145kV HV Gas-Insulated Switchgear (GIS)

  • 145kV HV Gas-Insulated Switchgear (GIS)

Key attributes

Brand ROCKWILL
Model NO. 145kV HV Gas-Insulated Switchgear (GIS)
Rated voltage 145kV
Rated normal current 3150A
Series ZF28
Place of Origin Zhejiang, China

Product descriptions from the supplier

Description

Product overview
ZF28-145 type GIS is composed of standard modules through same sized flanged joint, which can  meet the demand for substation optimization design through the flexible combination between modules. It saves space and conforms to technical requests.

This product can be applied to power system, power generation, rail transportation, petrochemical, metallurgy, mining, building materials and other large industrial consumer.

Features and advantages of the product

  •  Special arc extinguish chamber design with spring operation mechanism;

  • The structure is tight and the minimum interval width can reach 800mm;

  • Full three phase encapsulated;

  • Self-developed 3 position isolated grounding switch;

  • Completely self-research and development with high starting point and large investment;

  • Inspected to be qualified by KEMA High level of parameters, advanced structural design;

  • Insulation level is higher than IEC and GB standards;

  • Self-blast combined interrupter, 3-position disconnector and earthing switch, spring operating mechanism;

  • Double sealing ring structure;

  • Minimum area;Compact and standardized module design with minimum intervals width 800mm;

  • It is applied to cold, humid, salt fog, coastal, high altitude areas;

  • Spring operating mechanism base processed by  Four Axis Milling CNC Machining Center imported from DMG, German;

  • Basin-type produced by  vacuum epoxy casting Production line imported from Germany  Hubers;

Technical Parameter

ZF28A-145.png

 

Documentation Resource Library
Restricted
ZF28 HV Gas-Insulated Switchgear (GIS)
Catalogue
English
Consulting
Consulting
FAQ
Q: What is the insulation principle of gas-insulated switches?
A:

Insulation Principle:

  • In an electric field, the electrons in SF₆ gas molecules are slightly displaced from the nuclei. However, due to the stability of the SF₆ molecular structure, it is difficult for electrons to escape and form free electrons, resulting in high insulation resistance. In GIS (Gas-Insulated Switchgear) equipment, the insulation is achieved by precisely controlling the pressure, purity, and electric field distribution of the SF₆ gas. This ensures a uniform and stable insulating electric field between the high-voltage conductive parts and the grounded enclosure, as well as between different phase conductors.

  • Under normal operating voltage, the few free electrons in the gas gain energy from the electric field, but this energy is not sufficient to cause collision ionization of the gas molecules. This ensures the maintenance of the insulating properties.

Q: What are the characteristics of GIS equipment?
A:

Due to the excellent insulation performance, arc extinguishing performance and stability performance of SF6 gas, GIS equipment has the advantages of small footprint, strong arc extinguishing ability and high reliability, but the insulation ability of SF6 gas is greatly affected by the uniformity of the electric field, and it is easy to have insulation abnormalities when there are tips or foreign objects inside the GIS.

GIS equipment adopts a fully enclosed structure, which brings the advantages of internal components without environmental interference, long maintenance cycle, low maintenance workload, low electromagnetic interference, etc., while also having problems such as complex single overhaul work and relatively poor detection methods, and when the closed structure is eroded and damaged by the external environment, it will further bring a series of problems such as water ingress and air leakage.

Q: What are the core differences in application between HGIS and traditional AIS/GIS?
A:

The core difference lies in the scenario adaptability brought by the "hybrid application of insulating media": ① Compared with fully gas-insulated GIS, HGIS connects via air-insulated busbars, reducing reliance on a fully enclosed gas environment. It has more advantages in scenarios where installation space is relatively sufficient but the volume of core components needs to be controlled; ② Compared with fully air-insulated AIS, the core functional modules of HGIS adopt gas insulation, resulting in a more compact structure. It is suitable for scenarios with limited floor space (such as urban substations and offshore platforms) and reduces the impact of the external environment on core components.

Know your supplier
Online store
On-time delivery rate
Response time
100.0%
≤4h
Company overview
Workplace: 108000m²m² Total staff: 700+ Highest Annual Export(usD): 150000000
Workplace: 108000m²m²
Total staff: 700+
Highest Annual Export(usD): 150000000
Services
Business Type: Design/Manufacture/Sales
Main Categories: High Voltage Electrical Apparatus/Electric transformer
Whole life care manager
Whole-life care management services for equipment procurement, use, maintenance, and after-sales, ensuring safe operation of electrical equipment, continuous control, and worry-free electricity consumption.
The equipment supplier has passed platform qualification certification and technical evaluation, ensuring compliance, professionalism, and reliability from the source.

Related Products

Related Knowledges

Related Solutions

Haven't found the right supplier yet? Let matching verified suppliers find you. Get Quotation Now
Haven't found the right supplier yet? Let matching verified suppliers find you.
Get Quotation Now
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.