Pangataas nga Voltage sa Pagsugnod (TRV) sa Pag-interrupt sa Gamay nga Inductive Currents niadtong Gi-Interrupt Uban sa Circuit Breakers

Edwiin
Edwiin
Larangan: Switch sa kuryente
China

Pag-analisa sa mga Transient Phenomena sa mga Linear System Gamit ang Principle of Superposition

Sa pag-analisa sa mga transient phenomena gikan sa mga switching operations sa mga linear system, ang principle of superposition usa ka makapanginabang nga kasakyan. Pinaagi sa pag-combine sa steady-state solution nga adunay sa dili pa ang open-circuit operation sama sa mga transient responses nga gipasabot pinaagi sa short-circuit voltage sources ug open-circuit current sources, ug ang pag-consider sa current nga gipasok pinaagi sa switch contacts, makakuha kita og comprehensive description sa switching process.

Transient Analysis sa Open-Circuit Operations

Durante sa open-circuit operation, ang current nga nag-flow sa switch terminals kinahanglan maging zero human sa operasyon. Kini kaya, ang current nga gipasok sa system kinahanglan equal sa current nga nag-flow sa switch terminals dili pa ang opening operation. Human sa switch contacts magsugod mag-separate, immediate na ma-develop ang transient recovery voltage (TRV) sa mga contacts. Ang TRV mahimong visible immediate human ang current mabalhin sa zero ug typical na molabay sa milliseconds sa real-world systems. Sa practical power systems, ang characteristics sa TRV crucial para sa performance ug reliability sa mga circuit breakers.

Importance sa Transient Recovery Voltage (TRV)

Ang thorough understanding sa mga transient phenomena associated sa circuit breaker operations sa power systems makatabang significant sa pag-improve sa testing practices ug enhance sa reliability sa switching equipment. Standards specify recommended characteristic values para sa simulation sa TRV, nga makatabang sa mga engineers mas maayo nga predict ug design ang behavior sa mga switching devices.

Different Types of Circuit Switching

Ang sumusunod nga diagram illustrates ang TRV sa circuit breaker terminals human interrupt ang current sa very simple circuits. Bawat caso resulta sa different waveforms, depende sa nature sa circuit:

  • Resistive Load: Para sa purely resistive loads, ang current drops to zero quickly human ang switching operation, resulting in a relatively smooth TRV waveform.

  • Inductive Load: Para sa inductive loads, ang voltage across the inductor reaches its maximum value when the current becomes zero. Since the inductor stores energy, which needs to be dissipated through other components (such as capacitors), oscillations occur. These oscillations are caused by the energy transfer between the inductor and the capacitor.

  • Capacitive Load: Para sa capacitive loads, ang current gradually decreases human ang switching operation, while the voltage rises rapidly. The TRV waveform typically exhibits a fast-rising voltage pulse.

Small Current Interruption and Current Chopping Phenomena

Sa power systems, ang interruption sa small currents mahimong lead sa phenomena known as current chopping ug virtual chopping. Kini nga mga phenomena adunay significant impacts sa transient recovery voltage (TRV) ug mahimong resulta sa overvoltage ug reignition issues.

Normal Interruption vs. Current Chopping

  • Normal Interruption: When the current is interrupted naturally at its zero crossing point, this is the ideal switching operation. In this case, the TRV typically remains within specified limits, and no overvoltage or reignition occurs.

  • Current Chopping: If the current is interrupted prematurely before it reaches zero, this phenomenon is called current chopping. The sudden interruption of current leads to the generation of transient overvoltages, which can cause high-frequency reignition. This type of abnormal interruption poses potential hazards to the circuit breaker and the system.

Consequences of Current Chopping

When a circuit breaker interrupts the current near its peak, the voltage almost instantly rises. If this overvoltage exceeds the dielectric strength specified for the circuit breaker, reignition occurs. When this process repeats multiple times, the voltage continues to rise rapidly due to high-frequency reignition. This high-frequency oscillation is controlled by the electrical parameters of the associated circuit, the circuit configuration, and the design of the circuit breaker, leading to a zero crossing before the actual power frequency current reaches zero.

