Description
Calculate the operating current of electrical equipment based on active power, voltage, efficiency, and power factor.
Supports:
- Single-phase and three-phase systems
- Standard voltages (400V/230V, 690V/400V, etc.)
- Custom voltage input
- Adjustable efficiency and power factor
- Coincidence factor
Key Formula
I = P / (√3 × V × η × cosφ)
Where:
P: Active power (kW)
V: Line voltage (V)
η: Efficiency
cosφ: Power factor
Example
Three-phase system, 400V, 10kW, η=0.9, PF=0.85
→ Operating current ≈ 19.5 A