DS23B 126kV 145kV 225kV 230kV 252kV 363kV 420kV 550kV High voltage disconnect switch with Anti-Corrosion Technology

  • DS23B 126kV 145kV 225kV 230kV 252kV 363kV 420kV 550kV High voltage disconnect switch with Anti-Corrosion Technology

Key attributes

Brand ROCKWILL
Model NO. DS23B 126kV 145kV 225kV 230kV 252kV 363kV 420kV 550kV High voltage disconnect switch with Anti-Corrosion Technology
Rated voltage 550kV
Rated normal current 5000A
Rated frequency 50/60Hz
Rated peak value withstand current 160kA
Rated short-time withstand current 63kA
Series DS23B

Product descriptions from the supplier

Description

Product introduction

We are China's first source factory specializing in high-voltage disconnectors.DS23B high-voltage Isolating Switch is a kind of outdoor HV electricity transmission equipment at three-phase AC frequency of 50Hz/60Hz. It is used for breaking or connecting HV lines under no loads so that these lines can be changed and connected and the way the electricity nuns is changed. in addition, it can be used to exercise safe electrical insulation for such HV electric apparatuses as bus and breaker. The switch can open and close inductance/capacitance current and is able to open and close the bus to switch current.

This product is in the double-post horizontal telescopic structure, with the plug-type contact. Ater the opening, a horizontal insulating break will be formed. The product can be used as an disconnect switch at the 110kV to 550kV substation. The JW10 earthing switch can be attached at one or two sides, When two GW23B disconnect switches are combined into a fixed contact, half of the line for a switch can be cut of and the land coverage can be saved. 363kV and 550kV disconnect switch and earthing switch are equipped with the SRCJ8 motor actuator the single pole operation. Meanwhile, the tri-pole linkage can be achieved The 126kV and 252kv disconnect switches adopt SRCJ7 and SRCJ3 motor-based actuators to realize the tri-pole linkage. The earthing switch adopts CS11 and SRCS manual actuators to actualize tri-pole linkage.

This high-voltage Isolating Switch has passed the verification by the review procedure organized by China Machinery Industry Federation that the product structure and performance satisfy the requirements on perfection, and product's performance indices have reached the internally level of the same kinds of products."

DS23B high-voltage Isolating Switch comprises three single poles and actuator, Each pole consists of a movable side post and a fixed side post. The movable side post is made up of a base, post insulator, operating insulator, foldable conductive tube; while the static side post comprises a base, post insulator and static contact.

The actuator drives the operating insulator, and through the link lever, brings the foldable conducive tube to extend horizontally to plug the moving contact into or extract it out of the fixed contact so that the isolating switch can be opened or closed. After the opening, a horizontal insulating break will be formed.

Main characteristic

  • Superior conductance system: The conductive part made of Al-alloy of high conductance rate is characteristic of good conductance, high mechanical strength, light weight and strong corrosion resistance. The current will pass through the foldable area of the conductive arm via soft connection (without any movable contacts) to ensure reliable conductance, few maintenance, no examination, and long-term reliable operation.

  • State -of-art structure: The switch disconnector is in the single-arm, foldable and telescopic structure, The driving elements and balancing springs are sealed within the conductive tube to reduce their adverse effects on natural environment and render the appearance compact and simple. The drive base adopts a link lever, Compared with angular wheels, the product is simpler and easier to adjust

  • Simple and superior grounding switch363kV earthing switch is in the single-arm standing and openable structure, with the structurally simple plug-type contact. The conductive rod for grounding will move in two steps at the moments of opening and closing. At the moment of opening, the conductive rod will rotate vertically and rise up to the static contact, and then automatically plug itself into the star-shaped contact. By doing so, the contact will be made reliable and be able to sustain heavy short-circuit current.

  • Plug-type contact: The moving contact is the plug-type and has the self-cleaning ability. One end of the U-shaped finger of 126kV and 252kV fixed contact is fixed onto the contact base, forming a fixed connection and ensuring the reliable conduction; while the other end will produce contact pressure on the moving contact as a result of the influence of external spring and the own elastic force of the con-tact finger, and the gripping force will automatically increase when the short-circuit current passes through the contact. The contact spring is made of stainless steel and is equipped with insulating gasket. The spring will not corrupt nor shunt. The arc contact can be mounted onto the movable and fixed contacts to enable the disconnect switch to switch current, capacitive and inductive cur-rent by opening and closing bus line.

  •  Provide one-key sequential control "double confirmation" function expansion.

Main technical parameters:

   Among these voltage levels 225kV/230kV/245kV/275kV/330kV/345kV/400kV/765kV non-standard custom manufacturing disconnector switch , the rated short-circuit breaking current is 63kA, and customization is available.

