• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


How to Find the DC Gain of a Transfer Function (Examples Included)

Electrical4u
Field: Basic Electrical
0
China

What Is A Transfer Function

What is a Transfer Function?

A transfer function describes the relationship between the output signal of a control system and the input signal. A block diagram is a visualization of the control system that uses blocks to represent the transfer function and arrows representing the different input and output signals.



Transfer Function
Transfer Function



The transfer function is a convenient representation of a linear time-invariant dynamical system. Mathematically the transfer function is a function of complex variables

For any control system, there is a reference input known as excitation or cause that operates through a transfer function to produce an effect resulting in a controlled output or response.

Thus, the cause and effect relationship between output and input is linked to each other through a transfer function. In a Laplace Transform, if the input is represented by R(s) and the output is represented by C(s).

The control system transfer function is defined as the Laplace transform ratio of the output variable to the Laplace transform of the input variable, assuming that all initial conditions are zero.


  \begin{align*} G(s)=\frac{C(s)}{R(s)}\end{align*}


What is DC Gain?

The transfer function has many useful physical interpretations. The steady-state gain of a system is simply the ratio of the output and the input in steady-state represented by a real number between negative infinity and positive infinity.

When a stable control system is stimulated with a step input, the response at a steady-state reaches a constant level.

The term DC gain is described as the ratio of amplitude between the response of the steady-state and the step input.



DC gain
DC gain



DC gain is the ratio of the magnitude of the response to the steady-state step to the magnitude of the step input. The final value theorem demonstrates that DC gain is the value of the transfer function assessed at 0 for stable transfer functions.

Time Response of First Order Systems

The order of a dynamic system is the order of the highest derivative of its governing differential equation. First-order systems are the simplest dynamic systems to analyze.

To understand the concept of steady-state gain or DC gain, consider a general first-order transfer function.


  \begin{align*}G(s)=\frac{G(s)}{R(s)} = \frac{b_{0}}{s+ a_{0}}\end{align*}


G(s) can also be written as

\begin{align*}\frac{K}{\tau s+1} = \frac{b_{0}}{s+a_{0}}\end{align*}


Here,


  \begin{align*} a {0}=\frac{1}{\tau} \; \; \; \; b {0}=\frac{K}{\tau} \end{align*}

\tau is called the time constant. K is called the DC gain or steady-state gain

How to Find the DC Gain of a Transfer Function

DC gain is the ratio of the steady-state output of a system to its constant input, i.e., steady-state of the unit step response.

To find the DC gain of a transfer function, let us consider both continuous and discrete Linear Transform Inverse (LTI) systems.

Continuous LTI system is given as


(1) \begin{equation*} G(s)=\frac{Y(s)}{U(s)}\end{equation*}

Discrete LTI system is given as

\begin{equation*} G(z)=\frac{Y(z)}{U(z)}\end{equation*}


Use final value theorem to compute the steady-state of the unit step response.


(3) \begin{equation*} L\left ( y_{step(t)} \right )=G(s)\frac{1}{s}\end{equation*}



(4) \begin{equation*}DC\; \; Gain = \lim_{t\rightarrow \infty }y_{step(t)}\end{equation*}



(5) \begin{equation*} DC\; \; Gain = \lim_{s\rightarrow 0 }s\left [ G(s)\frac{1}{s} \right ]\end{equation*}


G(s) is stable and all poles lie on the left hand side

Hence,


(6) \begin{equation*}DC\; \; Gain = \lim_{s\rightarrow 0 }s\left [ G(s)\right ]\end{equation*}

The formula of the final value theorem used for a continuous LTI system is


(7) \begin{equation*}\frac{y(\infty)}{u(\infty)} = G(s)_{s=0}=G(0)\end{equation*}


The formula of the final value theorem used for a discrete LTI system is


(8) \begin{equation*}\frac{y(\infty)}{u(\infty)} = G(z)_{z=1}=G(1)\end{equation*}


In both cases, if the system has an integration the result will be \infty.

The DC gain is the ratio between the steady-state input and the steady-state derivative of the output can be obtained via differentiation of the obtained output. It is nearly same for both continuous and discrete system.

Differentiation in the Continuous Domain

In the continuous system or ‘s’ domain, the equation (1) is differentiated by multiplying the equation by ‘s’.


(9) \begin{equation*}\frac{\dot{Y(s)}}{U(s)}= sG(s)\end{equation*}


where \dot{Y(s)} is the Laplace transform of \dot{y(t)}

Differentiation in the Discrete Domain

Th derivative in the discrete domain can be obtained by a first difference.


(10) \begin{equation*}\dot{y(k)}=\frac{y_{k}-y_{k-1}}{T}\end{equation*}



(11) \begin{equation*}\dot{Y(z)}=\frac{Y(z)-z^{-1}Y(z)}{T}\end{equation*}



(12) \begin{equation*}\dot{Y(z)}=Y(z)\left [\frac{ ^{1-z^{-1}}}{T} \right ]\end{equation*}



(13) \begin{equation*}\dot{Y(z)}=Y(z)\left [\frac{z-1}{T_{z}} \right ]\end{equation*}


Thus to differentiate in the discrete domain, we need to multiply \frac{z-1}{T_{z}}

Numerical Examples To Find DC Gain

Example 1

Consider the continuous transfer function,


  \begin{align*} H(s) =\frac{Y(s)}{U(s)} = \frac{12}{(s+2)(s+10)}\end{align*}


To find the DC gain (steady-state gain) of the above transfer function, apply the final value theorem


  \begin{align*}\lim_{t\rightarrow \infty}y(t)= \lim_{s\rightarrow 0}s\times \frac{12}{(s+2)(s+10)}\end{align*}



  \begin{align*}\lim_{t\rightarrow \infty}y(t)= \lim_{s\rightarrow 0}s\times \frac{12}{2\times 3}=2\end{align*}


Now the DC gain is defined as the ratio of steady state value to the applied unit step input.

DC Gain = \frac{2}{1}=2

Hence it is important to note that the concept of DC Gain is applicable only to those systems which are stable in nature.

Example 2

Determine the DC gain for the equation


  \begin{align*}G(s)=\frac{K}{\tau s+1}\end{align*}


The step response of the above transfer equation is


  \begin{align*}y_{step}(t)=L^{-1}\left [\frac{K}{(\tau s+1)s} \right ]\end{align*}



  \begin{align*}y_{step}(t)=L^{-1}\left [ K\left ( \frac{1}{s}-\frac{\tau }{\tau s+1} \right ) \right ]\end{align*}


Now, apply the final value theorem to find the DC gain.


  \begin{align*}y_{ss}=\lim_{t\rightarrow \infty }y_{step}(t)= \lim_{s\rightarrow 0}\frac{K}{(\tau s+1)s}s = K\end{align*}

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
HECI GCB for Generators – Fast SF6 Circuit Breaker
1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
01/06/2026
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.