Phenomena created during switching of no-load transformers by AIS high voltage disconnect switch

Edwiin
12/04/2024

Introduction to High-Voltage Isolators

  1. Difference Between High-Voltage Circuit Breakers and Earthing Switches

High-Voltage Circuit Breaker (Circuit Breaker) and Earthing Switch are two different mechanical switching devices, each playing a crucial role in power systems.

  • High-Voltage Circuit Breaker: It is primarily used to indicate whether a circuit is open or closed. The circuit breaker has the capability to interrupt current, allowing it to cut off large currents under live conditions and maintain stability when the contact points are separated and a recovery voltage is established. High-voltage circuit breakers are typically used to protect power systems from faults such as short circuits and overloads.
  • Earthing Switch: Its main function is to ground various parts of a circuit, including equipment, ensuring safe contact. An earthing switch does not have the ability to interrupt current, so it cannot be used to cut off load currents. It is usually used in conjunction with a high-voltage circuit breaker to ensure that, after the circuit breaker is opened, all parts of the circuit can be reliably grounded to prevent accidental electric shock.
  1. Operational Limitations of AIS High-Voltage Circuit Breakers

In Air Insulated Switchgear (AIS), a high-voltage circuit breaker cannot interrupt current while conducting or after the contacts are separated and a recovery voltage is established between them. This means that if the circuit breaker operates under live conditions, it can only effectively interrupt small currents. Specifically, when the rated voltage appears across the contacts, the circuit breaker can interrupt small currents but cannot handle high currents or heavy loads.

  1. Function of Earthing Switches

The primary role of an earthing switch is to ground various parts of a circuit, ensuring safety during maintenance or inspection. It can be used in conjunction with a high-voltage circuit breaker or independently. By grounding the circuit, the earthing switch effectively eliminates static charge accumulation, prevents accidental electric shock, and provides safety for subsequent maintenance work.

Overview of Capacitive and No-Load Transformer Switching

  1. Capacitive Current Switching Capability of High-Voltage Circuit Breakers

According to IEC standards, high-voltage circuit breakers are not specifically designed for interrupting fault currents, but since they operate under live conditions, they are expected to interrupt small currents. The IEC definition of isolators (disconnectors) states that a circuit breaker (isolator) can open or close a circuit where negligible current is interrupted or connected, or where the voltage between the terminals of the circuit breaker's poles does not change.

Although not explicitly stated, this description can be interpreted to refer to small capacitive charging currents and loop switching (also known as parallel switching), which in specific applications are called bus transfer switches. IEC 62271-102 confirms this and sets an upper limit of 0.5 A for "negligible" capacitive charging currents, with higher values requiring agreement between the user and the manufacturer.

  1. Rated Bus Transfer Current

According to IEC 62271-102, the rated bus transfer current is specified as follows:

  • For voltage levels 52 kV < Ur < 245 kV, the bus transfer current is 80% of the circuit breaker's rated normal current, but limited to 1600 A.
  • For voltage levels 245 kV ≤ Ur ≤ 550 kV, the bus transfer current is 60% of the circuit breaker's rated normal current.
  • For voltage levels Ur > 550 kV, the bus transfer current is 80% of the circuit breaker's rated normal current, but limited to 4000 A.
  1. Application of No-Load Transformer Switching

In practice, especially in North America, air circuit breakers are commonly used for switching no-load transformers. The magnetizing current of a no-load transformer is typically very low, usually 1 A or less. In this case, the transformer can be represented as a series RLC circuit (as shown in Figure 1), with related oscillations being underdamped, and the amplitude factor being 1.4 or less per unit.

  1. Loop Switching in Parallel Transmission Loops

Another common practice is to extend bus transfer to switching between parallel transmission loops, although the current is lower due to higher loop impedance. This approach can effectively reduce arc generation and voltage fluctuations during switching.

  1. Application of Auxiliary Switching Devices

A widely used practice in North America, but less common in other regions, is the addition of auxiliary switching devices to mitigate the severity of switching events. For example, these devices can minimize the occurrence of restrikes or achieve higher breaking capacity. The use of auxiliary switching devices can enhance system reliability and safety, especially when handling high currents or complex circuits.