Difference Between Current Chopping and Virtual Chopping

  • Current Chopping: Occurs when the current is interrupted before it reaches zero, resulting in transient overvoltage and high-frequency reignition.

  • Virtual Chopping: Happens when the current is interrupted just before it reaches zero, although it is very close to zero. This can still cause minor overvoltage and reignition.

Comparison of Load-Side Voltage and TRV

The following diagram compares the load-side voltage and TRV under two different scenarios:

  1. Interruption at the Current Zero Point: In this case, the load-side voltage rises steadily, and the TRV remains within specified limits, ensuring normal system operation.

  2. Interruption Before the Current Zero Point (Current Chopping): Here, the load-side voltage rises rapidly, and the TRV significantly increases, potentially leading to overvoltage and reignition. It is clear from this example that the second scenario is more severe.

Importance of Understanding Current Chopping

To better understand the impact of current chopping, consider ignoring the effects of load-side losses. After the current is interrupted at the zero point, the energy stored on the load side is primarily in the capacitors, where the voltage reaches its maximum value. However, if the current is chopped before reaching zero, the energy in the capacitors cannot be fully dissipated, leading to a rapid voltage rise and subsequent overvoltage and reignition issues.

(a) Equivalent Circuit. (b) Arc Interruption at Current Zero Point. (c) Arc Interruption Before Current Zero Point.

Current Chopping and High-Frequency Transient Phenomena

In the case of current chopping, the instability of the arc near the current zero point can lead to high-frequency transient currents flowing into adjacent network components. This high-frequency current overlays on the smaller power frequency current, which is effectively chopped to zero. Specifically:

  • Arc Instability Near Current Zero: As the current approaches zero, the arc may become unstable, generating high-frequency transient currents. These currents superimpose on the already small power frequency current, further complicating the system's transient response.

  • Impact of High-Frequency Transient Currents: The presence of high-frequency transient currents can cause overvoltage and reignition, especially in inductive loads. Due to the rapid changes in these currents, they can produce extremely high voltage peaks in a short time, posing a threat to the insulation materials in the system.

Virtual Chopping and Its Effects

In the case of virtual chopping, the arc instability is exacerbated by oscillations with adjacent phases, leading to the generation of high-frequency currents even before the current reaches zero. Specifically:

  • Mechanism of Virtual Chopping: Virtual chopping typically occurs when the current is close to but has not yet reached zero. At this point, the arc may interact with oscillations from adjacent phases, resulting in high-frequency current generation. This further destabilizes the system and increases the risk of reignition.

  • Observed Phenomenon: Virtual chopping has been observed in gaseous arcs in air, SF6, and oil. Vacuum arcs are also highly sensitive to current chopping because the arc in a vacuum environment is more susceptible to external conditions, leading to increased instability.

Causes of Chopping and Reignition

The phenomena of chopping and reignition, along with associated high-frequency oscillatory overvoltages, are primarily attributed to the design of the circuit breaker. Specifically:

  • Design for High Fault Currents: Circuit breakers are typically designed to handle high fault currents. If the design focuses solely on the effective performance for high currents, it may also be equally effective for small currents, attempting to interrupt them before their natural zero crossing.

  • Adverse Consequences: This design approach can lead to current chopping and reignition, resulting in overvoltage and other undesirable effects. For example, overvoltage can damage the system's insulation, leading to equipment failure or shortened lifespan.

Optimizing Circuit Breaker Design

To effectively address both small and large currents, circuit breaker design should incorporate multiple features to ensure reliable performance under various conditions. Specific recommendations include:

  • Balancing Performance for Small and Large Currents: Circuit breaker design should consider both small and large currents, avoiding over-optimization for one type at the expense of the other. For instance, adjusting contact materials, arc extinguishing chamber design, and control strategies can help balance performance across different current levels.

