• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


How to Handle Overheating of Busbar Isolating Switches

Felix Spark
Field: Failure and maintenance
China

Overheating of Busbar Isolating Switches: Causes and Handling Procedures

Overheating of busbar isolating switches is a common electrical equipment defect. If not addressed promptly, the situation can severely deteriorate during a system short circuit—when high short-circuit current flows through the overheated point, potentially causing contact melting or even destruction of the switch.

Isolating Switch..jpg

When overheating of a busbar isolating switch is detected, follow these steps for safe handling:

  • Report the defect to the grid dispatcher and request load reduction to lower the current through the affected circuit.

  • If a bypass busbar is available, use the bypass circuit breaker to take over the load, allowing the overheated busbar isolating switch to be taken out of service.

  • If conditions permit, energize a standby line, open the circuit breaker of the faulty line, and then open the overheated busbar isolating switch for maintenance.

  • If neither bypass operation nor de-energization is possible, apply the following measures based on the busbar configuration:

    • For single-busbar configurations:
      Minimize the load current in the affected circuit as much as possible. Improve cooling conditions (e.g., by installing temporary forced ventilation fans), enhance real-time monitoring, and coordinate with the dispatcher to create conditions for an early outage and repair.

    • For double-busbar configurations:
      Reconfigure the system operation mode—close the spare busbar isolating switch and open the faulty (overheated) one to isolate it from service. Ensure that bus differential protection and non-selective switching logic remain correctly configured and functional during the transition.

Give a tip and encourage the author!

Recommended

Impact of DC Bias in Transformers at Renewable Energy Stations Near UHVDC Grounding Electrodes
Impact of DC Bias in Transformers at Renewable Energy Stations Near UHVDC Grounding ElectrodesWhen the grounding electrode of an Ultra-High-Voltage Direct Current (UHVDC) transmission system is located close to a renewable energy power station, the return current flowing through the earth can cause a rise in ground potential around the electrode area. This ground potential rise leads to a shift in the neutral-point potential of nearby power transformers, inducing DC bias (or DC offset) in their
01/15/2026
HECI GCB for Generators – Fast SF6 Circuit Breaker
1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
01/06/2026
Distribution Equipment Transformer Testing, Inspection, and Maintenance
1.Transformer Maintenance and Inspection Open the low-voltage (LV) circuit breaker of the transformer under maintenance, remove the control power fuse, and hang a “Do Not Close” warning sign on the switch handle. Open the high-voltage (HV) circuit breaker of the transformer under maintenance, close the grounding switch, fully discharge the transformer, lock the HV switchgear, and hang a “Do Not Close” warning sign on the switch handle. For dry-type transformer maintenance: first clean the porcel
12/25/2025
How to Test Insulation Resistance of Distribution Transformers
In practical work, insulation resistance of distribution transformers is generally measured twice: the insulation resistance between thehigh-voltage (HV) windingand thelow-voltage (LV) winding plus the transformer tank, and the insulation resistance between theLV windingand theHV winding plus the transformer tank.If both measurements yield acceptable values, it indicates that the insulation among the HV winding, LV winding, and transformer tank is qualified. If either measurement fails, pairwise
12/25/2025
Send inquiry
+86
Click to upload file

IEE Business will not sell or share your personal information.

Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.