Key attributes

Brand ROCKWILL
Model NO. DS6B 126kV 145kV 252kV 420kV 550kV High voltage disconnect switch trader
Rated voltage 252kV
Rated normal current 2000A
Rated frequency 50/60Hz
Rated peak value withstand current 125kA
Rated short-time withstand current 50kA
Series DS6B

Product descriptions from the supplier

Description

Product introduction:

DSDS6B Switch Disconnector is a kind of outdoor HV electricity transmission equipment’s at three-phase AC frequency of 50Hz/60Hz. It is used for breaking or connecting HV lines under no loads so that these lines can be changed and connected and the way the electricity runs is changed, In addition, it can be used to exercise safe electrical insulation for such HV electric

apparatuses as bus and breaker. The switch can open and close inductance/capacitance current and is able to open and close the bus to switch current.

This product is of the single-post bi-arm vertical telescope type (scissor-type) and suitable for the bus's Switch Disconnector. It can be laid out directly under the bus, thus occupying a small area. It’s effect of saving energy can be prominent at the substation where double bus lines are accompanied by the bypass bus.

The Switch Disconnector is accompanied by a JW10 earthing switch which will be used for the bus grounding at the lower layer, The grounding of the bus line at the upper layer requires the use of an independent earthing switch. 363kV and 550Kv Switch Disconnector and earthing switch are equipped with the SRCJ8 motor actuator for the single pole operation. Meanwhile, the tri-pole linkage can be achieved. The 126kV and 252kV Switch Disconnector adopt SRCJ3 motor-based actuator to realize the tri-pole linkage. The earthing switch adopts SRCS manual actuator to actualize tri-pole linkage.

This Switch Disconnector has passed the verification by the review procedure organized by China Machinery industry federation that the product structure and performance satisfy the requirements on perfection, and product's performance indices have reached the internally level of the same kinds of products

DS6B Switch Disconnector comprises three single poles and actuator. Each single pole is made of a base, post insulator, operating insulator and conducive part., The conductive pat includes the gear box and foldable conductive am fixed on the top of the post insulator, and the fixed contact hanging on the overload bus.

The actuator dives the operating insulator, and through the four link lever-driven scissor-type conductive arm, lift and lower the insulator to tighten or separate the moving contact and fixed contact on the directly overhead bus line, to open or close the Switch Disconnector. After the closing, a vertical insulating break will be formed.

Main characteristic:

  • Superior conductance system; With open structure, conductor is laid out in the middle of the transmission base while the main rod and reverse connecting rod are installed outside. Balancing spring is sealed with aluminum cover and transmission parts needing debugging are exposed for easy installation and debugging. dust prevention. Add a dustcover to bearing and adopt seal structure externally.

  • Contact forceps can cover a large area of rated contact, This product is in the double arm telescopic (scissor-type) structure. The forceps of the moving contact cover a large area of rated contact, particularly applicable to soft bus line, and also to hard bus line.

  • Open gear box, which has a good visibility, is convenient for installation, debugging and maintenance. The main crank arm is combined with operating flange to reduce he transmission link and the height of transmission base, which can improve the transmission efficiency and reliability. The rotation shat is designed as double bearing structure so that the transmission is flexible and reliable.

  • Structural design: the separation of machines from power. The design concept is the separation of machines from power, that is, the conductive elements, springs and mechanic driving elements are mutually isolated to prevent current from passing through springs and mechanical driving elements. in this way, the stability of the driving elements can be enhanced.

  • Provide one key sequential control "double confirmation" function expansion.

Main technical parameters:

Among these voltage levels 225kV/230kV/330kV/345kV disconnect switches, the rated short-circuit breaking current is 63kA, and customization is available.

