15 A i.e., si valor calculatus MOCP minor est quam 15 A, tunc ad 15 A redigitur. Hoc 15 A est minimum amperium aut rating fusibilis vel interruptoris circuiti permisso per codicem.

Vidamus exempla de modo eligendi valorem MOCP basati in tribus supra conditionibus.

Exemplum 1 : Calcula valor MOCP pro onere calidoreo 3 – phase, 480 V, 10 KW cum motor FLA 4.5 A.

Data data: Tensio supply = 3-phase 480 V, Onus calidoreum = 10 KW, Motor FLA = 4.5 A

  \begin{align*} \begin{split} for \,\, 3-phase \,\, load \,\, the \,\, current \,\,I = \frac {P}{\sqrt3 * V}  \\ Heater\,\,current \,\, (I) = \frac {10000}{\sqrt3 * 480} \\ = \frac {10000}{1.73 * 480} \\ Heater\,\,current \,\, (I) = 12.04 \,\,A \end{split} \end{align*}

Nunc,

  \begin{align*} MCA = 1.25 * (Motor\,\,FLA + Heater\,\,Current) \end{align*}

  \begin{align*} = 1.25 * (4.5 + 12.04) \end{align*}

  \begin{align*} = 1.25*16.54 \end{align*}

  \begin{align*} MCA = 20.68 \,\, A  \end{align*}

et

  \begin{align*} MOCP = (2.25 * FLA\,\,of\,\,the\,\,Largest\,\,Motor)+(Other\,\,Motor\,\,Loads)+ \\(All\,\,Heater\,\,Load) \end{align*}

  \begin{align*} = (2.25 * 4.5) + (0) + (12.04) \end{align*}

  \begin{align*} = 10.125 + 12.04 \end{align*}

  \begin{align*} MOCP = 22.17 \,\, A \end{align*}

Hic, valor MOCP non est multiplex par numerus quinque, ideo ad proximum circuitum disiunctoris, id est, viginti A, redigitur. ergo,

MOCP = 20 A (conditio 1),

sed 20 A minor est quam MCA valor, ideo MOCP aequetur MCA valori et ad proximam interruptoris censum adiuncta. Sic, MOCP est 25 A pro hac 3-phasica onere (Condicio 2).

(Nota quod in USA 277 V est 1 – phasica voltus et 480 V est 3 – phasica voltus et pro India 230 V est 1-phasica et 415 V est 3-phasica voltus).

Exemplum 2: Calcula MOCP valor pro 1 – phasica, 277 V, 5 KW calefactor onere.

Data data: Tensio supply = 1-phasica 277 V, Calefactor onus = 5 KW, Motor FLA = 0

  \begin{align*}   \begin{split} for \,\, 1-phase \,\, load \,\, the \,\, current \,\,I = \frac {P}{V}  \\ Heater\,\,current \,\, (I) = \frac {5000}{277} \\ Heater\,\,current \,\, (I) = 18.05 \,\,A \end{split} \end{align*}

Nunc,

  \begin{align*} MCA = 1.25 * (Motor\,\,FLA + Heater\,\,Current) \end{align*}

  \begin{align*} = 1.25 * (0 + 18.05) \end{align*}

  \begin{align*} = 1.25 * 18.05 \end{align*}

  \begin{align*} MCA = 22.56 \,\, A  \end{align*}

et

  \begin{align*} MOCP = (2.25 * FLA\,\,of\,\,the\,\,Largest\,\,Motor)+(Other\,\,Motor\,\,Loads)+ \\(All\,\,Heater\,\,Load) \end{align*}

  \begin{align*} = (2.25 * 0) + (0) + (18.05) \end{align*}

  \begin{align*} MOCP = 18.05 \,\, A  \end{align*}

Hic MOCP < MCA ergo valor MOCP acceptatur aequus valori MCA et ad proximum circuiti disiunctionis rating est rotundatus. Sic MOCP est 25 A pro hac 1-phase heater oneri (Condicio 2).

Exemplum 3: Calcula MOCP valor pro 3 – phase 480 V 5 KW heater oneri.

Data data: Supply Voltage = 3-phase 480 V Heater onus = 5 KW Motor FLA = 0

  \begin{align*}   \begin{split} for \,\, 3-phase \,\, load \,\, the \,\, current \,\,I = \frac {P}{\sqrt3 * V}  \\ Heater\,\,current \,\, (I) = \frac {5000}{\sqrt3 * 480} \\ = \frac {5000}{1.73 * 480} \\ Heater\,\,current \,\, (I) = 6.02 \,\,A \end{split} \end{align*}

Nunc

  \begin{align*} MCA = 1.25 * (Motor\,\,FLA + Heater\,\,Current) \end{align*}

  \begin{align*} = 1.25 * (0 + 6.02) \end{align*}

  \begin{align*} = 1.25 * 6.02 \end{align*}

  \begin{align*} MCA = 7.53 \,\, A \end{align*}

et

  \begin{align*} MOCP = (2.25 * FLA\,\,of\,\,the\,\,Largest\,\,Motor)+(Other\,\,Motor\,\,Loads)+ \\(All\,\,Heater\,\,Load) \end{align*}

  \begin{align*} = (2.25 * 0) + (0) + (6.02) \end{align*}

  \begin{align*} MOCP = 6.02 \,\, A   \end{align*}

Hic, MOCP < 15 A ergo, valor MOCP est ad 15 A quod est minimum currus rating circuiti disjunctoris (Condition 3).

Quomodo Calculare MCA

Valor MCA est in tabula nominis cuiuslibet apparati vel unitatis a manufactore pro operatione tuta. Possumus calculare valorem MCA per calculandum valorem FLA.

Ut calculemus valorem MCA, debemus calculare currus rating ceterorum omnium apparatorum, id est, ventilator, motor, compressores, etc….

MCA = 1.25 * (Motor FLA + Heater Current)

Vidamus unum exemplum de modo calculandi valorem MCA.

Exemplum: Calcula valorem MOCP pro onere calefactoris 3 – phase, 480 V, 12 KW cum motor FLA 5 A.

Data data: Tensio alimenti = 3-phase 480 V, Onus calefactoris = 12 KW, Motor FLA = 5 A

  \begin{align*}   \begin{split} for \,\, 3-phase \,\, load \,\, the \,\, current \,\,I = \frac {P}{\sqrt3 * V}  \\ Heater\,\,current \,\, (I) = \frac {12000}{\sqrt3 * 480} \\ = \frac {12000}{1.73 * 480} \\ Heater\,\,current \,\, (I) = 14.45 \,\,A \end{split} \end{align*}

Nunc,

  \begin{align*} MCA = 1.25 * (Motor\,\,FLA + Heater\,\,Current) \end{align*}

  \begin{align*} = 1.25 * (5 + 14.45) \end{align*}

  \begin{align*} = 1.25 * 19.45 \end{align*}

  \begin{align*} MCA = 20.7 \,\, A \end{align*}

Ita ergo MCA valor est 20.7 A.

Ut supra dictum, MOCP et MCA valores in apparatu nomenplacato indicantur. Hoc in sequenti nomenplacato ostenditur.


Name Plate Rating
Nomenplacatum


Ut in nomenplacato ostenditur, maximus fusi vel circuiti interruptoris magnitudo seu rating est 20 A, id est, MOCP valor est 20 A. Itaque, possimus overcurrent protective devices secundum praedictum MOCP rating seligere.

Similiter, minimus circuitus amperes sunt 12.2 A, id est, MCA valor est 12.2 A. Ita, possimus minimum filum magnitudinem secundum MCA rating seligere.

Ventilatoris motricis LRA et FLA valores quoque indicantur.