• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Loss of Field or Excitation Protection of Alternator or Generator

Electrical4u
Electrical4u
Field: Basic Electrical
0
China

What Is The Excitation Protection Of Alternator Or Generator

Loss of field or excitation can be caused in the generator due to excitation failure. In larger sized generator, energy for excitation is often taken from a separate auxiliary source or from a separately driven DC generator. The failure of auxiliary supply or failure of driving motor can also cause the loss of excitation in a generator. Failure of excitation that is failure of field system in the generator makes the generator run at a speed above the synchronous speed.
In that situation the generator or
alternator becomes an induction generator which draws magnetizing current from the system. Although this situation does not create any problem in the system immediately but over loading of the stator and overheating of the rotor due to continuous operation of the machine in this mode may create problems in the system in long-run. Therefore special care should be taken for rectifying the field or excitation system of the generator immediately after failure of that system. The generator should be isolated from rest of the system till the field system is properly restored.

There are mainly two schemes available for protection against loss of field or excitation of a generator. In 1st scheme, we use an undercurrent relay connected in shunt with main field winding circuit. This relay will operate if the excitation current comes below its predetermined value. If the relay is to operate for complete loss of field along, it must have a setting lies well below the minimum excitation current value which can be 8% of the rated full load current. Again when loss of field occurs due to failure of exciter but not due to problem in the field circuit (field circuit remains intact) there will be an induced current at slip frequency in the field circuit. This situation makes the relay to pick up and drop off as per slip frequency of the induced current in the field. This problem can be overcome in the following manner.

loss of field protection

In this case a setting of 5% of normal of full load current is recommended. There is a normally closed contact attached with the undercurrent relay. This normally closed contact remains open as the relay coil is energized by shunted excitation current during normal operation of the excitation system. As soon as there is any failure of excitation system, the relay coil becomes de-energized and the normally closed contact closes the supply across the coil of timing relay T1.

As the relay coil is energized, the normally open contact of this relay T1 is closed. This contact closes the supply across another timing relay T2 with an adjustable pickup time delay of 2 to 10 seconds. Relay T1 is time delayed on drop off to stabilize scheme again slip frequency effect. Relay T2 closes its contacts after the prescribed time delay to either shut down the set or initiate an alarm. It is time delayed on pickup to prevent spurious operation of the scheme during an external fault.
loss of excitation protectionloss of field protection of alternatorFor larger generator or alternator, we use a more sophisticated scheme for that purpose. For larger machines, it is recommended to trip the machine after a certain prescribed delay in presence of swing condition resulting from loss of field. In addition to that there must be subsequent load shedding to maintain stability of the system. In this scheme of protection, an automatic imposition of load shedding to the system is also inherently required if the field is not restored within the described time delay. The scheme comprises an offset mho relay, and an instantaneous under voltage relay. As we have said earlier that it is not always required to isolate the generator immediately in the event of loss of field, unless there is a significant disturb in system stability.
We know that system voltage is the main indication of system stability. Therefore the offset mho relay is arranged to shut the machine down instantaneously when operation of generator is accompanied by a system voltage collapse. The drop in system voltage is detected by an under
voltage relay which is set to approximately 70 % of normal rated system voltage. The offset mho relay is arranged to initiate load shedding to the system up to a safe value and then to initiate a master tripping relay after a predetermined time.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!
Recommended
PT Fuse Slow Blow: Causes, Detection & Prevention
PT Fuse Slow Blow: Causes, Detection & Prevention
I. Fuse Structure and Root Cause AnalysisSlow Fuse Blowing:From the design principle of fuses, when a large fault current passes through the fuse element, due to the metal effect (certain refractory metals become fusible under specific alloy conditions), the fuse first melts at the soldered tin ball. The arc then rapidly vaporizes the entire fuse element. The resulting arc is quickly extinguished by quartz sand.However, due to harsh operating environments, the fuse element may age under the comb
Edwiin
10/24/2025
Why Fuses Blow: Overload, Short Circuit & Surge Causes
Why Fuses Blow: Overload, Short Circuit & Surge Causes
Common Causes of Fuse BlowingCommon reasons for fuse blowing include voltage fluctuations, short circuits, lightning strikes during storms, and current overloads. These conditions can easily cause the fuse element to melt.A fuse is an electrical device that interrupts the circuit by melting its fusible element due to heat generated when current exceeds a specified value. It operates on the principle that, after an overcurrent persists for a certain period, the heat produced by the current melts
Echo
10/24/2025
Fuse Maintenance & Replacement: Safety and Best Practices
Fuse Maintenance & Replacement: Safety and Best Practices
1. Fuse MaintenanceFuses in service should be regularly inspected. The inspection includes the following items: Load current should be compatible with the rated current of the fuse element. For fuses equipped with a fuse blown indicator, check whether the indicator has actuated. Check the conductors, connection points, and the fuse itself for overheating; ensure connections are tight and making good contact. Inspect the fuse exterior for cracks, contamination, or signs of arcing/discharge. Liste
James
10/24/2025
Maintenance and Repair Items for 10kV High-Voltage Switchgear
Maintenance and Repair Items for 10kV High-Voltage Switchgear
I. Routine Maintenance and Inspection(1) Visual Inspection of Switchgear Enclosure No deformation or physical damage to the enclosure. Protective paint coating shows no severe rust, peeling, or flaking. Cabinet is securely installed, clean on the surface, and free of foreign objects. Nameplates and identification labels are neatly affixed and not falling off.(2) Check of Switchgear Operating Parameters Instruments and meters indicate normal values (comparable to typical operating data, with no s
Edwiin
10/24/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.