  • Reducing High-Frequency Oscillations: The design should aim to minimize high-frequency oscillations, especially near the current zero point. This can be achieved by introducing appropriate damping elements or optimizing circuit parameters to suppress high-frequency transient currents.

  • Enhancing Insulation Performance: To handle potential overvoltages, the circuit breaker's insulation design should have sufficient dielectric strength. Selecting high-performance insulating materials and optimizing the insulation structure can ensure reliable insulation even under extreme conditions.

Maghatag og tip ug pagsalig sa author
Gipareserbado
Online nga device sa pag-monitor sa kondisyon (OLM2) sa high voltage Circuit Breakers
Online nga device sa pag-monitor sa kondisyon (OLM2) sa high voltage Circuit Breakers
Kini nga device makapahimulos ug mabiling sa pipila ka mga parametro batas sa gipangutana nga mga espesipikasyon:Paghimolus sa Gas SF6: Nagamit og espesyal nga sensor para sa pagsukol sa gas density sa SF6. Ang mga kapabilidad nimo maglakip sa pagsukol sa temperatura sa gas, pagbantay sa rate sa pag-leak sa SF6, ug pagkalkula sa optimal nga adlaw para sa refilling.Analisis sa Operasyon sa Mekaniko: Nagsukol sa oras sa operasyon para sa closing ug opening cycles. Nag-evaluate sa primary contacts
Edwiin
02/13/2025
Pungtaas nga pankasyon sa mekanismo sa pagoperar sa mga circuit breakers
Pungtaas nga pankasyon sa mekanismo sa pagoperar sa mga circuit breakers
Ang anti-pumping function usa ka importante nga katangian sa mga control circuit. Wala niini nga anti-pumping function, asumahan nato nga ang user mag-connection og maintained contact sa closing circuit. Kon ang circuit breaker mag-close sa usa ka fault current, ang protective relays will promptly trigger a tripping action. Apan, ang maintained contact sa closing circuit will attempt to close the breaker (usa pa) sa fault. Kini nga repetitive ug dangerous nga proseso gitawag og “pumpin
Edwiin
02/12/2025
Pagkakasira sa mga blades nga nagpasa og kuryente sa high voltage disconnector switch
Pagkakasira sa mga blades nga nagpasa og kuryente sa high voltage disconnector switch
Ang kasinatian kini adunay tulo ka pangunang pinaka-ugmad: Electrical Causes: Ang pagbago sa current sama sa loop currents makapadako og lokal nga pagkasira. Sa mas taas nga current, ang electric arc matabangan og specific spot, nagsulob sa lokal nga resistance. Kon mas daghan pa ang switching operations, ang contact surface mas matapos pa, nagdako ang resistance. Mechanical Causes: Ang vibrations, kasagaran gikan sa hangin, mao ang pangunang contributor sa mechanical aging. Kini nga mga vibrati
Edwiin
02/11/2025
Unang Transyente sa Pagkuha Balik Voltage (ITRV) para sa mataas na kuryente circuit breakers
Unang Transyente sa Pagkuha Balik Voltage (ITRV) para sa mataas na kuryente circuit breakers
Ang stress sa Transient Recovery Voltage (TRV) sama sa natukod sa usa ka short-line fault mahimong mogamit usab tungod sa mga koneksyon sa busbar sa supply side sa circuit breaker. Kini nga partikular nga TRV stress gitawag og Initial Transient Recovery Voltage (ITRV). Tungod sa relatyibong mauswagon nga distansya, ang oras aron mabaton ang unang peak sa ITRV kasagaran mas gamay sa 1 microsecond. Ang surge impedance sa mga busbar sa usa ka substation kasagaran mas baba kaysa sa overhead lines.An
Edwiin
02/08/2025