Calculate neutral current in 3-phase systems with unbalanced loads using phase A, B, C currents. No harmonics assumed. Compliant with NEC 220.61 & IEC 60364.
Calculate the neutral current in a three-phase, four-wire system based on unbalanced phase currents. This tool uses vector summation principles for linear loads only, assuming no harmonic distortion.
The neutral current is calculated using the following formula:
IN = √(IA2 + IB2 + IC2 - IA×IB - IB×IC - IC×IA)
Where:
Note: This formula applies to sinusoidal, linear loads with 120° phase separation. It does not account for harmonic currents, which can significantly increase neutral current.
Scenario: A commercial building has the following phase currents:
Calculation:
I_N = √(10² + 5² + 2² - 10×5 - 5×2 - 2×10)
= √(100 + 25 + 4 - 50 - 10 - 20)
= √(59) ≈ 7.68 A → Rounded to 7.7 A
This means the neutral conductor must carry ~7.7 A continuously. If not sized correctly, it may overheat or trip protective devices.
| Industry | Application |
|---|---|
| Commercial Buildings | Panelboard neutral sizing for lighting and outlets |
| Industrial Facilities | Feeder design for mixed motor and control loads |
| Data Centers | Assessing neutral current in UPS distribution |
| Residential | Verifying service entrance neutral capacity |
| Education | Teaching three-phase system behavior |
For unbalanced linear loads without harmonics, use: I_N = √(I_A² + I_B² + I_C² - I_A×I_B - I_B×I_C - I_C×I_A). This accounts for phase angles and vector addition. In balanced systems, I_N = 0.
Neutral current carries the imbalance between phases. If too high, it can overheat conductors, trip breakers, or cause voltage drop—especially in lighting or IT systems where loads are often unbalanced.
Without a neutral connection, phase voltages become unbalanced, potentially causing equipment damage or malfunction. The neutral ensures stable voltage across single-phase loads.
No. This tool assumes linear loads with no harmonics. For non-linear loads (e.g., VFDs, LED drivers), triplen harmonics (3rd, 9th, etc.) add in phase on the neutral—can cause up to 1.7× total load.