NO

Specifications

Unit

Value

1

Product model


DS6B-126D

DS6B-145D

DS6B - 252D

DS6B - 420D

DS6B-550D

Rated voltage

kV

126

145

252

420

550

3

1min power frequency withstand voltage (r.m.s)

Phase to phase to earth

kV

230

275

460

520

740

Across isolating distance

kV

230(+70)

315

460(+145)

610

740(+315)

4

Lightning impulse withstand voltage (peak 1.2/50μs)

Phase to phase to earth

kV

550

750

1050

1425

1675

Across isolating distance

kV

550(+100)

750

1050(+200)

1425(+240)

1675(+450)

5

Rated frequency

HZ

50/60

6

Rated current

A

2000/3150

2000/3150

2000/2500/3150/4000/5000

4000

4000

7

Rated short - time withstand current (r.m.s)

kA

50

104

125/160

164

160

8

Rated peak withstand current

kA

125

104

50/63

63

63

9

Rated short - circuit withstand time

S

3

3

3

2

3

10

Wiring terminal static mechanical load -

Longitudinal

N

1250

1250

2000

4000

4000

Horizontal

N

750

800

1500

2000

2000

Vertical

N

1000

1000

1250

1500

2000

11

Creepage distances

mm

3150,3906

3625,4495

6300,7812

10500,13020

13750

12

Mechanical life

Times

10000

13

Motor operating mechanism

Model

SRCJ7

SRCJ3

SRCJ8

14

Motor voltage

V

AC380/DC220

15

Control circuit’s voltage

V

AC220/DC220/DC110

16

Opening/closing time

S

12±1

16±1

17

Manual operating mechanism

Model

SRCS

18

Electromagnetic lock’s voltage

V

AC220/DC220/DC110

 

Order notice 

Product model, rated voltage, rated current, rated short-lime withstand current and creepage distance must be specified at the goods-ordering time;

It must be decided whether a earthing switch should be attached to the Switch Disconnector;it must be decided whether the upper bus line of the Switch Disconnector is soft or hard.

Additionally, the external diameter of the tubular busbar shall be specified;

It must be decided whether the Switch Disconnector is arranged in cross-over or parallel form;

The actuator's model and name, motor's voltage, control voltage and the number of contacts for auxiliary switch

 

FAQ
Q: How do these 550kV disconnectors (Siemens, Hitachi, GE, and Pinggao) perform in terms of key electrical parameters such as rated voltage, rated current, and withstand current?
A:

Basic Electrical Parameters

  • Rated Voltage: All four models from Siemens, Hitachi Energy, GE, and Pinggao are rated for 550 kV.

  • Rated Current: The Siemens, Hitachi, and Pinggao models are rated for 4000A. The GE PKG Gen3-550 offers a higher rated current of 5000A, making it suitable for applications with higher power flow requirements.

  • Short-Circuit Withstand: All models demonstrate identical performance, with a short-time withstand current of 63 kA for 3 seconds.

  • Peak Withstand Current: All models share the same peak withstand current rating of 171 kA.

Q: What are the interlocking regulations for bypass disconnectors in thermal power plants and substations?
A:
 The interlocking regulations for bypass disconnectors in thermal power plants and substations are as follows:
  • The bypass disconnector of each line can only be operated when the bypass circuit breaker is open and its bypass bus disconnector is closed. For the operation of the line bypass disconnector, it can only be operated when its outgoing line earthing switch is open.
  • The bypass bus-side disconnector of the bypass circuit breaker can only be operated when the bypass circuit breaker is open and the disconnector connected for bus tie operation is open.
  • The earthing switch on the bypass bus side of the bypass circuit can only be operated when the disconnector on the bypass bus side of the bypass circuit breaker is open.
  • The earthing switch on the bypass circuit breaker side of the bypass circuit can only be operated when the bypass circuit breaker and its bypass bus-side disconnector are open, and the disconnector connected for bus tie operation is open.
Know your supplier
Online store
On-time delivery rate
Response time
100.0%
≤4h
Company overview
Workplace: 108000m²m² Total staff: 700+ Highest Annual Export(usD): 150000000
Workplace: 108000m²m²
Total staff: 700+
Highest Annual Export(usD): 150000000
Services
Business Type: Design/Manufacture/Sales
Main Categories: High Voltage Electrical Apparatus/Electric transformer
Whole life care manager
Whole-life care management services for equipment procurement, use, maintenance, and after-sales, ensuring safe operation of electrical equipment, continuous control, and worry-free electricity consumption.
The equipment supplier has passed platform qualification certification and technical evaluation, ensuring compliance, professionalism, and reliability from the source.

Related Products

Related Knowledges

Related Solutions

Haven't found the right supplier yet? Let matching verified suppliers find you. Get Quotation Now
Haven't found the right supplier yet? Let matching verified suppliers find you.
Get Quotation Now
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.