No-Load Transformer Switching Using AIS High-Voltage Isolators

For no-load transformer switching in the 72.5–245 kV range, AIS high-voltage isolators are commonly used. Since the magnetizing current of a no-load transformer is typically very low (usually 1 A or less), isolators can safely perform the switching operation. The transformer can be simplified as a series RLC circuit, with related oscillations being underdamped, and the amplitude factor being 1.4 or less per unit.

In this scenario, the primary task of the isolator is to ensure that the transformer's magnetizing current does not cause significant arcing or voltage fluctuations during switching. Through proper design and operation, AIS high-voltage isolators can effectively accomplish this task, ensuring the safe and stable operation of the power system.

 A trace from an actual field-switching event is shown in Fig. 2.

The transient recovery voltage (TRV) across the disconnecting switch is thus the difference between the source voltage and the transformer-side oscillation as illustrated in Fig. 3.

Current Interruption: A Dielectric Event

Current interruption fundamentally occurs when the gap between the contacts becomes sufficiently large to withstand the transient recovery voltage (TRV). This process is inherently a dielectric event, where the insulation strength of the air or vacuum between the contacts surpasses the applied voltage, effectively quenching the arc and interrupting the current flow.

Interrupting the Magnetizing Current of a No-Load Transformer

Interrupting the magnetizing current of a no-load transformer is a repetitive open-close event that can result in multiple restrikes. Each restrike can induce surge currents, which prolong the arc duration, extend the overall switching time, and cause wear on the arc contacts. The repeated nature of these events can lead to significant stress on the switching equipment and potentially degrade its performance over time.

To mitigate these effects, it is crucial to ensure that the switching device is capable of handling the specific characteristics of the magnetizing current, such as its inrush behavior and the associated transient voltages. Proper design and selection of the switching equipment, along with the use of auxiliary devices like surge arresters or damping resistors, can help reduce the likelihood of restrikes and minimize the impact on the system.

Edwiin

Online condition monitoring device (OLM2) on high voltage Circuit Breakers
Online condition monitoring device (OLM2) on high voltage Circuit Breakers
This device is capable of monitoring and detecting various parameters according to the specifications outlined:SF6 Gas Monitoring:Utilizes a specialized sensor for measuring SF6 gas density.Capabilities include measuring gas temperature, monitoring SF6 leak rates, and calculating the optimal date for refilling.Mechanical Operation Analysis:Measures operational times for closing and opening cycles.Evaluates primary contacts separation speed, damping, and contact overtravel.Identifies signs of mec
Edwiin
02/13/2025
Ageing phenomena of current pass blades in high voltage disconnector switch
Ageing phenomena of current pass blades in high voltage disconnector switch
This failure mode has three primary origins:Electrical Causes: The switching of currents, such as loop currents, can lead to localized wear. At higher currents, an electric arc may burn at a specific spot, increasing the local resistance. As more switching operations occur, the contact surface wears down further, causing an increase in resistance.Mechanical Causes: Vibrations, often due to wind, are the main contributors to mechanical aging. These vibrations cause abrasion over time, leading to
Edwiin
02/11/2025
Initial Transient Recovery Voltage (ITRV) for high voltage circuit breakers
Initial Transient Recovery Voltage (ITRV) for high voltage circuit breakers
Transient Recovery Voltage (TRV) stress similar to that encountered during a short-line fault can also occur due to the busbar connections on the supply side of a circuit breaker. This specific TRV stress is known as Initial Transient Recovery Voltage (ITRV). Given the relatively short distances involved, the time to reach the first peak of ITRV is typically less than 1 microsecond. The surge impedance of the busbars within a substation is generally lower compared to that of overhead lines.The f
Edwiin
02/08/2025
Typical transient recovery voltage waveshapes under fault conditions
Typical transient recovery voltage waveshapes under fault conditions
Transient Recovery Voltages (TRVs) caused by fault current interruptions are typically categorized into three types of waveshapes: exponential, oscillatory, and sawtoothed. Additionally, significant TRV conditions can be classified under two main scenarios:Short Circuit Current Interruption: This is the simplest scenario involving the interruption of a symmetrical, rated-frequency short-circuit current. Since this current naturally reduces to zero at least once every half cycle, it represents th