Busbars and Connectors in HV and EHV installations

05/23/2025

What is an Electric Busbar?

An electric busbar is a conductor or set of conductors designed to collect electrical power from incoming feeders and distribute it to outgoing feeders. Functionally, it serves as a junction where inflowing and outflowing currents converge, acting as a central hub for power aggregation and distribution.
Outdoor Busbar Installations
In high-voltage (HV), extra-high-voltage (EHV), and outdoor medium-voltage (MV) systems, bare busbars and connectors are typically used, with conductors available in tubular or stranded-wire configurations:
  • Tubular Busbars: Supported by column insulators (usually ceramic), these offer high mechanical strength and superior corona resistance.
  • Stranded-Wire Busbars: Secured with dead-end clamps, ideal for installations requiring large-span flexibility.
(Examples of the above configurations are illustrated in Figures 1 and 2.)
Busbars for Switchgear Installations
Switchgear busbars are typically fabricated from copper, aluminum, or aluminum alloys (e.g., Al-Mg-Si series), with key characteristics of bare busbars including:
  • Geometric Parameters
    • Tubular conductors: Outer diameter and wall thickness
    • Stranded wires: Nominal cross-sectional area
  • Mechanical Properties
    • Tensile/compressive/bending strength
    • Buckling resistance
    • Section modulus and moment of inertia
  • Current-Carrying Capacity
    • Rated current: Determined by material resistivity and heat dissipation conditions.Since bare conductors rely on air insulation, rated voltage is not a primary selection criterion.
Busbar Connection Technology
Dedicated connectors are essential for terminating busbars to equipment, as illustrated in Figure 3. Typical configurations include:
  • Bolted connections: Rigid joints secured by torque-controlled bolts, requiring contact resistance management to prevent overheating
  • Expansion joints: Compensate for thermal expansion, mitigating structural stress concentrations
  • Transition terminals: Address electrochemical corrosion between dissimilar materials (e.g., copper-aluminum interfaces)
Connection design must comply with:
  • Contact area standards for temperature rise (e.g., IEC 61439)
  • Material compatibility treatments (e.g., tin-plating for copper-aluminum transitions)
  • Mechanical stability under short-circuit electro-dynamic forces
Engineering Considerations
Medium/high-voltage switchgear busbar systems require integrated design for:
  • Thermal management: Optimized air convection or forced cooling to control temperature rise
  • Dynamic stability: Structural integrity under short-circuit electrodynamic forces
  • Environmental protection: IP3X or higher ingress protection matching operational environments

These measures collectively ensure reliable power transmission and extended equipment service life.

Widely used in data centers and industrial plants for high-current power distribution, these systems enable flexible layout and easy expansion through modular design.
For copper-copper connections, bronze connectors are used; for aluminium-aluminium connections, aluminium alloy connectors should be applied; and for copper-aluminium connections, bi-metallic connectors are mandatory to prevent corrosion caused by electrolytic effects.
Insulated Busbars & Trunking Systems
In indoor medium-voltage (MV) and low-voltage (LV) installations—particularly where high currents and limited space coexist—busbars are often enclosed in metallic casings for mechanical protection and insulation.This design reduces busbar heat dissipation due to restricted air flow and radiation losses, resulting in current ratings significantly lower than those for free-air installations. Ventilated enclosures can be used to minimize current derating.

Technical Details Analysis

  • Electrochemical Protection for Different Material Connections
    • Copper-copper joints: Bronze connectors (tin bronze or aluminium bronze) enhance contact reliability via solid solution strengthening, preventing pure copper creep relaxation.
    • Aluminium-aluminium joints: 6061-T6 aluminium alloy connectors undergo aging treatment to ensure oxide film stability.
    • Copper-aluminium transitions: Bi-metallic connectors use explosive welding or brazing (e.g., copper-aluminium composite bars) to block electrochemical corrosion paths.
  • Thermal Management Challenges in Enclosed Busbars
    Thermal resistance analysis: Air gaps formed by enclosures reduce thermal conductivity by 30%-50%.
    Compensation solutions:
    • Forced air cooling: Internal fans increase current-carrying capacity by 20%-30%.
    • Enclosure cooling fins: Enhanced surface area for natural convection.
    • High thermal conductivity insulation: Silicone rubber coatings to reduce thermal resistance.
  • Engineering Application Specifications
    • Protection class: Typically IP54 for indoor environments, upgraded to IP65 in humid conditions.
    • Short-circuit withstand: Compliant with IEC 61439 dynamic and thermal stability requirements.
    • Expansion compensation: Expansion joints every 30-50 meters to accommodate thermal deformation.