NO

Specifications

Unit

Value

1

Product model

 

DS23B-126D

DS23B- 145D

DS23B - 252D

DS23B- 363D

DS23B - 420D

DS23B - 550D

2

Rated voltage

kV

126

145

252

363

420

550

3

1min power frequency withstand voltage (r.m.s)

 

Phase to phase to earth

kV

230

275

460

510

520

740

Across isolating distance

kV

230 (+70)

315

460 (+145)

510 (+210)

610

740 (+318)

4

Lightning impulse withstand voltage(peak 1.2/50μs)

Phase to phase to earth

kV

550

650

1050

1175

1425

1675

Across isolating distance

kV

550 (+100)

750

1050

1175 (+200)

1425 (+295)

1675 (+450)

5

Rated frequency

HZ

50/60

50/60

50/60

50/60

50/60

50/60

6

Rated current

A

2000/3150/4000

2500

2000/2500/3150/4000/5000

4000/5000

3150

4000/5000

7

Rated short - time withstand current (r.m.s)

kA

50

50

50/63

63

63

63

8

Rated peak withstand current

kA

125

125

125/160

160

160

160

9

Rated short - circuit withstand time

S

3

3

3

3

2

3

10

Wiring terminal static mechanical load

Longitudinal

N

1250

1250

2000

2500

4000

4000

Horizontal

N

750

800

1500

2000

1600

2000

Vertical

N

1000

1000

1250

2000

1500

2000

11

Creepage distances

mm

3150, 3906

3625, 4495

6300, 7812

9450

10500, 13020

17050

12

Mechanical life

Times

10K

10K

13

Motor operating mechanism

Model

SRCJ7

SRCJ7

SRCJ3

SRCJ2

14

Motor voltage

V

AC380/DC220

15

Control circuit's voltage

V

AC220/DC220/DC110

16

Opening/closing time

S

12±1

16±1

17

Manual operating mechanism

Model

SRCS

 

18

Electromagnetic lock's voltage

V

AC220/DC220/DC110

     

 

Order notice :

Product model, rated voltage, rated current, rated short-time withstand current and creepage distance must be specified at the goods-ordering time;

It can be decided whether a earthing switch should be attached to the switch disconnector;

It must be decided whether the upper bus line of the switch disconnector is soft or hard. Additionally, the external diameter of the tubular busbar shall be specified;

It must be decided whether the disconnect switch is arranged in cross-over or parallel form;

The actuator's model, motor's voltage, control voltage and the number of contacts for auxiliary switch.

 

FAQ
Q: For a 110kV system whose main wiring adopts a sectionalized single busbar with a bypass circuit breaker, which of the following statements about the interlocking of the bypass disconnector is correct?
A:
  • The earthing switch on the bypass bus side of the bypass circuit must be operable only when the disconnector on the bypass bus side of the bypass circuit breaker is open.
  • The bypass bus disconnector of the circuit breaker must be operable only when the circuit breaker is open and the sectionalizing disconnector connecting the disconnector to the busbar is open.
Q: Which manufacturer models are recommended for 500kV substation projects?
A:

For 500kV substation projects, the following high-performance disconnectors are recommended:

  • Rockwill Electric: DS23B-550D/5000, offering high cost-effectiveness with high rated current, strong withstand capability, long mechanical lifespan, and reliable insulation performance, suitable for stable operation in high-voltage scenarios.

  • Pinggao Electric: GW27-550(W)/4000, suitable for high-current applications with excellent pollution resistance.

  • China XD Electric: GW28-550/4000, featuring a robust structure and adaptability to high voltage levels.

  • Siyuan Electric: GW28-G-550/4000, an improved design with optimized transmission mechanisms for enhanced operational reliability.

  • Shandong Taikai: GW27-550(W)/4000, providing cost-effectiveness and extensive engineering application support.

Comparison Points:

  • Rated Current: All recommended models support 4000A (except Rockwill's 5000A), meeting the requirements of 500kV substations.

  • Environmental Adaptability: The "W" suffix in Pinggao and Taikai models indicates specialized suitability for heavily polluted areas.

  • Intelligent Features: The "G" suffix in Siyuan products denotes support for advanced smart monitoring functions.

Q: 225kV/230kV/245kV all fall into the medium-high voltage category. What are their core differences?
A:

The main differences lie in rated voltage calibration and insulation level requirements. 245kV is closer to the standard 252kV class, while 225kV/230kV are mostly customized for regional needs to match specific power grid loads.

Know your supplier
Online store
On-time delivery rate
Response time
100.0%
≤4h
Company overview
Workplace: 108000m²m² Total staff: 700+ Highest Annual Export(usD): 150000000
Workplace: 108000m²m²
Total staff: 700+
Highest Annual Export(usD): 150000000
Services
Business Type: Design/Manufacture/Sales
Main Categories: High Voltage Electrical Apparatus/Electric transformer
Whole life care manager
Whole-life care management services for equipment procurement, use, maintenance, and after-sales, ensuring safe operation of electrical equipment, continuous control, and worry-free electricity consumption.
The equipment supplier has passed platform qualification certification and technical evaluation, ensuring compliance, professionalism, and reliability from the source.

Related Products

Related Knowledges

Related Solutions

Haven't found the right supplier yet? Let matching verified suppliers find you. Get Quotation Now
Haven't found the right supplier yet? Let matching verified suppliers find you.
Get Quotation Now
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.