What are the polarity test methods for GIS current transformers?

Oliver Watts
07/07/2025

I’m Oliver, an 8 - year current transformer testing pro. Today, let’s break down new and old polarity test methods for GIS current transformers—how they work and their pros/cons.
1.Testing Methods
1.1New Method
  • Pre - test ops: Open FDS21/FDS22 fast disconnectors + DS23 disconnector. Close CB21 breaker, then ES21/ES22 grounding disconnectors. Disconnect ES21’s SF6 - shell ground.
  • Wiring: Connect battery between ES21’s moving contact (negative grounded) + ground electrode. This lets current flow L1→L2 in TA’s primary coil. Wire K1 (CT secondary) to DC milliammeter +ve, K2 to - ve.
  • Test: Use DC method—apply DC to primary, check milliammeter deflection. Use ≤100mA range (100μA best for clear deflection). Briefly connect/disconnect ES21’s moving contact + K - battery +ve. Positive deflection (battery on) + negative (battery off) means L1 (CT) and K1 (secondary) are same polarity. Note CT primary coil positions; draw results.

1.2 Old Method

  • Pre - test ops: Close FDS21/FDS22 disconnector, matching disconnector. Open ES21/ES22 grounding disconnectors. Close CB21 breaker.
  • Wiring: Connect battery +ve to 110kV inlet bushing (Ⅰ/Ⅱ), - ve to GIS outlet bushing. Briefly connect/disconnect. Positive deflection (on) + negative (off) means L1/K1 are same polarity. Note CT positions; draw results.

2 Method Comparison

  • New: Simple wiring/ops, low energy loss, works with small batteries. Milliammeter deflects sharply—high sensitivity, accurate.
  • Old: Complex steps, long wires—troublesome on - site. High - altitude risks (battery wiring on bushings). More series components → high impedance → unstable results. Often needs big batteries (rare on - site), risking wrong calls.
3. Safety Must - Dos
Follow strict sequence: Keep CB21 open → open FDS21/FDS22 (line) + DS23 (bus) → close ES21/ES22 (grounding). Critical for live lines/buses—avoids “live + ground disconnector” accidents.
4. Wrap - Up
The new method solves on - site polarity testing pain points, ensures relay protection works, and stabilizes grids. After 8 years in testing, I swear: choosing the right method balances safety + efficiency. 
Oliver Watts

Hey! I'm Oliver Watts, an electrical engineer in Inspection and Testing. With years of hands - on experience, I ensure electrical systems meet top safety and performance standards. Using advanced gear, I conduct diverse tests, easily spotting issues in both large - scale industrial and small - scale commercial setups. I love teaming up, sharing knowledge, and keeping up with industry regs. Also, I'm skilled at data analysis with software. If you're into electrical inspection or just want to chat engineering, reach out. Let's connect and explore!

A Quick Verification Method for Low-Voltage Current Transformers
A Quick Verification Method for Low-Voltage Current Transformers
To ensure safe operation of the power system, power equipment operation must be monitored/measured. General devices can’t connect to primary high - voltage equipment directly; instead, large primary currents are scaled down for current transformation, electrical isolation, and use by measurement/protection devices. For AC large - current measurement, conversion to a unified current eases secondary instrument use.Current transformers split into measurement - and protection - type, with accu
Oliver Watts
07/16/2025
What Tests Are Required for a Qualified AIS Voltage Transformer?
What Tests Are Required for a Qualified AIS Voltage Transformer?
Hey everyone! I’m Oliver, an experienced electrician with over a decade in the power system industry. Today, we’re diving into a practical topic — what tests are required to ensure an Air Insulated Switchgear (AIS) voltage transformer is qualified? These tests are crucial not only for ensuring the device operates correctly but also for maintaining the safety and stability of the power grid. Let’s get started!1. Visual InspectionFirst Look MattersThe very first step is a v
Oliver Watts
07/14/2025
What Tests Must a Qualified AIS Current Transformer Undergo?
What Tests Must a Qualified AIS Current Transformer Undergo?
Hey everyone, I’m Oliver, a 10-year veteran in the power system industry. Today we’re going to talk about a very practical topic — how do you know if a current transformer (CT) used in Air Insulated Switchgear (AIS) is truly qualified? This isn’t just about meeting technical specs; it’s directly tied to equipment safety, grid stability, and accurate metering.Let’s dive in — based on my real-world experience.IntroductionIn substations or distribution syst
Oliver Watts
07/12/2025
What are the routine tests for outdoor voltage transformers?
What are the routine tests for outdoor voltage transformers?
1. IntroductionOutdoor voltage transformers are key equipment for ensuring the safety of electrical apparatus. Scientific and comprehensive test analysis is required to avoid hazards and property losses caused by improper operation. Test analysis can guide the formulation of operation strategies and precautions, ensure the stable operation of equipment, and maximize economic and social benefits.2. Concept of Outdoor Voltage TransformersAn outdoor voltage transformer is essentially an outdoor ste
Oliver Watts
07/10/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!