• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Primum 252 kV IEE-Business mixtum aerem duorum interruptorum GIS productum in China cum successu transivit testem on-site potestatis ferquentiae sustinendae.

Baker
Baker
Campus: Nuntii
Engineer
4-6Year
Canada

Nuper fabricantes Chini apparatus GIS annuntiaverunt novitatem exultantem: primus productus ZF11C-252(L) duplex interruptor GIS mixto-gas, a fabricante Chino GIS conflatum, successu primum in loco experimentum tenacitatis tensionis frequentiae communi superavit. Hoc factum alium miliarium lapidem designat ad progressum viridis et optime qualitatis fabricatoribus Chinois apparatus GIS.

ZF11C-252(L) duplex interruptor GIS mixto-gas, quod experimentum superavit, repraesentat coronam innovationis technologicae a fabricantibus Chinois apparatus GIS. Per formulam gas mixti diligenter optimizatam, hic productus utilem SF₆ gas valde minuit, effectu restringendo emissiones gasum effectorum hothouse et ostendens fortiter commitmentum responsabilitatis ambientalis fabricantis. Ad stabilia characteristica gasea et insulativam fortem confirmantes, team R&D investigationes extensas et experimenta severa de parametri claves gas mixti fecerunt, garantientes productum excellentem performance et latam applicabilitatem.

GIS.jpg

Notabiliter, designum duplex interruptor huius producti est responsum innovativum ad recentissimas exigentias ab State Grid Corporation of China et China Southern Power Grid Company. Hic design non solum permittit expansionem et experimentum GIS sine interruptione operationis aequipmenti existentis (Phase I), sed etiam substantiale meliorat fiabilitatem et securitatem aequipmenti. Interruptor duplex 252 kV habet currentem nominalem usque ad 4,000 A et currentem brevem temporalem nominalem 50 kA, occupans spatium idem ac bays consuetudinariae—garantens integrationem perfectam cum systemis existentibus et praebens supportum robustum ad upgrades grid.

GIS..jpg

Perfectio experimenti tenacitatis tensionis in loco primo tentamine potens testimonium est de capacitate technica fabricatorum Chinois apparatus GIS et significat breakthrougem majorem in applicationibus gas mixtis et technologia interruptoris duplex. Hoc achievement non solum ditat portefeuille productorum GIS fabricantis et fortificat competitivitatem eius in mercato apparatorum switchgear altae tensionis, sed etiam contributum significativum ad developmentem novi systematis electricitatis Sinensis facit.

Prospiciendo, fabricantes Chini apparatus GIS perseverabunt in commitmento ad innovationem technologicam, focalizando in transformatione viridi et low-carbon apparatorum switchgear altae tensionis et continuando augmentando core competitiveness suam.

Donum da et auctorem hortare
Suggestus
Testing Methods for Newly Installed 35 kV GIS Gas-Insulated Switchgear
Testing Methods for Newly Installed 35 kV GIS Gas-Insulated Switchgear
GIS (Gas-Insulated Switchgear) offers advantages such as compact structure, flexible operation, reliable interlocking, long service life, maintenance-free operation, and small footprint. It also possesses many irreplaceable advantages in insulation performance, environmental friendliness, and energy saving, and is increasingly applied in industrial and mining enterprises, airports, railways, subways, wind power stations, and other fields.A certain enterprise’s 35 kV indoor substation was origina
Oliver Watts
11/18/2025
Analysis and Handling of a Breakdown Discharge Fault in a 550 kV GIS Disconnector
Analysis and Handling of a Breakdown Discharge Fault in a 550 kV GIS Disconnector
1.Description of the Fault PhenomenonThe disconnector fault in a 550 kV GIS equipment occurred at 13:25 on August 15, 2024, while the equipment was operating under full load with a load current of 2500 A. At the moment of failure, the associated protection devices acted promptly, tripping the corresponding circuit breaker and isolating the faulty line. System operating parameters changed significantly: the line current dropped abruptly from 2500 A to 0 A, and the bus voltage instantly decreased
Felix Spark
11/17/2025
Impact Analysis of GIS Disconnector Operations on Secondary Equipment
Impact Analysis of GIS Disconnector Operations on Secondary Equipment
Impact of GIS Disconnector Operations on Secondary Equipment and Mitigation Measures1.Impacts of GIS Disconnector Operations on Secondary Equipment 1.1Transient Overvoltage Effects During opening/closing operations of Gas-Insulated Switchgear (GIS) disconnectors, repeated arc reignition and extinction between contacts cause energy exchange between system inductance and capacitance, generating switching overvoltages with magnitudes 2–4 times the rated phase voltage and durations ranging from tens
Echo
11/15/2025
Hitachi Energy to deliver the world’s first 550kV SF6-free eco-efficient GIS.
Hitachi Energy to deliver the world’s first 550kV SF6-free eco-efficient GIS.
Hitachi Energy recently announced it will supply State Grid Corporation of China’s Central China Branch with the world’s first 550 kV SF₆-free GIS. This groundbreaking innovation marks a significant milestone in grid decarbonization and contributes to China’s commitment to achieving carbon neutrality by 2060.State Grid Corporation of China is the world’s largest power grid operator, serving 88% of China’s territory and over 1.1 billion people. As a leader in the energy sector, State Grid activel