Widely used in data centers and industrial plants for high-current power distribution, these systems enable flexible layout and easy expansion through modular design.

Isolated Busbars

Isolated busbars typically consist of copper or aluminium flat bars (one or more per phase, sized according to current requirements), with each phase enclosed in a separately earthed sheath. The sheath ends are connected by short-circuit rated bars capable of carrying full fault currents.The sheath primarily prevents inter-phase short circuits. Additionally, it cancels out magnetic fields generated by conductor currents: an equal and opposite current induced in the sheath neutralizes the electromagnetic field almost completely.Common insulating media include air and SF₆.

LV Busbar Trunking Systems
In low-voltage installations, busbar trunking systems offer a cost-effective solution for power distribution, supplying multiple devices and interconnecting switchboards or transformers, as shown in Figure 5.
Busbar Trunking Systems
A busbar trunking system is a pre-assembled configuration housing flat-bar conductors (phase and neutral) within a single metallic enclosure.In feeder trunking systems, power tap-off is achieved via standardized tap-off units, which connect at predefined positions along the trunking. These units enable power extraction through compatible protective devices.
Advantages Over Cable Systems:
  • Cost-Effectiveness & Installation Efficiency
    • More economical for high-current applications: Eliminates the need for parallel single-core cables to meet current ratings, voltage drop, and dip requirements.
    • Reduces overheating risks: Avoids heat buildup in cable bundles that can lead to short circuits.
  • Mechanical Superiority
    • Long-span stability: Requires minimal fixings, reducing installation time.
    • Eliminates cable support structures: Minimizes metalwork requirements.
  • Space & Maintenance Benefits
    • Reduces switchboard termination space.
    • Eliminates cable joints: Lowers contact resistance and failure points.
    • Flexible tap-off design:
      • Accommodates post-installation power changes (within trunking ratings).
      • Enables easy repositioning of distribution points.
      • Facilitates system expansion.
  • Additional Advantages
    • Aesthetic appeal in visible areas.
    • Reusability: Can be dismantled and relocated.
    • Enhanced fire resistance: Metal enclosures contain fire spread.

Hello,I'm Wdwiin. A decade of hands-on experience in electrical engineering, specializing in high-voltage systems, smart grids, and renewable energy technologies. Passionate about technical exchange and knowledge sharing, committed to interpreting industry trends with professional insights to empower peers. Connection creates value—let’s explore the boundless possibilities of the electrical world together!

What is the difference between a dielectric and an insulator?
What is the difference between a dielectric and an insulator?
Dielectrics and insulators are distinguished primarily by their applications. One of the main differences is that a dielectric can store electrical energy by becoming polarized in an electric field, whereas an insulator resists the flow of electrons to prevent current conduction. Other key differences between them are outlined in the comparison chart below.Definition of DielectricA dielectric material is a type of insulator that contains few or no free electrons. When subjected to an electric fi
08/30/2025
What losses occur during operation of the transformer? How to reduce losses?
What losses occur during operation of the transformer? How to reduce losses?
Transformers experience various types of losses during operation, primarily categorized into two main types: copper losses and iron losses.Copper LossesCopper losses, also known as I²R losses, are caused by the electrical resistance of the transformer windings—typically made of copper. As current flows through the windings, energy is dissipated in the form of heat. These losses are proportional to the square of the load current (I²R), meaning they increase significantly with high
Rockwell
08/29/2025
Cable Fault Detection, Testing, Location and Repair
Cable Fault Detection, Testing, Location and Repair
I. Methods for Cable Testing and Inspection:Insulation Resistance Test: Use an insulation resistance tester to measure the insulation resistance value of the cable. A high insulation resistance value indicates good insulation, while a low value may suggest insulation problems requiring further investigation.Voltage Withstand Test: Apply a high-voltage test using a high-voltage tester to verify whether the cable can withstand high voltage under its rated operating conditions. Under normal circums
08/29/2025
Cable Quality Inspection and Cable Detection & Testing
Cable Quality Inspection and Cable Detection & Testing
Power cable quality inspection and cable testing are conducted to ensure that the cable's quality and performance meet specified requirements, thereby guaranteeing the safe and stable operation of power systems. Below are some common contents of power cable quality inspection and cable testing:Visual Inspection: Check the cable surface for physical defects such as damage, deformation, or scratches to ensure the cable's exterior is intact.Dimensional Measurement: Measure dimensional parameters su