Alternating single-phase
Ib = (Fc * P) / (U0 * cosφ)
Ib = (Fc * S) / U0
Alternating two-phase
Ib = (Fc * P) / (U * cosφ)
Ib = (Fc * S) / U
Alternating three-phase
Ib = (Fc * P) / (√3 * U * cosφ)
Ib = (Fc * S) / (√3 * U)
S = √(P² + Q²)
Where:
Ib = Operating current (A)
Fc = Coincidence factor
S = Apparent power (VA)
P = Active power (W)
Q = Reactive power (VAr)
U0 = Voltage [L-N] (V)
U = Voltage [L-L] (V)
cos φ = Power factor
Calculate the operating current (Ib) of electrical equipment based on active power, voltage, power factor, and coincidence factor—essential for sizing cables, breakers, and protection devices in AC systems.
This tool helps engineers, electricians, and designers determine the actual running current under real-world conditions, including multiple loads with varying usage patterns.
Single-phase, two-phase, and three-phase AC systems
Standard voltages (e.g., 230V L-N, 400V L-L)
Custom voltage input
Adjustable power factor (cosφ)
Adjustable coincidence factor (Fc) for group load estimation
Input via active power (P) or apparent power (S)
Single-phase:
I b = (F c × P) / (U 0 × cosφ)
I b = (F c × S) / U 0
Two-phase:
I b = (F c × P) / (U × cosφ)
I b = (F c × S) / U
Three-phase:
I b = (F c × P) / (√3 × U × cosφ)
I b = (F c × S) / (√3 × U)
Apparent Power:
S = √(P² + Q²)
Ib: Operating current (A)
Fc: Coincidence factor (0–1)
P: Active power (W)
Q: Reactive power (VAr)
S: Apparent power (VA)
U0: Line-to-neutral voltage (V)
U: Line-to-line voltage (V)
cosφ: Power factor (0.1–1.0)
Three-phase system, 400 V (L-L), 10 kW, PF = 0.85, F c = 1.0
→ Operating current ≈ 19.5 A
Electrical Design: Size conductors, circuit breakers, and fuses based on actual load demand.
Panel Load Calculation: Estimate total current for multiple devices using coincidence factor.
Energy Audits: Convert nameplate data into real-world current draw.
Renewable Integration: Calculate inverter output current with partial load factors.
Educational Use: Teach students about AC power relationships and load diversity.
Electrical engineers designing LV distribution systems
Electricians installing motors, pumps, or HVAC systems
Maintenance technicians troubleshooting overloads
Facility managers planning upgrades or expansions
Students learning AC power fundamentals
Operating current (Ib) is the actual current drawn by equipment during normal operation, adjusted for load diversity using the coincidence factor.
Because not all loads operate at full capacity simultaneously. For example, a factory may have 10 motors, but only 7 run at once → use Fc = 0.7 to avoid over-sizing circuits.
No—this calculator is designed for AC systems only. For DC, use I = P / V (no √3 or power factor).
Use typical values: 0.8–0.9 for motors, 0.95–1.0 for resistive loads (heaters, lighting). You can adjust it to see how current changes.